Welcome to Interactive Power Flow!

Interactive Power Flow (IPF) is a software package for doing power flow studies. IPF models the operation of a bulk electric power network. It can be used to:

  • Investigate bulk electric power networks

  • Determine bus voltage distribution

  • Study real and reactive power flows in lines

  • Evaluate line overloads

  • Plan area interchange control

  • Determine transformer tap settings

  • Determine remote-bus voltage controls

  • Plan for system reactive power requirements

  • Determine effect of load shedding, generator dropping, and line outages

  • Run transient stability studies on generator rotor dynamics

_images/IPF_GUI.png

Interactive Power Flow X Window GUI

Electric power system network design encompasses the following tasks:

  • Determination of load centers and generation patterns as well as sizes of loads and generation.

  • Determination of available transmission corridors (rights-of-way) and assessment of the capacity of these corridors to accommodate transmission lines.

  • Evaluation of existing or planned networks with regard to adequate power-carrying capability, voltage regulation, reliability of service, and operating economics.

  • Determination of size and routing of new transmission lines, and size and location of terminal equipment for achieving efficient and economical reinforcements when needed.

  • Evaluation of proposed reinforcements in light of power flow capability, ability to withstand transient disturbances, reliability of overall service, economics, impact on regional economy, environment, energy conservation and operational constraints such as construction lead times, coordination of various facility ownership interests, flexibility for future growth and compatibility with other long-range plans.

The dynamic nature of load growth, load distribution, and generation patterns make the problem of network design one of planning. To plan for the future, power system planners and design engineers must look at the past and present. This makes Interactive Power Flow a great tool for the network design engineer, but it can also be used by students for academic studies. IPF models the complex network structure and can evaluate it at various points in time.

Features

Interactive Power Flow has the following high level feature set:

Contents

Installation

IPF is installed by compiling from source. This is probably easiest using the Docker approach outlined below, but compiling manually from source is also an option.

Docker

You can use docker to build and run this project. Just build the container:

$ git clone https://github.com/mbheinen/bpa-ipf-tsp
$ cd bpa-ipf-tsp
$ docker build -t bpa-ipf-tsp .

Then run it using interactive -i and tty -t option. The container will run bpf by default so once the container is started you can just type the name of the file in the data directory that you’d like to run (e.g. bench.pfc):

$ docker run -it --rm bpa-ipf-tsp
 BPA POWER FLOW PROGRAM VERSION:IPF  327
 Enter Power Flow Control (PFC) file name > bench.pfc

Otherwise start an interactive tty with bash to run other processes.

$ docker run -it --rm bpa-ipf-tsp bash
[root@e9d28ac4f070 data]# bpf bench.pfc
[root@e9d28ac4f070 data]# tsp bench.fil

Compiling Manually

If Docker isn’t an option, compile manually. The majority of this codebase is written in Fortran with some C so both Fortran and C compiler are needed in order to compile it. Also, note that to this point it has only been test compiled on CentOS/RHEL 7 (gcc 4.8.5) and Ubuntu 20.04 (gcc 9.4.0). Pull Requests are welcome if you want to try a different platform or run into issues on another platform and want to fix something!

Install the build tool (CMake), compilers, and dependencies (Motif X Window):

CentOS/RHEL

$ yum install cmake gcc gcc-gfortran motif motif-devel

Ubuntu

$ apt-get install cmake gcc gfortran libmotif-dev libxmu-dev

Then you’re ready to compile. This project uses CMake. CMake is a multi-platform build tool that can generate build files for many different target platforms. CMake recommends doing “out of source” builds, that is, the build files and artifacts are separated from the source files. This is convenient when doing development because there is no need to clean out compiled stuff (e.g. object files, libraries, executables, etc.) from the source tree. To do this, you create a build/ directory at the top level of the project and everything gets built there. This allows you to just delete the build/ directory when you’re done.

Doing a checkout and compile of this repository is done as follows:

$ git clone https://github.com/mbheinen/bpa-ipf-tsp
$ cd bpa-ipf-tsp
$ mkdir build
$ cd build
$ cmake ..
$ make
$ sudo make install

After running these commands, you will see the library binaries in a lib/ directory and the executables in a bin/ directory. The sudo make install command will also place the binaries in /usr/local/bin, which should be in your path.

Debug

To build with debug symbols, do cmake -DCMAKE_BUILD_TYPE=Debug .. instead of cmake ...

Testing

You can run the test suite after compiling by running ctest -C <Build Type>`:

$ ctest -C Release

Overview

You can interact with IPF using the Command Line Tools (bpf, ipfbat, ipfcut, etc.), the X Window Graphical Interface (gui) or the CFLOW C API (libcflow). Many of the functions and features of the command line tools are available through specially designed GUI features. The GUI simplifies creating network data, running the base case solutions, and graphically visualizing the network diagrams.

IPF Interaction Model

The conceptual model of IPF is quite simple. You load power system network data into IPF; the IPF solution “engine” performs the calculations for the solution, and then outputs this solution data.

IPF offers different approaches to accomplish power system solutions. Their style of interaction and processing are quite different.

  • The batch power flow (e.g. bpf or ipfnet) approach. This is an Input-Process-Output approach. You write a command file containing all of the “orders” that you want filled, and the program performs the actions it determines are necessary to produce the ordered results.

  • The Graphical User Interface (GUI) approach. This is command oriented - you click a button or enter a command, and it is executed immediately by the backend power flow engine (ipfsrv).

  • The CFLOW approach (the C API called libcflow). This is a programming based approach where you write C code to interact with IPF.

Two Domain Specific Languages (DSLs) called Powerflow Command Language (PCL) and Power Flow Control (PFC) allow users to define the “scenarios” or “orders”. PCL is directly available through a Command Dialog window in the X Window GUI and can be used with the ipfbat program. PFC is used with the bpf program. See Power Flow Control (PFC) for details of the PFC syntax and Powerflow Command Language (PCL) for details of the PCL sytanx.

Note

The PFC syntax was developed first and later Bonneville Power Administration (BPA) added the PCL syntax. They referred to PCL as the “new style”, and the PFC as the “old style”. These two sets of commands are not completely compatible even though the “new style” command set and syntax is closely modeled on the “old style.”

The bpf Batch Approach

When you use bpf, you must first create a Powerflow Command Language (PCL) file with the appropriate commands to accomplish the solution task at hand. At runtime these commands are accepted by ``bpf``and executed according to a logical processing order determined by the program. Hence you need not be concerned with the ordering of commands in your PFC file. Input commands will be processed first, and a solution done automatically before any output is produced. Finally, a new base file will be created, if you have requested one. See PFC Examples for examples of PFC files.

_images/BPF_Information_Flow_Model.png

BPF Information Flow Model

The ipfbat Batch Approach

ipfbat allows you to interact with the solution “engine” (ipfsrv) without the GUI. You first create a PCL file with the appropriate commands, in the right order, to accomplish the solution task at hand. At runtime these commands are interpreted by ipfbat. The PCL file commands are processed sequentially. Additional PCL command files may be specified by name, so that a “chain” of PCL files may be processed in one run.

The GUI Approach

When you use the GUI approach, you use an X Window graphical interface with dialog boxes, menus, windows, etc. This makes data input, output, and manipulation easy. In addition to allowing basic case solution tasks to be accomplished, certain specialized tasks such as line impedance calculations are available. See Calculating Line Impedance for details. However, for more involved tasks, you’ll need to use the bpf approach. For information about how to work with the GUI dialog boxes, menus, windows, etc., see X Window Graphical Interface (gui). That section also has a tutorial to show you how to solve straightforward power system cases.

_images/PCL_Information_Flow_Model.png

PCL Information Flow Model

The core powerflow engine (ipfsrv) can be ran on separate machine from the graphical user interface. These two (gui and ipfsrv) processes are joined by interprocess communication (IPC) routines that shuttle data and instruction messages back and forth between the GUI and powerflow program using sockets. ipfsrv serves primarily as a solution and data engine that sends and receives data when requested by the user through the GUI.

The CFLOW Approach

Many times users need to do a large number of similar runs or they need to process data from another system or set of files before running studies. CFLOW is a C library API (libcflow) for IPF. To use CFLOW, you write a C program, including the header file cflowlib.h, which defines all the structures, unions, and functions which allow access to the powerflow input and solution. To retrieve solution values, you call various CFLOW functions. The API interacts with ipfsrv interally. This allows you to do things like ask for a new solution, change the model, etc. See CFLOW C API (libcflow) for details on the API and examples.

Executables

IPF consists of many executable programs. Several of the most common executables are briefly described below.

bpf

Command line program that performs power flow. bpf is the batch form of the powerflow program and unlike ipfsrv it doesn’t use socket communication to interact with the powerflow engine. Rather it uses direct code library linking. It allows one or more scenarios to be defined in input files and run all at once via a call to bpf from a command line terminal. It executes using the commands from a Power Flow Control (PFC) file. Example usage: bpf bench.pfc. The PFC commands (i.e. the content of the .pfc file) used with bpf allow for complete power flow runs including defining the network model and commands to perform various operations. The Record Formats section describes the network model records available and the Power Flow Control (PFC) section describes the PFC syntax and commands available. More documentation about this program is in bpf section.

gui

Launches the Graphical User Interface program built with `Motif X Window`_ that works in conjunction with the power flow server, ipfsrv. When the editing and displaying of buses and branches is being handled by the gui process, the work of calculating solution voltages for a given power system network is done by ipfsrv, which is just the bpf program in a different guise. More documentation about this program is in X Window Graphical Interface (gui) section.

ipfsrv

The power flow service daemon which runs as the backend component of the gui. It executes Powerflow Command Language (PCL) commands through scripts dispatched from the gui. See ipfsrv for more details.

ipfbat

Command line program that is the batch version of ipfsrv. It accepts a Powerflow Command Language (.pcl) file. Plotting can be done with a control file; however, for most plots ipfplot is easier to use. Example of use: ipfbat bench.pcl. The PCL commands used with ipfsrv and ipfbat are described in Powerflow Command Language (PCL).

ipfcut

Command line program that cuts out a subsystem from a solved base case file (.bse). Flows at the cut branches are converted into equivalent generation or load on specially formatted +A continuation bus records (read more about Continuation Bus Data (+)). An ensuing power flow run should solve with internal branch flows and bus voltages which are identical to those quantities in the original base case. More documentation about this program is in ipfcut section. Several methods are available to define the cut system: bus names, zones, base kVs, and individual branches. A pi-back feature replaces selected buses with a passive-node sequence (lines consisting of sections) with the original loads pi-backed in proportion to the line admittances.

ipfplot

Command line plotting program to produce printed maps in batch. The program accepts a coordinate file (.cor) and a base case file (.bse) on the command line, as well as an optional second base case file. When the second base case file is specified, a difference plot is produced. You can also use ipfplot to produce bubble diagrams. The same coordinate files are used for both gui and ipfplot, but not all capabilities are available in gui. Documentation is in Network Diagrams. More documentation about this program is in ipfplot section.

tsp

Command line program that performs transient stability studies. Users specify power system network distrubances (line faults, generator trips), and the program simulates the affects on power system dynamics including key data points like generator rotor angle. This tool can be used to evaluate short term (on order of seconds to minutes) affects of these disturbances. Example of use: tsp bench.fil. More documentation about this program is in Transient Stability Program (tsp) section.

ipfnet

The command line batch version of the “save netdata file” command built into the gui / ipfsrv. This program generates a WSCC-formatted network data file in any of the following dialects: BPA, WSCC, or PTI. “Dialects” means that the file is still WSCC, but the data is generated with special processing or restrictions and is destined for use with other programs. In the case of the PTI dialect, that data is preprocessed by the PTI-proprietary conversion program WSCFOR. Detailed documentation is in ipfnet.

ipf_reports

The command line report tool to create output reports and summaries from solved base cases (.bse). Enter ipf_reports from the command line and follow the prompts.

ips2ipf

The program that converts a network data file from WSCC’s Interactive Powerflow System (IPS) format to IPF format. Duplicate buses are renamed; Load Tap Changer (LTC) steps are converted to taps, shunt susceptance on slack and BQ buses are transferred to +A records; sectionalized lines containing a section 0 are renumbered 1, 2, … ; BX, X, and remote controlled bus data are converted to IPF format, etc. Documentation is in IPS IPF Differences.

Network Data

A core component to any power system analysis problem is the power system network (the interconnected lines, generators, loads, transformers, nodes/buses, breakers, and other components). In IPF, this is referred to as Network Data. Network Data defines the structure (connectivity) and properties (base voltage, real power injections, real and reactive power loads, transformer tap settings, etc.) of the power system network. This data is defined in files that contain bus (nodes) and branch (lines, transformers, etc.) records. Most of the input files are ASCII text files. But one important file, the base case file (.bse), is in binary format. You can, of course, edit ASCII text files with any text editor. This is often done, but your data integrity is safer if you do all the editing you can in the GUI. The base case binary file cannot be edited with an ordinary text editor, but can in effect be edited via the GUI when you have a base case file loaded.

There are multiple methods for specifying the Network Data. The following is a list of the various methods with descriptions.

.pfc

This input file contains job control information for the bpf program. This file may contain Network Data explicitly (listing out Record Formats right in the file), but more often includes a property called NETWORK_DATA that specifies a file containing the Record Formats in ASCII format. Alternatively, users can specify a property called OLD_BASE that specifies a base case (.bse) file, or other job control data to be described. Keeping the Network Data out of the .pfc file allows more clear separation between the commands of the batch study and the network model.

You can edit this file using any ASCII text editor to add, modify, and delete commands and data records. See PFC Examples for examples.

NETWORK_DATA

This ASCII text input file consists of area, bus, and branch records. It must not contain modification records.

This file can be maintained by using an ASCII text editor. Or you can edit the records you want in the GUI through the various dialog boxes and then save a new NETWORK_DATA file. In the file, data records may be in random order, but actual processing is done in the following order:

  1. Area interchange records.

Each area record identifies a composition of zones whose member (associated) buses define specific aggregate quantities that may be controlled to specified export values.

A (Area interchange records)

I (Area intertie records)

  1. Bus data record group containing at least two records.

Each bus data record identifies one bus in the network. Buses are uniquely identified by their bus name and base kV.

B (Bus records)

+ (Continuation bus records)

X (Switched Reactance records)

Q (PQ Curve data records)

  1. Branch data record group containing at least one record.

L (AC or DC Transmission line records)

E (Equivalent Branch records)

T (Transformer records)

R (Regulators (Automatic or LTC transformer) records)

Branch data entered in any of the ASCII files is single-entry or one-way only. This means, for example, that a branch connecting buses A and B has a user-submitted entry (A,B) or (B,A) but not both. The program transposes the record internally as required during execution. Normally which way the branch is entered does not matter, but it does affect the default end metered on a tie line, and the physical position of line sections. See Record Formats, for a discussion of this feature.

Branches are uniquely identified by three fields:

  • Their terminal bus names and base kVs.

  • Their circuit or parallel ID code.

  • Their section code.

BRANCH_DATA

This ASCII text input file contains the branch data of all branches coded with in-service date and out-of-service date. This file is searched for branches in service on the date requested. bpf selects the appropriate branches.

NEW_BASE

This program-generated, binary output file contains complete base network data and steady-state operating values for the case being processed. This file is identical in format to the OLD_BASE file. NEW_BASE simply designates the file when it is produced as the output from a recently concluded case study. See The BASE (.bse) File section for more details on this file.

OLD_BASE

This program-generated, binary input file contains complete base network data and steady-state operating values. This file is identical in format to the NEW_BASE file. OLD_BASE simply designates the file when it functions as an already existing input file. See The BASE (.bse) File section for more details on this file.

CHANGE

This ASCII text input file contains changes (new and modification records) to the data input from any combination of NETWORK_DATA, BRANCH_DATA, and OLD_BASE files making up the case to be studied. These change records change the input data for the base case.

Printout File .pfo

This is an ASCII text output file that contains bus, branch, and solution data from a completed case study and is intended for ordinary, paper hardcopy output.

Microfiche file .pff

This is a special format output file that contains bus, branch, and solution data from a completed case study and is intended for microfiche format.

IPF Input/Output Files

File

Format

Input/Output (I/O)

Created by

Editing

Information Contained

.pfc

ASCII

bpf (I)

User

Yes

Bus, Branch, Commands, File Names

.pcl

ASCII

gui, ipbat (I)

User

Yes

Commands, File Names

NETWORK_DATA

ASCII

bpf (I) GUI,IPFBAT (I/O)

User gui ipfnet

Yes

Bus, Branch

BRANCH_DATA

ASCII

Input Only

User

Yes

Branch

OLD_BASE .bse

Binary

Input Only

IPF

No

Bus, Branch, Solution Values

CHANGES

ASCII

Input or Output

User gui

Yes

Bus, Branch, Modifications

NEW_BASE .bse

Binary

Output Only

IPF

No

Bus, Branch, Solution Values

Printout file (<name>.pfo)

ASCII

Output Only

bpf

No

Input Data and Solution Reports, User Analysis

Microfiche file (<name>.pff)

ASCII

Output Only

bpf

No

Input Data and Solution Reports, User Analysis

Debug file (<name>.pfd)

ASCII

Output Only

bpf

No

Solution arrays and iteration processing

Printout file (<logon>.pfo)

ASCII

Output Only

gui

No

Messages, Iteration Summary

Debug file (<logon>.pfd)

ASCII

Output Only

gui

No

Solution arrays and iteration processing

The BASE (.bse) File

This file, designated OLD_BASE if you are loading it, or NEW_BASE if you are saving it, is binary in format and contains the following data:

  • The case identification, project ID, and two header records.

  • The date the case was generated.

  • The program version used to generate the file (so future program versions can read the file if file structures change).

  • Up to 100 comment records.

History

IPF was developed by Bonneville Power Administration (BPA) and its contractors in the 1990s with about 20% of the cost supported by the Electric Power Research Institute (EPRI). By mutual agreement, as described in EPRI Agreement RP2746-03 entitled Graphical User Interface for Powerflow, March, 1992,

“all results of this project–including the computer program and its documentation–are to be in the public domain.”

In a separate Memorandum of Understanding with the Western Systems Coordinating Council (WSCC), BPA agreed in March, 1992, to

“keep WSCC informed of progress, to make its best effort to develop the program according to the Guidelines adopted by the WSCC Computer Program Management Subcommittee, and to make the final results available for possible further development by WSCC.”

Prior to the development of the Interactive Power Flow in the 1990s, BPA had developed the core power flow program and a set of tools they called the Power System Analysis Package (PSAP), which were a collection of Fortran-coded computer programs permitting the analysis of the steady-state operation of an electric power network. PSAP was developed over a 20-year period and many features were added during this time. Since the core power flow code was developed in 70s and 80s, it had to make efficient use of computer memory space and computation time, the core engine uses traditional techniques of large power system analysis including the Newton-Raphson method of solution of algebraic equations and sparse matrix computation techniques.

The Western Systems Coordinating Council (WSCC) now known as the Western Electricity Coordinating Council (WECC) had a similar set of tools known as Interactive Powerflow System (IPS) complete with a Domain Specific Language called Computationally Oriented Programming Environment (COPE) for defining power flow studies in a programmatic way. Many of the features and data record formats for IPF, especially for transient stability, were influenced by WSCC’s IPS.

These programs were designed for character-based terminals connected to mainframes. However, the 1980s and 90s saw the creation and maturation of graphical user interfaces (GUI) based on the mouse, windows, and menus. These components were generally available on the Macintosh computer since 1984 and on IBM PC-compatible computers as an option since 1987. The third most popular GUI in the 90s was the one associated with the X Window System. GUIs were more intuitive and easier to use than character/keyboard-based interfaces. Starting in 1991, BPA began a two-way joint development of a GUI interface for the powerflow program, based upon the X-Window System and the Motif X Window GUI. The joint partners were the Electric Power Research Institute EPRI and WSCC. The powerflow program itself was also restructured and enhanced in the process, and a libcflow library was added as a means to provide users API access to the IPF functions for use in other programs.

The Bonneville Power Administration (BPA) Transient Stability Program was developed in accordance with specifications written by the Western Systems Coordinating Council (WSCC), now known as the Western Electricity Coordinating Council (WECC), and was originally written to be executed on a VAX 11/780 computer. With some exceptions this program closely paralleled the program used in Salt Lake City by the WSCC Technical Staff in the 1980s.

A copy of the original WSCC specifications for both power flow and transient stability can be found in WSCC Specifications.

The difference between this version of the program (i.e. tsp) and the one used in Salt Lake City was the control record requirements for defining the problem such as where the fault is applied, line switching, etc., and the format for all output options. The formats for almost all other intput data requirements maintain strict compatibility between the two programs. Therefore, with grateful acknowledgements to the WSCC Staff, a substantial portion of the materials used in this documentation are reproduced copies taken from the WSCC Program Manual.

Acknowledgement is given to Teshmont Consultants, Inc. of Winnipeg, Manitoba for their many corrections and additions to the transient stability code.

Original License

Below is a copy of the original license notice from BPA.

The BPA Powerflow software (IPF) is Public Domain; here is a copy of the License.

IMPORTANT NOTE:
IPF is in the public domain and certain conditions apply. The terms in which
it is released are described in the section "Notice to Non-BPA Users" in
each of the IPF manuals.

NOTICE TO NON-BPA USERS:
The Bonneville Power Administration (BPA) releases BPA-developed computer
programs under the following conditions:

1. BPA does not charge for program development costs; however, a fee to cover
   costs incurred in answering inquiries is assessed against the organization
   receiving the material. This fee typically includes costs for personnel
   and computer resources, reproduction, shipping, and postage.

2. BPA cannot provide assistance with conversion to other computers or
   consulting services to the program users.

3. In consideration of receipt and acceptance of these programs or portions
   thereof, if sold, assigned, or transferred to another organization, you
   and your organization agree to advise any third-party recipient in writing
   that the program(s) and/or documentation are in the public domain and
   available from BPA. The intent of this agreement is to ensure that
   BPA-developed or supplied programs, and/or documentation, whether in
   whole or in part, that are in the public domain, are identified as such
   to recipients.

"LEGAL NOTICE"

Neither BPA nor any person acting on behalf of BPA:

1. Makes any warranty or representation, expressed or implied, with respect
   to the accuracy, completeness, or usefulness of the information contained
   in this report, or that the use of any information, apparatus, method, or
   process disclosed in this report may not infringe upon privately owned
   rights; or

2. Assumes any liability with respect to the use of, or for damages resulting
   from the use of any information, apparatus, method or process disclosed in
   this report.

9/20/95

In keeping with the license, please know that original code is in public domain. Also, you should be able to obtain the original code released by BPA by contacting Bonneville Power Administration . However, for your convenience the v0.0.1 release of this project contains the original code released by BPA.

Original Contributors

The original project is the result of a lot of hard work from engineers at BPA and EPRI. These include, but are not limited to:

  • Dan L. Clark

  • Jay G. Coleman

  • Tsu-huei Liu

  • Walter L. Powell

  • Bill E. Rogers

  • William D. Rogers

  • K E Rowell

  • John L Rutis

  • David M Stefonik

  • D M Syzmanski

Application Examples

Introduction

Some typical power system design application examples are given in this section to demonstrate possible applications of the core power flow programs IPF provides. Each example indicates possible uses of the program relative to some stated network planning objectives.

Setting Up a Network Data File

Use the following values for this four-bus network:

_images/Four_Bus_Network.png

Four Bus Network

Line Data

  • Use 100 MVA, 500 kV base.

  • X = .525 ohm/mile, X/R = 18.

  • B/2 = .01024 pu/mile, where B is the total line charging and B/2 is equal to \(B_{pi}\), if long-line effect is ignored.

  • Current Rating is 3000 amps.

Transformer Data

  • X = 20% (0.20 pu) on 525 kV, 1770 MVA base.

  • Transformer Taps = 22 kV, 525 kV.

Generator Data for Power Flow

  • P(max) = 1770MW, P(g) = 1680 MW.

  • Q(lim) = +/- 521MVAR.

  • Type G bus controlling voltage of GEN HI to 1.08 pu.

Station Service Load

  • 190 + j95 (constant power for stability).

Approach The preparation of the network data will be presented in the following steps:

  1. Prepare the bus data group.

    Define the following buses:

    GEN 22
    GEN HI 500
    INF BUS 500
    MID 500
    
    1. Data for GEN 22

    Record Type:     B
    Sub Type:        G
    Change Code:     blank
    Owner:           blank (not specified)
    Name:            GEN
    kV:              22
    Zone:            blank (not specified)
    Load P MW:       190
    Load Q MVAR:     95
    Shunt Load MW:   blank (or zero)
    Shunt Load MVAR: blank (or zero)
    P MAX:           1770
    P GEN MW:        1680
    Q MAX MVAR:      521
    Q MIN MVAR:      -521
    V MAX PU:        blank (not specified)
    V MIN PU:        blank (not specified)
    Remote Bus Name: GEN HI
    Remote Bus kV:   500
    % VARS Supplied: blank (defaults to 100)
    
    1. Data for GEN HI 500

    Record Type:     B
    Sub Type:        C  (remotely controlled)
    Change Code:     blank
    Owner:           blank
    Name:            GEN HI
    kV:              500
    Zone:            blank
    Load P MW:       blank  (or zero)
    Load Q MVAR:     blank  (or zero)
    Shunt Load MW:   blank
    Shunt Load MVAR: blank
    P MAX:           blank
    P GEN MW:        blank  (or zero)
    Q MAX MVAR:      blank
    Q MIN MVAR:      blank
    V Hold PU:       1.08
    V MIN PU:        blank  (not used)
    Remote Bus Name: blank (none)
    Remote Bus kV:   blank (none)
    % VARS Supplied: blank (not applicable)
    
    1. Data for INF BUS 500

    Record Type:     B
    Subtype:         S
    Change Code:     blank
    Owner:           blank
    Name:            INF BUS
    kV:              500
    Zone:            blank
    Load P MW:       blank
    Load Q MVAR:     blank
    Shunt Load MW:   blank
    Shunt Load MVAR: blank
    P MAX:           blank
    P GEN MW:        blank
    Q SCHED MVAR:    blank
    Q MIN MVAR:      blank
    V Hold PU:       1.05
    V MIN PU:        blank
    Remote Bus Name: blank
    Remote Bus kV:   blank
    % VARS Supplied: blank
    
    1. Data for MID 500

    Record Type:      B
    Sub Type:         blank
    Change Code:      blank
    Owner:            blank (not known)
    Name:             MID
    kV:               500
    Zone:             blank
    Load P MW:        blank (zero)
    Load Q MVAR:      blank (zero)
    Shunt Load MW:    blank (zero)
    Shunt React MVAR: -300
    P MAX:            blank
    P GEN MW:         blank
    Q MAX MVAR:       blank (fixed)
    Q MIN MVAR:       blank (fixed = Q MAX)
    MAX PU:         blank (defaults to global limit)
    V MIN PU:         blank (defaults to global limit)
    Remote Bus Name:  blank
    Remote Bus kV:    blank
    % VARS Supplied:  blank (not applicable)
    

Note

A bus can only be of one subtype. The subtype of a bus is suggested by information given about the bus. Therefore, the user should try to be familiar with various bus subtypes and when and how they are indicated by descriptive information given

  1. Prepare the branch data group.

Transformer:  GEN 22               GEN HI 500
Line:         GEN HI 500           MID 500 circuit 1
Line:         GEN HI 500           MID 500 circuit 2
Line:         INF BUS 500          MID 500 circuit 1
Line:         INF BUS 500          MID 500 circuit 2

Note

1 and 2 designations are arbitrary identifications for parallel branches. Letters A-Z and digits 0-9 are acceptable.

  1. Data for Transformer GEN 22 GEN HI 500

Record Type:      T
Sub Type:         blank
Change Code:      blank
Owner:            blank (not known)
Name 1:           GEN
kV 1:             22
Meter:            blank
Name 2:           GEN HI
kV 2:             500
ID:               blank
Section:          blank
Total MVA RATE:   1770
No of CKT:        blank
Z_pi
Rpu(100MVA):  blank (or zero)
Xpu(100MVA):  .01246
Y_pi
Gpu(100MVA):  blank (or zero)
Bpu(100MVA):  blank (or zero)
Tap 1 kV:         22
Tap 2 kV:         525
Date In:          blank (in)
Date Out:         blank (not out)
  1. Data for Line GEN HI 500 MID 500 circuit 1

Record Type:      L
Sub Type:         blank
Change Code:      blank
Owner:            blank (not known)
Name 1:           GEN HI
kV 1:             500
Name 2:           MID
kV 2:             500
ID:               1
Section:          blank
Total AMP RATING: 3000
No of CKT:        blank (means 1)
Z_pi
Rpu:          .00117
Xpu:          .02100
Y_pi
Gpu:          blank (zero)
Bpu:          1.024
Miles:            100
DESC DATA:        blank
Date In:          blank (in)
Date Out:         blank (not out)
  1. Data for Line GEN HI 500 MID 500 circuit 2

Record Type:      L
Sub Type:         blank
Change Code:      blank
Owner:            blank (not known)
Name 1:           GEN HI
kV 1:             500
Meter:            blank
Name 2:           MID
kV 2:             500
ID:               2
Section:          blank
Total AMP RATING: 3000
No of CKT:        blank (means 1)
Z_pi
Rpu:          .00117
Xpu:          .02100
Y_pi
Gpu:          blank
Bpu:          1.024
Miles:            100
DESC DATA:        blank
Date In:          blank (in)
Date Out:         blank (not out)
  1. Data for Line INF BUS 500 MID 500 circuit 1

Record Type:      L
Sub Type:         blank
Change Code:      blank
Owner:            blank (not known)
Name 1:           INF BUS
kV 1:             500
Meter:            blank
Name 2:           MID
kV 2:             500
ID:               1
Section:          blank
Total AMP RATING: 3000
No of CKT:        blank (means 1)
Z_pi
Rpu:          .00117
Xpu:          .02100
Y_pi
Gpu:          blank (zero)
Bpu:          1.024
Miles:            100
DESC DATA:        blank
Date In:          blank (in)
Date Out:         blank (not out)
  1. Data for Line INF BUS 500 MID 500 circuit 2

Record Type:      L
Sub Type:         blank
Change Code:      blank
Owner:            blank (not known)
Name 1:           INF BUS
kV 1:             500
Meter:            blank
Name 2:           MID
kV 2:             500
ID:               2
Section:          blank
Total AMP RATING: 3000
No of CKT:        blank (means 1)
Z_pi
Rpu:          .00117
Xpu:          .02100
Y_pi
Gpu:          blank (zero)
Bpu:          1.024
Miles:            100
DESC DATA:        blank
Date In:          blank (in)
Date Out:         blank (not out)

Note

The most difficult task in setting up branch data is determining the per unit (pu) values of R, X, G and B. See Calculating Line Impedance for some help on this.

Note

In this example, some preliminary information has been furnished on a per-mile basis. We have multiplied the per-mile quantities by the line lengths in order to obtain the data entered in the record. The reader should generally use detailed line constant calculation procedures to obtain more accurate values for high-voltage long lines. At 500 kV, 100 miles should be considered a long line. Energy conservation analysis is sensitive to the accuracy of high-voltage long-line branch data and transformer branch data.

Derivation of Transformer Xpu on 500kV, 100 MVA:

\[\begin{split}(Xpu on 500kV 100 MVA) &= (Xpu on 525kV 1770 MVA) * \frac{525 * 525}{500 * 500} * \frac{100}{1770} \\ &= 0.20 * \frac{525 * 525}{500 * 500} * \frac{100}{1770} \\ &= 0.012458\end{split}\]

Derivation of Line Xpu on 500 kV, 100 MVA:

All four lines are the same:

\[\begin{split}Base inpedance in ohms &= \frac{Base kV * Base kV}{Base MVA} \\ &= \frac{(500)(500)}{100} &= 2500 ohms\end{split}\]

Ignoring long-line effect, reactance for 100-mile line is 52.2 ohms:

\[\begin{split}&= \frac{52.5}{2500}pu \\ &= 0.02100pu\end{split}\]

Derivation of Line Rpu on 500 kV, 100MVA:

All four lines are the same:

New Facilities

The purpose of this example is to provide new generating facilities to serve the growing loads near the town of Keller and Mount Tolman.

Proposed New Facility

The proposed facility includes a new substation at NEW SUB, a 21-mile 230 kV line tapped from the A SUB - B SUB No. 2 line and another line to D SUB tapped from A SUB - NEW SUB line but which will be built and owned by another utility. The equipment at NEW SUB substation will include a 25 MVA transformer with protective equipment serving a 34.5 kV load. In the diagram on the following page, starred or dotted lines are the proposed facility while the dashed lines indicate existing facility. This proposed facility may be one among other possible alternatives. Each alternative, and modifications thereof, will be considered a case and submitted to the power flow program for analysis and report.

Possible Uses of IPF

IPF will be used to study the power flows, voltage regulation and reliability of service utilizing the proposed facility.

_images/A-SUB_New_SUB_230_kV_Line.png

A-SUB - New SUB 230 kV Line

The processes (POWERFLOW) and (OUTAGE_SIM) will be used to check power flow as well as reliability. Refer to Power Flow Control (PFC), for complete description of these processes.

Suppose the base network which the proposed new facility will amend has been described in an old base file named BASENET.BSE. The following program control file can be built for this case:

(POWERFLOW, CASEID = EXAMPLE1, PROJECT=KELLER-SUB)
/OLDBASE FILE = BASENET.BSE\
/NEWBASE = EXAMPLE1.CAS\
....
....  Optional Network Solution Qualifiers Listed Under
....                  (POWERFLOW)
/CHANGES
B - record for NEW SUB 34.5
B - record for NEW SUB 230
B - record for NEW SUB Tap 230
B - record for D SUB 230
B - record for A SUB TAP 230
L - record to delete A SUB 230 B SUB 230  2
L - record for A SUB 230 A SUB Tap 230
L - record for A SUB Tap 230 B SUB 230
T - record for NEW SUB 230 NEW SUB 34.5
. The above record formats are described
. Under appropriate Heading starting with the key letter
(POWERFLOW, CASEID=EXAMPLE1, PROJECT=NEW-SUB)
/OLDBASE FILE=EXAMPLE1.CAS
/OUTAGE_SIM
....
....  Optional Qualifiers Listed Under /OUTAGE_SIM
....
(STOP)

The output listings from this case will be inspected to make sure no overloads occur during normal operation as well as during the outages of key lines.

Special environmental concerns may suggest evaluation of alternatives to the river crossing indicated in the exhibit. Conductor sizing may also be influenced by energy conservation (loss-reduction) considerations. The effect of each alternative can be determined from the network solution output listing.

In this example, the major point to monitor is the impact of tapping lines since segments of a tapped line perform differently from the untapped line.

Reconductoring

The purpose of this example is to cure poor voltage regulation at delivery point C occurring when lines AB, BC or DE are out of service, and to improve energy conservation.

Proposed New Facility

Lines AB, BC and DE will be reconductored to reduce series impedances using higher capacity lines. The higher capacity lines will give rise to acceptable voltages and save energy otherwise lost in transmission.

Possible Uses of Powerflow

IPF can be used to study the power flows, voltage regulation and reliability of service utilizing the proposed facility. In reference to the Program Control Language:

  1. The base case is run to determine power flows, voltage levels and transmission losses.

  2. The change case is run to modify the data for lines AB, BC and DE reflecting the new conductors used. Power flows, voltages and losses will again be reviewed.

3. The outage simulations case is run to verify the effect of certain lines being out of service on power flows, voltage levels, line loading and line losses. If the base network to be amended by the proposed new facility is described in an old-base file named BASENET.BSE, the program control file following the diagram of the reconductoring can be built for this project.:

( POWERFLOW, CASEID = EXAMPLE30, PROJECT = RECONDUCT )
/ OLD_BASE, FILE = BASENET.BSE
. . .
. . .  Optional network solution qualifiers.
. . .
( NEXTCASE, CASEID = EXAMPLE31, PROJECT = RECONDUCT )
/ NEW_BASE, FILE = EXAMPLE31.CAS
. . .  Optional qualifiers to override options
. . .  already selected above.  This should be
. . .  an empty set.
/ CHANGES
L - record to modify line AB
L - record to modify line BC
L - record to modify line DE
( NEXTCASE, CASEID = EXAMPLE32, PROJECT = RECONDUCT )
/ OUTAGE_SIM
. . .
. . .  Optional simulation qualifiers.
. . .
( STOP )

Series Compsensation

The purpose of this example is to add series compensation to existing parallel lines so as to cause more power to be shifted to these lines from lines with less loss-reduction.

Proposed New Facility

A 540 MVAR series capacitor at Station C is installed (270 MVAR per line), along with additional control and protective equipment. Station C is sited 72 miles from Station A and 102 miles from Station B.

Possible Uses of Powerflow

IPF will be used to study the power flows utilizing the proposed facility.

If the base network amended by the proposed new facility is described in an old-base file named BASENET.BSE, then the following program control file can be built for this case:

( POWERFLOW, CASEID = EXAMPLE4, PROJECT = SERIES COMP )
/ OLD_BASE, FILE = BASENET.BSE
. . .
. . .  Optional solution qualifiers.
. . .
/ CHANGES
L - record to delete line AB circuit 1
L - record to delete line AB circuit 2
L - record to add Ckt circuit 1 section 1 (line AC)
L - record to add Ckt circuit 1 section 2 (capacitor)
L - record to add Ckt circuit 1 section 3 (line CB)
L - record to add Ckt circuit 2 section 1 (line AC)
L - record to add Ckt circuit 2 section 2 (capacitor)
L - record to add Ckt circuit 2 section 3 (line CB)
( STOP )

Record Formats

Overview

This section describes all data record formats recognized by IPF. Records are used to represent buses, lines, transformers, reactive devices, area interchange control, and more. Records defined in the input files for the command line tools (bpf, ipfbat, ipfcut, etc.) are fixed column format. Please note that all information must be in the correct columns; you will experience processing errors otherwise. Most records are also available in the X Window GUI interface via forms and in libcflow via C structs. The record descriptions in this section are organized alphabetically by record ID as you go through the section (except for the DC bus records which follow the AC bus records). The table below enables you to quickly locate a specific record format entry. The table also gives you a quick description of each record format.

Each record description in this section has a “card” figure that shows you where to put record identification and the other fields and properties of the record. These “card” figures are artifacts from the days of punchcards and mainframes, but they do provide good visual represenation of the data for each record format when manually creating intput files for IPF. Each card figure has a legend showing whether each fields is required, optional, or ignored.

Each entry also has a table of column descriptions and data formats. This supplements the card figure. Additional text accompanies any record formats that need extended discussion.

Some data are real numbers. For these fields, the implicit decimal point is shown as a black dot on the card. figure, just above the information entry row. Note that you can enter data with an explicit decimal point in any position within the field. A black dot that appears at the extreme right side of a field represents a decimal point at the right end (least significant digit) of a number. All other black dots appear above a line, indicating that the decimal point will fall between the digits on either side.

All IPF data record types are identified by the characters in columns 1 and 2. To fully specify a particular record, additional fields need to be filled in. These additional ID fields are usually the bus name and base kV. ID fields are called out in the column description tables.

Record Types

Record ID (columns 1-2)

Field Width

Description

Period (.)

120

Comment (not printed)

+

80

Bus continuation

A

80

Area interchange control

AO

80

Area output sort

-

-

General AC bus description

B

80

AC bus - load bus

BC

80

AC bus - voltage controlled by BG bus

BE

80

AC bus - constant voltage

BF

80

AC bus - special purpose bus for Newton-Raphson solution

BG

80

AC bus - generator

BQ

80

AC bus - constant voltage within Q limits

BS

80

AC bus - system slack bus

BT

80

AC bus - LTC transformer controlled AC bus

BV

80

AC bus - constant Q within V limits

BX

80

AC bus - attempts constant V using switched Q specified on X record

BD

80

Two-terminal DC bus

BM

80

Multi-terminal DC bus

DA

80

Delete buses by area

DZ

80

Delete buses by zones

E

88

Equivalent branch (has extended ratings)

I

80

Area intertie I record

L

88

Transmission line (has extended ratings)

LD

80

Two-terminal DC line

LM

80

Multi-terminal DC line

PO PZ PN PA PB PC PD

80

Factor changes

QN QP QX

120

Reactive capability curve

R RV RQ RP RN RM

80

Regulating transformer

RZ

80

VAR compensator model

T

92

Transformer (has extended ratings)

TP

92

Phase shifter (has extended ratings)

X

80

Switched reactance (BX record)

Z

80

Zone rename

System Changes

After a base case has been established, it may be changed with the use of change records. The change records are identified as system data records which immediately follow the network-solution qualifier /CHANGES statement. See CHANGES for details.

The change records are system data records with a change code in column 3. Each of the input data forms describe the permissible types of changes under the caption CHANGE CODES. In all, there are five types of changes.

  • Additions: Change code = blank

    The data record identification must be unique to the system. The contents of the record must be complete as if it were being submitted to build a base case.

  • Deletions: Change code = D

    Only existing data may be deleted, and only the identification fields are needed. Numerical data in any other field is ignored. Special conditions are given:

    • Deleting a bus automatically deletes all continuation bus data, switched reactance data and all branch data associated with that bus. Deleting all branches connected to a bus will result in an error. It is better to delete the bus. A bus should not be deleted and added back in the same case with the same name in a single change file.

    • Deleting all transformer banks between two buses will automatically delete any regulating transformer data.

    • A line composed of sections may be deleted in its entirety by deleting section 0 (zero) or blank. The alternative is to delete each section with a separate change record. If a section is deleted the line is reconnected without that section. Transformer sections cannot be deleted.

    • A branch composed of parallel lines between two buses may be deleted in its entirety by entering a * in place of CKT ID. This provides a means of disconnecting two directly connected buses from each other. The branches may also be deleted individually.

    • A blank branch ID is legitimate identification.

    • Changing a bus from type X to any other type will delete all switched-reactance data automatically. No separate X delete record should be included.

  • Elimination: Change code = E

    This causes the elimination of all existing A (area interchange) records to make room for possible new A records. The user should note that this change code works for A records only.

  • Modifications: Change code = M

    All currently existing system data may be modified, which means changing the value of some quantity of system data. Data in the identification field cannot be changed.

    Only the data to be changed is entered on the change record. Nonblank fields constitute data modification, while blank fields indicate that the quantity is not to be changed. A blank and a zero quantity on the change record are distinguishable. Often, it is necessary to change a quantity into a blank. Examples are the bus zone name and the bus subtype. To change these into blank quantities, a 00 or 0 must be entered in the appropriate respective column fields. Special recognition is conferred on these change quantities.

  • Restorations: Change code = R

    Previously outaged system data may be reactivated with the use of restore change records. This type change permits data to be restored to the system with change records using the identification fields only. Any data fields on the restore record will be ignored, and the reactivated data assumes the same quantities it had prior to deletion. Restoring data is an option. Data could be re-entered with additional type change records as well. The operations and rules are similar to those for deletions. However, some important differences must be explained.

    • Restore changes are permissible only with data deleted in a previous change case but within the same base case. You cannot restore data outaged in a previous OLD_BASE case.

    • Area interchange records may not be restored.

    • Restoring a bus restores only branches which connect to a viable system base. In some cases, not all of the outaged branches can be restored.

    • Restoring all transformer banks between two buses will not automatically restore any regulating transformer data. If this is intended, the regulating R transformer data must be restored separately.

    • A restored branch record must match the branch code as well as the identification fields. For example, if the branch is type L, the restore record must match the type.

    The change records are read, interpreted and stored for further processing. As they are read the following are processed immediately:

    • Area Interchange (A-blank)

    • Zone Renames (Z-blank)

    • Area Deletes (DA)

    Processing of changes then continues in the following manner:

    • Changes Percents (P)

    • Deletes

    • Adds/Restores

    • Modifications

Note

If more than one modification for the same data item occurs, the changes will be made in the order encountered. In IPF, no message will be given the user.

If fatal data errors are encountered in batch mode, switches are set and the processing continues only to discover additional errors, list all changes and exit. For changes to existing data, component identification must be specified exactly as in the base case file. If fatal errors are encountered in interactive mode, appropriate diagnostics are issued so that the user can remedy the faulty command or data.

Comment

This comment text is used to annotate the program control file, network data file, or change file. Its contents are not added to the output listings nor saved in the binary base case file.

Simply place a . (period character) in the first column and the comment in the rest of the columns. This is also handy to temporarily deactivate a command or data line.

_images/Comment_Input_Format.png

Comment Input Format

Column Descriptions for Comment Format

Column

ID Field

Format

Content

1

yes

A1

. (period)

2-120

no

A119

Text string for record comment

Continuation Bus Data (+)

Continuation bus data is identified with a + in column 1 and supplements the data on any AC bus record. It specifies additional generation, load and shunt admittance at the bus and permits additional classification and utilization of data. Generally, it permits a more detailed analysis of data. Its most typical application is distinguishing loads represented by several different owners at the same bus. The following fields are for identification:

  • Bus name and base kV

  • Code and code year

  • Ownership

Each bus may have more than one continuation record. However, some means of distinction must be made in the minor identification fields of code year or owner. See figure and tables below for details.

A sample coding sheet and column descriptions for continuation bus data follows.

_images/Continuation_Bus_Data_Input_Format.png

Continuation Bus Data Input Format

Classification Codes

Code

Description

A

Equivalent injection data from network reduction. Note that data associated with this code is not subject to the effect of factor change (P) records.

C

Shunt MW or MVAR

F

Industrial firm load

I

Industrial interruptible load

N

Nonindustrial firm load (bus ownership differs from load ownership)

P

Industrial potential load

S

Nonindustrial secondary load

Blank

Nonindustrial firm load (bus ownership = load ownership)

In addition to the special classifications codes of column (2:2), the code year may convey special meaning or models to the continuation bus records. The table below summarizes the features.

Special Constant Current and Constant Impedance Loads

Code

Code year

P_load

Q_load

G_shunt

B_shunt

Description

+A

Constant power MW load (generation if negative)

Constant power MVAR load (generation if negative)

Constant admittance MW evaluated at nominal voltage

Constant admittance MVAR evaluated at nominal voltage

Quantity generated by Network Data or Cutting routines

+A

00

Constant power MW load (generation if negative)

Constant power MVAR load (generation if negative)

Constant admittance MW evaluated at nominal voltage

Constant admittance MVAR evaluated at nominal voltage

Quantity generated by Network Data routine

+A

01

Distributed constant current MW load (generation if negative) evaluated at nominal voltage

Distributed constant current conjugate MVAR load (generation if negative) evaluated at nominal voltage

Equivalent MW shunt admittance

Equivalent MVAR shunt admittance

Quantity generated by Network Reduction routines

+A

02

Distributed MW load (generation if negative)

Distributed MVAR load (generation if negative)

Equivalent MW shunt admittance

Equivalent MVAR shunt admittance

Quantity generated by Network Reduction; denote equivalent shunt admittances

*I

Constant current MW load (generation if negative) evaluated at nominal voltage

Constant current conjugate MVAR load (generation if negative) evaluated at nominal voltage

Not applicable

Not applicable

Quantity generated by %LOAD_DISTRIBUTION

*Z

Constant power MW load (generation if negative)

Constant power MVAR load (generation if negative)

Constant admittance MW load (generation if negative) evaluated at nominal voltage

Constant admittance MVAR load (generation if negative) evaluated at nominal voltage

Quantity generated by %LOAD_DISTRIBUTION

*P

Constant power MW load (generation if negative)

Constant power MVAR load (generation if negative)

Not applicable

Not applicable

Quantity generated by %LOAD_DISTRIBUTION

Column Description for Continuation Bus Data

Column

ID Field

Format

Description

1

yes

A1

Record type; + for all continuation bus data

2

yes

A1

Code (See code types above.)

3

no

A1

Change code

4-6

yes

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

yes

A2

Code year—alphanumeric subtype of code

21-25a

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR at base kV (+) = Capacitive (-) = Inductive

43-47

no

F5.0

P GEN MW

48-52

no

F5.0

Q GEN MVAR (or Q MAX) (+) = Capacitive (-) = Inductive

53-57

no

F5.0

Q MIN in MVAR

75-77

no

A1, A2

Energization date month and year {month = 1,2,3,4,5,6,7,8,9,O,N,D}

  1. If the Code (column 2) is A and the Code year (column 19-20) is 01, the load quantities are constant current-constant power factors and are:

  1. Interpreted as MW and MVAR evaluated at base kV (+) = Inductive (-) = Capacitive

  2. Evaluated as: \(P + jQ = (I*)|V|\)

Note

Q_max and Q_min represent inequality constraints (Q_max > Q_min). However special concerns apply for bus subtypes blank, C, T and V, where the Q is constrained. In order to assign appropriate values for scheduled Q, Q_min is first examined. If Q_min < 0 and Q_max > 0, the limits are recognized as erroneous constraints and both are ignored. If Q_min = 0, then the schedule Q is always Q_max

Area Interchange Control (A)

A network may be partitioned geographically by area. Similarly, areas may be partitioned by zones. The net power exported from each area can be specified with an area interchange record. Export power is controlled by varying the area slack bus generation. Interchange export is measured as the sum of the exported power on all area tie lines metered at the area boundaries. The total net export of all areas must add to zero; otherwise, the area interchange control is aborted. See the figure and tables below.

Valid subtypes are blank, 1, …, 9, with 1, …, 9 being continuation records. This allows up to 100 zones to be defined in an area.

In order for area interchange control to be activated, A records must be defined and the /AI_CONTROL option must be set to the default, CON (Control). Three slack bus restrictions pertain to each area.

  • One area slack bus must be the system swing bus.

  • Each area slack bus must be within the area it controls.

  • For all slack buses the P generation is variable.

Note

Area Continuation records (A1, …, A9) accept only area name and zones 1-10 fields.

_images/Area_Interchange_Control_Input_Format.png

Area Interchange Control Input Format

Column Description for Area Interchange

Column

ID Field

Format

Description

1

yes

A1

Record type — A

2

yes

A1

Subtype — blank, 1, …, 9

3

no

A1

Change code — see System Changes

4-13

yes

A10

Interchange area name — Name of area consisting of one or more zones. Alphanumeric entries are permitted.

14-25

no

A8,F4.0

Area slack bus name and base kV. (Does not apply to subtypes A1, …, A9.)

27-34

no

F8.0

Scheduled export — MW flow scheduled (+) out of area or (-) into area. If I (interchange) records are present for this area, the net schedule will be overwritten with the netting computed from the I records. (Does not apply to subtypes A1, …, A9.)

36-64

no

10(A2,1X)

Zones to be included in the interchange area named in columns 4-13. A blank zone terminates the scan unless it is zone 1. All zones must be listed within some area, but no zone may be common to more than one area.

73-76

no

F4.3

Maximum per unit voltage. (Does not apply to subtypes A1, …, A9.)

77-80

no

F4.3

Minimum per unit voltage. (Does not apply to subtypes A1, …, A9.)

Area Output Sort (AO)

The order of buses in the input and output listings may be grouped into areas with arbitrary zone configurations. The areas are sorted alphabetically and the buses within each area are then sorted alphabetically.

These records permit an area to be defined independently of any area interchange. Once introduced, these records become a permanent part of the base case file. A coding sheet and description of the record columns follows:

_images/Listing_by_Sorted_Areas_Input_Format.png

Listing by Sorted Areas Input Format

Column Description for Area Output Sort

Column

ID Field

Format

Description

1

yes

A1

Record type — A

2

yes

A1

Subtype — O

3

no

A1

Change code — see System Changes

4-13

yes

A10

Area Name — These names are independent of area interchange names but may be identical.

15-79

no

22(A2,1X)

Zone composition list — a blank zone terminates the zone scan unless it is zone 1.

80

no

blank

AC Bus Data

Bus records identify nodes in the network. The following description applies to AC buses only; DC buses are identified by a subtype D or M and are described in Two-Terminal DC Bus (BD) and Multi-Terminal DC Bus (BM).

Each AC bus consists of three attributes: generation, load, and shunt admittance. Various subtypes assign unique characteristics to these attributes. Some affect conditions in the solution; others affect only the allocation of quantities in the output listings.

The various subtypes permit different models to represent the operation of the system. Most buses have constant real injection. Exceptions are the system slack bus and any area interchange slack buses.

_images/Bus_Data_Input_Format.png

Bus Data Input Format

Column Description for AC Bus Data

Column

ID Field

Format

Description

1

yes

A1

AC B type record

2

no

A1

Subtype

3

no

A1

Change code

4-6

no

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-26

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR at base kV (+) = Capacitive (-) = Inductive

43-47

no

F5.0

P GEN MW

48-52

no

F5.0

Q GEN MVAR (+) = Capacitive (-) = Inductive

53-57

no

F5.0

Q MIN MVAR

58-61

no

F4.3

V HOLD - V MAX (in per unit)

62-65

no

F4.3

V MIN (in per unit)

66-73

no

A8

Controlled bus name

74-77

no

F4.0

Base kV

78-80

no

F3.0

Percent of vars supplied for remote bus voltage control.

For all subtypes, the following diagram illustrates the reactive allocation scheme.

_images/Reactive_Allocation_Scheme.png

Reactive Allocation Scheme

Allocation of reactive facilities is complex. These may be allocated by equality constraints (\(Q_{net}\) is constant), inequality constraints (\(Q_{net}\) varies between a minimum and maximum value), or no constraints.

Let \(Net\) define the total line export. Then the following equation is always valid:

\[Net = Generation - Load - Y_{shunt} * Voltage^2\]

The equation is complex; the real and reactive components are balanced separately. The separate equations are:

\[\begin{split}P_{net} &= P_{Gen} - P_{load} - G * V^2 \\ Q_{net} &= Q_{Gen} - Q_{load} + B * V^2\end{split}\]

The shunt admittance is

\[Y = \frac{1}{Z} = G + jB\]

The equations above define the interrelationship between quantities and are valid for all bus types. The bus type determines which equations are also constraints.

The preceding diagram illustrates the following priority scheme. In applying the equation for \(Q\), vars are allocated to generation and variable shunt components on a priority basis. If \(Q_{net}\) is less than \(Q_{load} + Q_{shunt}\) fixed, then vars are allocated first to variable shunt reactors and then, if necessary, to reactive generation. If, on the other hand, \(Q_{net}\) is higher than \(Q_{load} + Q_{shunt}\) fixed, then vars are allocated first to the variable shunt capacitors and then, if necessary, to reactive generation. If the limits of reactive generation are exceeded, then unscheduled reactive is allocated.

AC Bus Data (B-blank)

Application

This bus subtype is passive in the sense that it cannot control the voltage of another bus. Its primary use is for modeling load buses.

Bus Characteristics

Both real (\(P\)) and reactive (\(Q\)) power are held constant throughout the entire solution. This applies to generators, load and shunt devices (capacitors/reactors).

A specific amount of reactive generation can be requested. This can be accomplished by entering a zero (0) in the Q MIN field and the desired amount of reactive generation in the Q SCHED field.

Since this bus normally has no voltage control, the voltage limits (V MAX, V MIN) serve two purposes.

  • If the bus is remotely controlled by another bus (type BG or BX) or by an LTC transformer (which is not standard but is accepted), the limits specify the range of acceptable voltage.

  • For accounting purposes, these limits can flag undervoltage or overvoltage situations in the analysis reports.

It must be recognized that every bus has voltage limits, whether they are explicitly specified through the V MIN, V MAX fields or implicitly specified through default global voltage limits. See Voltage Limits and Starting Voltages for details on global limits.

Reactive limits are not allowed for this type of bus. If reactive limits are entered in the Q MAX and Q MIN fields, they will be ignored. However, legitimate Q GEN can be entered if Q MIN is zero.

For this subtype, \(Q_{net}\) is constant; its Q-V characteristic is shown in format drawing below.

If this bus is controlled by an LTC transformer or by a BG or BX bus, a warning diagnostic will be issued to the effect that remotely controlled buses are typically type BC or type BT and the controlled voltage is a single value, \(V_{sched}\) and not a range \(V_{min} < V_{controlled} < V_{max}\).

_images/B-blank_Subtype_Format.png

B-blank Subtype Format

Column Description for B Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

B - Generic load bus

3

no

A1

Change code

4-6

no

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-25

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR

39-42

no

F4.0

P MAX

43-47

no

F5.0

P GEN

48-52

no

F5.0

Q SCHED in MVAR

53-57

no

F5.0

Q MIN — Must be blank or zero for Q SCHED to apply

58-61

no

F4.3

VMAX. If blank, then limits default to global limits as outlined in ??.

62-65

no

F4.3

VMIN. If blank, then limits default to global limits as outlined in ??.

66-77

no

A8,F4.0

N/A

78-80

no

F3.0

N/A

_images/Q-V_Curve_for_B-blank_Subtype.png

Q-V Curve for B-blank Subtype

AC Bus Data (BC)

Application

This bus type has its voltage maintained by a subtype BG bus.

Bus Characteristics

Both real (\(P\)) and reactive (\(Q\)) power are held constant throughout the entire solution. This applies to generators, loads, and shunt devices (capacitors/reactors).

A specific amount of reactive generation can be requested. This can be accomplished by entering a zero (0) in the Q MIN field and the desired amount of reactive generation in the Q SCHED field.

Reactive constraints are not allowed for this type of bus. If reactive limits are entered in the Q MAX and Q MIN fields, they will be ignored.

Since this bus type has its voltage maintained by a generator bus, a V HOLD entry is strongly recommended on the bus record. However, if that field is blank, the global default limits apply, in effect, using VMAX for the VHOLD. See Voltage Limits and Starting Voltages for details on global limits.

_images/BC_Subtype_Format.png

BC Subtype Format

Column Description for BC Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BC - Voltage controlled by BG bus

3

no

A1

Change code

4-6

no

A3

Ownership

7-18

yes

Bus name and base kV

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-25

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR

39-42

no

F4.0

P MAX

43-47

no

F5.0

P GEN

48-52

no

F5.0

Q SCHED in MVAR

53-57

no

F5.0

Q MIN — Must be blank or zero for Q SCHED to apply

58-61

no

F4.3

V HOLD in per unit

62-65

no

F4.3

N/A

66-77

no

A8,F4.0

N/A

78-80

no

F3.0

N/A

_images/Q-V_Curve_for_BC_Subtype.png

Q-V Curve for BC Subtype

AC Bus Data (BE)

Application

This subtype is used to hold the bus voltage to a specified value, regardless of the amount of reactive required.

Bus Characteristics

Voltage magnitude (\(V\)) is held constant. Real (\(P\)) power is held constant. This applies to generators, load, and shunt devices. Reactive (Q) load is held constant for this bus type.

Reactive (\(Q\)) shunt is variable. The amount of shunt reactance added by the program can vary from 0 to Qshunt, depending upon the amount needed to maintain desired bus voltage.

Reactive (\(Q\)) generation is variable.

Reactive constraints are allowed for this bus type. These quantities are entered in the Q MAX and Q MIN fields. If reactive constraints are imposed, “unscheduled reactive” may be added by the program to hold the bus voltage.

A specific amount of reactive generation (Q SCHED) cannot be requested.

Since this bus type maintains its own voltage, a V HOLD entry is required on the record. The voltage is held fixed at this value, regardless of the amount of reactive required. Note that V HOLD is not required for type “M” changes.

_images/BE_Subtype_Format.png

BE Subtype Format

Column Description for BE Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BE - Constant voltage bus

3

no

A1

Change code

4-6

no

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-25

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR

39-42

no

F4.0

P MAX

43-47

no

F5.0

P GEN

48-52

no

F5.0

Q MAX in MVAR

53-57

no

F5.0

Q MIN in MVAR

58-61

no

F4.3

V HOLD in per unit

62-65

no

F4.3

N/A

66-77

no

A8,F4.0

N/A

78-80

no

F3.0

N/A

_images/Q-V_Curve_for_BE_Subtype.png

Q-V Curve for BE Subtype

AC Bus Data (BF)

This is a special purpose bus type used to assist the Newton-Raphson solution convergence. The BF type behaves as a BE bus until the P_net converges to the Newton-Raphson solution. Then it functions as a B- type. This feature is useful to bias a solution toward a more feasible voltage.

AC Bus Data (BG)

Application

This bus type is typically used to maintain the voltage at a remote bus (subtype BC).

This subtype may also be used for local control. For this application, the bus would maintain its own voltage. In this case, it would differ from a BQ bus only by the voltage limit. BG has \(V_{min} ≤ V_{max}\); BQ has \(V_{hold}\).

Bus Characteristics

Real (\(P\)) power is held constant. This applies to generators, load and shunt devices. However, it is not required to have generation (P GEN) at this bus.

Reactive (\(Q\)) load and shunt are held constant for this bus type.

Reactive (\(Q\)) generation is variable.

This bus type requires reactive limits to be entered in the Q MAX and Q MIN fields. The reactive limits on the subtype BG bus are used to maintain a specified voltage at a remote bus. If the remote bus voltage cannot be held with the available BG bus reactance, voltage control stops at either Q MAX or Q MIN.

A specific amount of reactive generation (Q SCHED) cannot be requested.

This bus type uses V MAX and V MIN limits. If these fields are blank, global voltages are used as defaults. The voltage on the BG bus must be between V MIN and V MAX when controlling a remote bus. If not, remote voltage control will be disabled.

If this bus type is being used to control another bus, the REMOTE BUS and % VARS SUPPLIED fields should be used.The REMOTE BUS may not be the system swing bus or another subtype BG bus. The % VARS SUPPLIED field is used to allow the voltage control of a remote bus, to be distributed among more than one BG bus.

If the % VARS SUPPLIED is left blank, the program computes these values based upon the percent of total VARS supplied by the bus.

If the bus is controlling itself, its own name must appear in the REMOTE BUS field.

_images/BG_Subtype_Format.png

BG Subtype Format

Column Description for BG Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BG - Maintains the voltage of a remote bus

3

no

A1

Change code

4-6

no

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-25

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR

39-42

no

F4.0

P MAX

43-47

no

F5.0

P GEN

48-52

no

F5.0

Q MAX in MVAR

53-57

no

F5.0

Q MIN — Must be blank or zero for Q SCHED to apply

58-61

no

F4.3

V MAX

62-65

no

F4.3

V MIN

66-77

no

A8,F4.0

Controlled bus name and base kV (self or remote)

78-80

no

F3.0

Percent of vars supplied for remote bus voltage control.

_images/Q-V_Curve_for_BG_Subtype.png

Q-V Curve for BG Subtype

AC Bus Data (BQ)

Application

This subtype is used to hold the bus voltage to a specified value within reactive limits.

Bus Characteristics

Real power (P GEN) is held constant. This applies to generators, load, and shunt devices.

Reactive load (Q MVAR) load is held constant for this bus type.

Reactive (SHUNT MVAR) shunt is variable. The amount of shunt reactance added by the program can vary from 0 to Qshunt, depending on the amount needed to maintain desired bus voltage.

Reactive (\(Q\)) generation is variable.

This bus type requires adjustable reactive generation or shunt to perform as intended. If neither is available, the bus functions as a bus type B-blank.

A specific amount of reactive generation (Q SCHED) cannot be requested.

Since this bus type is attempting to maintain its own voltage, a V HOLD entry is required on the record. If the voltage cannot be held at the desired level, using the reactive capability of the bus, the desired voltage will be violated and reactive will be held at the Q MAX or Q MIN limit. Note that V HOLD is not required for modifications.

_images/BQ_Subtype_Format.png

BQ Subtype Format

Note

For a type BQ bus to be viable, it needs a source of adjustable reactive. This may be the B_shunt field or the Q MIN - Q MAX fields. The necessary reactive component may be provided on the bus record, or it may be provided on an accompanying continuation (+) bus record or both

Column Description for BQ Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BQ - Constant voltage within Q limits

3

no

A1

Change code

4-6

no

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-25

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR

39-42

no

F4.0

P MAX

43-47

no

F5.0

P GEN

48-52

no

F5.0

Q MAX

53-57

no

F5.0

Q MIN

58-61

no

F4.3

V HOLD

62-65

no

F4.3

N/A

66-77

no

A8,F4.0

N/A

78-80

no

F3.0

N/A

_images/Q-V_Curve_for_BQ_Subtype.png

Q-V Curve for BQ Subtype

AC Bus Data (BS)

Application

This subtype designates the system swing or slack bus. The generators at the swing bus supply the difference between the specified power flowing into the system at the other buses and the total system output plus losses. Thus, real and reactive power are determined as part of the solution for this subtype.

Every power flow case must have a minimum of one swing bus. In addition, each isolated AC system must have its own swing bus. The maximum numbers of swing buses allowed for a single power flow case is ten.

Bus Characteristics

Real (\(P\)) load is held constant. Both real (\(P\)) generation and shunt are variable. The P GEN field is updated to the base case value. The P MAX field is used for reporting purposes only.

Reactive (\(Q\)) load is held constant for this bus type. Reactive (\(Q\)) shunt is variable. The amount of shunt reactance added by the program can vary from 0 to Qshunt, depending on the amount needed to maintain desired bus voltage.

Reactive (\(Q\)) generation is variable.

Reactive constraints are allowed for this bus type. These quantities are entered in the Q MAX and Q MIN fields. If reactive constraints are imposed, “unscheduled reactive” may be added by the program to maintain the bus voltage.

A specific amount of reactive generation can be requested, in place of reactive constraints. This is implemented by entering a 0 in the Q MIN field and the desired amount of reactive generation in the Q SCHED field. Again, “unscheduled reactive” may be added by the program to maintain the bus voltage.

The BS bus record requires an entry in the V HOLD field.

The V MIN field is used to specify the angle of the swing bus for this application. It should be noted that an implied decimal point exists between columns 64 and 65. For example, an angle of 3.7 degrees can be specified with a 3 in column 64 and a 7 in column 65.

_images/BS_Subtype_Format.png

BS Subtype Format

Column Description for BS Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BS - System swing or slack bus

3

no

A1

Change code

4-6

no

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-25

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR

39-42

no

F4.0

P MAX

43-47

no

F5.0

P GEN

48-52

no

F5.0

Q MAX

53-57

no

F5.0

Q MIN

58-61

no

F4.3

V HOLD

62-65

no

F4.1

Voltage angle (blank implies zero degrees)

66-77

no

A8,F4.0

N/A

78-80

no

F3.0

N/A

_images/Q-V_Curve_for_BS_Subtype.png

Q-V Curve for BS Subtype

AC Bus Data (BT)

Application

This subtype has its voltage maintained by an Load Tap Change (LTC) transformer.

Bus Characteristics

Both real (\(P\)) and reactive (\(Q\)) power are held constant throughout the entire solution. This applies to generators, load, and shunt devices (capacitors/reactors).

A specific amount of reactive generation can be requested. This can be accomplished by entering a zero (0) or blank in the Q MIN field and the desired amount of reactive generation in the Q SCHED field.

Reactive constraints are not allowed for this type of bus. If reactive limits are entered in the Q MAX and Q MIN fields, they will be ignored.

Since this bus type has its voltage maintained by an LTC transformer, a V HOLD entry is required. This subtype requires an additional record, the R (Regulating Transformer) record.

_images/BT_Subtype_Format.png
Column Description for BT Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BT - LTC transformer controlled bus

3

no

A1

Change code

4-6

no

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-25

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR

39-42

no

F4.0

P MAX

43-47

no

F5.0

P GEN

48-52

no

F5.0

Q SCHED

53-57

no

F5.0

QMIN must be blank or zero for QSCHED to apply

58-61

no

F4.3

V HOLD

62-65

no

F4.1

N/A

66-77

no

A8,F4.0

N/A

78-80

no

F3.0

N/A

AC Bus Data (BV)

Application

This subtype maintains the bus’s net reactive (\(Q_{net}\)) power flow as long as the bus voltage does not violate the user specified voltage range.

Bus Characteristics

Real (\(P\)) power is held constant throughout the entire solution. This applies to generators, load, and shunt devices.

Reactive (\(Q\)) load and shunt are also held constant.

Reactive (\(Q\)) generation is normally constant. Although this bus type actually has infinitely adjustable reactive limits, the program attempts to hold Qnet constant. However, if either of the voltage limits are violated, \(Q_{net}\) is changed to hold that limit. If any additional reactive generation is added by the program, it will be referred to as “unscheduled reactive” in the program output file.

A specific amount of reactive generation can be requested. This is accomplished by entering a zero (0) in the Q MIN field and the desired amount of reactive generation in the Q SCHED field.

Reactive constraints are not allowed for this type of bus. If reactive limits are entered in the Q MAX and Q MIN fields, they will be ignored.

The BV bus record requires entries in the V MAX and V MIN fields. The program’s solution voltage will be within the range of V MAX to V MIN, regardless of how much reactive is required. If voltage attempts to rise above V MAX, additional negative reactive (\(-Q_{shunt}\)) is added to bring the voltage down to V MAX. Also, if the voltage is below V MIN, additional reactive (\(+Q_{shunt}\)) is added until the bus voltage has reached V MIN.

_images/BV_Subtype_Format.png

BV Subtype Format

Column Description for BV Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BV - Constant \(Q\) within \(V\) limits

3

no

A1

Change code

4-6

no

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-25

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR

39-42

no

F4.0

P MAX

43-47

no

F5.0

P GEN

48-52

no

F5.0

Q SCHED or QMA

53-57

no

F5.0

Q MIN

58-61

no

F4.3

V MAX in per unit

62-65

no

F4.1

V MIN in per unit

66-77

no

A8,F4.0

N/A

78-80

no

F3.0

N/A

_images/Q-V_Curve_for_BV_Subtype.png

Q-V Curve for BV Subtype

AC Bus Data (BX)

Application

This subtype may be used for a truer representation of capacitors/reactors that are switched in discrete blocks to control bus voltages. The BX subtype is most often used for local voltage control. Here, the bus would maintain its own voltage within a specified range of voltages. It is recommended, but is not mandatory, that for local control the bus name should be repeated in the REMOTE field. This subtype may also be used for remote control, where the BX bus maintains a specified voltage level at another bus. Provide the remote bus name.

Bus Characteristics

The real (\(G\)) and reactive (\(B\)) shunt fields hold the base case values of discrete reactance. These values may be updated by the solution. Real (\(P\)) power is held constant. This applies to generators and loads.

Reactive (\(Q\)) load is held constant. Reactive (\(Q\)) generation is variable.

Reactive constraints are allowed for this bus type. These quantities are entered in the Q MAX and Q MIN fields. A specific amount of reactive generation (Q SCHED) is available only if QMAX = QMIN. This bus type uses V MAX and V MIN limits. If these fields are blank, global voltages are used as defaults. The voltage on the BG bus must be between V MIN and V MAX when controlling a remote bus. If not, remote voltage control will be disabled.

Reactive shunt (\(+/- Q\)) is added in discrete blocks to maintain the desired bus voltage. The capacitive/inductive blocks of reactance are identified on the X (switched reactance) record. It should be noted that actual convergence is implemented with continuous susceptance control, then discretization occurs automatically. This means that exact voltage control may not be possible.

It should be noted that the program will attempt to select a discrete reactive step, which yields the highest voltage within the specified limits, so that losses can be minimized. This is the default (BPA) value, for the third level >MISC_CNTRL Program Control Statement, X_BUS option.

_images/BX_Subtype_Format.png

BX Subtype Format

Note

The value on the \(B_{shunt}\) field dictates the initial value

Column Description for BX Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BX — Attempts constant V using switched Q

3

no

A1

Change code

4-6

no

A3

Ownership

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

21-25

no

F5.0

Load MW

26-30

no

F5.0

Load MVAR

31-34

no

F4.0

Shunt Admittance Load in MW at base kV

35-38

no

F4.0

Shunt Admittance in MVAR

39-42

no

F4.0

P MAX

43-47

no

F5.0

P GEN

48-52

no

F5.0

Q SCHED or QMAX

53-57

no

F5.0

Q MIN

58-61

no

F4.3

V MAX in per unit

62-65

no

F4.1

V MIN in per unit

66-77

no

A8,F4.0

Controlled bus name and kV (self or remote). If blank, self is assumed.

78-80

no

F3.0

N/A

_images/Q-V_Curve_for_BX_Subtype.png

Q-V Curve for BX Subtype

Two-Terminal DC Bus (BD)

This record defines a DC bus to be used in conjunction with a two-terminal DC line. It is subtype D and interpreted with a different format from AC bus data records. No injections of any kind are permitted. The data contained on the record defines the rectifier or inverter valve characteristics. During the solution, the injection from the converter into the DC line is replaced with an equivalent but fictitious injection, and the DC line is removed entirely from the AC solution.

The DC model determines the initial AC injections and voltage magnitude on the converter bus. If these conditions can be held in the AC solution, no further DC adjustments occur. If the conditions cannot be held, the firing or extinction angles are readjusted to interface the current voltage magnitude on the converter buses while observing the scheduled DC power in the DC line. These adjustments will change the equivalent AC injections and will require a new AC solution.

The DC bus must be connected to a single AC bus through a commutating transformer. The commutating bus name is required, and the commutating transformer must be an LTC. All reactive sources supplying the harmonic filter must be connected on the commutating bus; it is not restricted in subtype.

Data for the inverter and rectifier buses are identical. Identification of each is by the DC line data record which compares the sign of the DC power flow with the DC terminal buses. The rectifier and inverter buses may be interchanging the sign of the scheduled DC power.

_images/BD_Subtype_Format.png

BD Subtype Format

Column Description for BD Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BD — Code for direct current (DC) bus, terminal of a DC line.

3

no

A1

Change code — see System Changes

4-6

no

A3

Ownership code

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone

24-25

no

I2

Bridges per ckt. — Number of valves in series per circuit.

26-30

no

F5.1

Smoothing reactor (mh) — Inductance of the smoothing reactor in millihenries.

31-35

no

F5.1

Rectifier operation (alpha min.) — Minimum firing angle in degrees as a rectifier.

36-40

no

F5.1

Inverter operation (alpha stop) — Maximum firing angle in degrees. Both inverter and rectifier buses have alpha. However, only the minimum alpha on the rectifier bus is used in the power flow. The remaining valves are required for the transient stability program in event of power reversals in the dc line.

41-45

no

F5.1

Valve drop (volts) — Valve voltage drop per bridge in volts.

46-50

no

F5.1

Bridge current rating (amps) — Maximum bridge current in amperes.

51-62

no

A8,F4.0

Commutating bus — Alphanumeric name in columns 51-58 and base kV in columns 59-62. This is on the AC system side of the commutating transformer bank

Multi-Terminal DC Bus (BM)

The multi-terminal DC system introduces flexibility in network configuration which is already present in the AC system. This DC scheme is a general extension of the two-terminal DC scheme. The converter modeling itself is unchanged, but the DC converter control is more flexible. All N-node DC systems must have N DC constraints. These are either converter DC voltage or DC power. At least one DC voltage constraint must be specified. It is permissible to constrain both DC voltage and power on the same node. The choice of voltage or power constraints on each converter is flexible.

It is possible to define a DC tap node. This node is passive only and is not a converter. Nevertheless, it implicitly constrains zero power on itself.

The distinction between rectifiers and inverters is very simple. Any converter’s mode of operation is based upon the sign of the converter-calculated output power. The converter output power is positive for rectifiers and negative for inverters. Obviously, a DC tap node will have zero power.

The range of converter angle adjustments is determined by the converters’s mode of operation.

\[\begin{split}\alpha_{min} &\leq \alpha_{stop} \\ \gamma_{0} &\leq \alpha_{stop}\end{split}\]

If an excessive number of DC constraints are specified, some superfluous power constraints will be omitted. If the DC system is unable to maintain the dc voltage constraints, the DC voltages will be changed to values realized by the actual commutator bus voltage and the converter angle limits.

It is permissible to model two-terminal DC networks with the multi-terminal type M formats. However, it is not permissible to mix two-terminal type D data with multi-terminal type M data on the same DC circuit. The two different types of DC data may coexist in the same case, but when both types are present, they must pertain to separate DC circuits.

_images/BM_Subtype_Format.png

BM Subtype Format

Column Description for BM Bus Data

Column

ID Field

Format

Description

1-2

yes

A2

BM - Code for multi-terminal dc bus

3

no

A1

Change code - see System Changes

4-6

no

A3

Ownership code

7-14ac

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

A2

Zone code

24-25

no

I2

Number of bridges per DC circuit - (Number of converters serially connected)

26-30

no

F5.1

Smoothing reactor inductance in mh

31-35

no

F5.1

Minimum ignition delay angle (\(\alpha_{min}\)) in degrees

36-40

no

F5.1

Maximum ignition delay angle (\(\alpha_{stop}\)) in degrees

41-45

no

F5.1

Converter valve drop per bridge in volts

46-50

no

F5.1

Maximum converter current in amps

51-62

no

A8,F4.0

Commutator bus name and base kV of commutator.

63b

no

A1

Converter code (R1): R — Normal operation as a rectifier I — Normal operation as an Inverter M — Normal operation as an inverter with current margin Blank — A passive DC tap

64-66

no

F3.1

Normal ignition delay angle (\(\alpha_{N}\)) if a rectifier, or normal extinction angle (\(\gamma_{N}\)) if an inverter, in degrees

67-69

no

F3.1

Minimum ignition angle (\(\alpha_{min}\)) if a rectifier, or minimum extinction angle (\(\gamma_{0}\)) in degrees if an inverter

70-75c

no

F6.1

Scheduled net converter DC output power in MW

76-80d

no

F5.1

Scheduled converter DC voltage in kV

  1. A passive DC node has columns 24-80 all blank

  2. If the actual converter operation does not correspond to the converter code, subsequent swing studies will abort.

  3. If the DC power or voltage is not constrained, leave the corresponding field blank or enter a zero value.

  4. If the DC power or voltage is not constrained, leave the corresponding field blank or enter a zero value.

Delete Buses by Area (DA)

This command deletes all buses that reside in the area named in columns 4-13. Place a DA in the first two columns. Format of the input is shown below. This is a change record and must be preceded with a /CHANGES command or otherwise reside in a change set.

_images/Area_Delete_Input_Format.png

Area Delete Input Format

Column Description for Delete Buses by Area Format

Column

ID Field

Format

Content

1-2

yes

A2

Record type - DA

4-13

yes

A10

Area Name

Delete Buses by Zone (DZ)

This command deletes all buses that reside in the zone named in columns 4-5. Place a DZ in the first two columns. Format for input is shown below. This is a change record and must be preceded with a /CHANGES command or otherwise reside in a change set.

_images/Zone_Delete_Input_Format.png

Zone Delete Input Format

Column Description for Delete Buses by Zone Format

Column

ID Field

Format

Content

1-2

yes

A2

Record type - DZ

4-5

yes

A2

Zone Name

Equivalent Transmission Line Branch (E)

This record differs from the type L record by allowing for an asymmetrical pi. Two additional fields of data must describe the second leg to ground admittances. The additional fields occupy the columns which are used for line description and mileage on the L record. In all other aspects, the description of the L branch pertains also to the type E branch.

This branch representation is useful for modeling transmission line components that do not have evenly distributed parameters, such as lines with shunt capacitors and line/transformer combinations.

Following is a sample of a coding sheet for equivalent branch data along with descriptions of its various columns.

_images/Equivalent_Branch_Data_Input_Format.png

Equivalent Branch Data Input Format

Column Description for Equivalent Branch Data

Column

ID Field

Format

Description

1

yes

A1

Record type - E for equivalent

2

no

A1

Blank

3

no

A1

Change code - see System Changes

4-6

no

A3

Ownership code - Line and transformer losses will be summarized by ownership at end of final area summary.

7-14

yes

A8

Bus name 1

15-18

yes

F4.0

Base kV 1

19

no

I1

Tie line metering point flag for area tie lines. 1 in column 19 provides for metering at bus name 1 2 in column 19 provides for metering at bus name 2 Blank allows for program assumption as follows:

Metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus Name 1 will be the metering point.

20-27

yes

A8

Bus name 2

29-31

yes

F4.0

Base kV 2

32

yes

A1

Circuit identification

33

yes

I1

Section number for making an equivalent for series elements. (numeric)

34-37

no

F4.0

Total ampere rating for all lines represented by this record.

38

no

I1

Number of parallel circuits represented by this record, for information purposes only. The equivalent impedance is entered in columns 39-74 for lines with unequal legs.

39-50

no

2F6.5

Per unit R and X on base kV and base MVA.

51-62

no

2F6.5

Per unit G and B at bus name 1 end of line.

63-74

no

2F6.5

Per unit G and B at bus name 2 end of line.

75-77

no

A1,I2

Energization Date - MYY

M = {1,2,3,4,5,6,7,8,9,O,N,D} YY = last two digits of year

78-80

no

A1,I2

De-energization Data - MYY

M = {0,1,2,3,4,5,6,7,8,9,O,N,D} YY = last two digits of year

81-84

no

F4.0

Thermal ratings in Amps

85-88

no

F4.0

Bottleneck rating in Amps

Scheduled Area Intertie (I)

Intertie is the power flowing between two areas. Scheduled Area Intertie are the values scheduled on the area bubble diagrams from which the net area interchange export is derived. The net export is simply the sum of all individual interties emanating from each area. Intertie I records permit the net area interchange schedules to be defined directly from the scheduled intertie quantities. New net area export is computed from these values; they override any scheduled net interchange on the AC control records.

A coding sheet and column descriptions follow.

_images/Area_Intertie_Input_Format.png

Area Intertie Input Format

Column Description for Scheduled Area Intertie

Column

ID Field

Format

Description

1

yes

A1

Record type - I

3

no

A1

Change code - see System Changes

4-13

yes

A10

Area 1

15-24

yes

A10

Area 2

27-34

no

F8.0

Area 1 - Area 2 export in MW. (Import will be negative.) Blanks are interpreted as 0.0 scheduled export

“Scheduled” is actually misapplied because no direct controls are available to regulate the intertie flow between two areas. Net area export can be controlled using area slack buses, but not interarea export, which requires additional but unavailable intertie slack buses. Therefore, without direct control of intertie, the scheduled flow can never be maintained. The term circulating flow is introduced to reconcile the discrepancy between the scheduled and the actual flow:

Circulating flow = Scheduled flow - Actual flow

Circulating flow is also a misnomer because it implies wasteful circulating power eddies within a network. If any circulating flow exists, it is introduced deliberately with the application of transformers (MVAR) or phase shifters (MW). Otherwise the flows will always be distributed optimally to minimize losses by simply following Kirchoff’s voltage and current laws. The circulating flows are calculated in the interchange output.

Balanced Transmission Line Branch (L)

This record defines the identification and the electrical characteristics of a line, section of a line or series capacitor. The model assumes the form of a lumped, symmetric pi. The following identifies a branch item:

  • Line type (L in this case).

  • Bus 1 (name and base kV) and bus 2 (name and base kV).

  • Circuit identification if more than one parallel branch exits.

  • Section number (if appropriate).

Lines can be divided into equivalent series elements identified with unique section numbers. Section numbers need not be consecutive, but must be unique. Sections are presumed to be physically ordered such that the lowest numbered section is connected to bus 1 and the highest is connected to bus 2.

_images/Balanced_Transmission_Line_Branch.png

Balanced Transmission Line Branch

The entries in RATING and MILES are used in output to flag overloaded lines and produce a MW-Miles listing by ownership and voltage class if requested.

The metering point (1 or 2) is used when the line spans two areas which are controlled. A simple comparison of the zones for each terminal bus will determine if that branch is a tie line. The metering point field determines which end of a line will represent the area boundary. The line losses are assigned to the other area. The entry in the No. of CKTS field (column 38) identifies the number of parallel branches represented by the branch item. A blank or zero is interpreted as one. This is for information purposes only.

The DATE IN and DATE OUT columns specify the expected energization and de-energization dates. These are used for descriptive purposes

To simulate a bus tie or bus sectionalizing breaker normally closed, a line impedance of \(X = 0.00020 p.u.\) is used. This allows two sections to be connected or disconnected by adding or deleting this branch.

A sample coding sheet with column explanations follows.

_images/Transmission_Line_Data_Input_Format.png

Transmission Line Data Input Format

Column Description for Transmission Line Data

Column

ID Field

Format

Description

1

yes

A1

Record type - L for branch

2

no

A1

Blank

3

no

A1

Change code - see System Changes

4-6

no

A3

Ownership code - Line and transformer losses will be summarized by ownership at end of final area summary.

7-14

yes

A8

Bus name 1

15-18

yes

F4.0

Base kV 1

19

no

I1

The line metering point for area tie lines. 1 in column 19 provides for metering at bus name 1 end. 2 in column 19 provides for metering at bus name 2 end. Blank allows for program assumption as follows:

Metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus name 1 will be the metering point.

20-27

yes

A8

Bus name 2

29-31

yes

F4.0

Base kV 2

32

no

A1

Circuit identification if more than one parallel branch exists.

33

no

I1

Section number for making an equivalent for series elements (numeric). Program assembles series elements in numerical order of section numbers (need not be consecutive).

34-37

no

F4.0

Total ampere rating for all lines.

38

no

I1

Number of parallel circuits represented by this record, for information purposes only. The equivalent impedance is entered in columns 39-62 for lines with equal legs.

39-44

no

F6.5

Per unit R at base kV and base MVA (normally 100).

45-50

no

F6.5

Per unit X at base kV and base MVA (normally 100).

51-56

no

F6.5

Per unit G_pi/2 at base kV and MVA (normally 100). This format is for balanced lines when Y_pi sending equals Y_pi receiving and only Y_pi needs to be input.

57-62

no

F6.5

Per unit B_pi/2 at base kV and MVA (normally 100). This format is for balanced lines when Y_pi sending equals Y_pi receiving and only Y_pi needs to be input.

63-66

no

F4.1

Circuit miles of line or section.

67-74

no

A8

Descriptive data (alphanumeric, for example 6-wire).

75-77

no

A1,I2

Energization Date - MYY

M = {1,2,3,4,5,6,7,8,9,O,N,D}

YY = last two digits of year

78-80

no

A1,I2

De-energization Data - MYY

M = {0,1,2,3,4,5,6,7,8,9,O,N,D}

YY = last two digits of year

81-84

no

F4.0

Thermal rating in Amps

85-88

no

F4.0

Bottleneck rating in Amps

Two-Terminal DC Line (LD)

This record is used in conjunction with Two-Terminal DC Bus (BD) records; collectively they define the dc model. The dc line data contains pertinent information describing the electrical characteristics of the line, the scheduled dc power and voltage, and the initial firing (ignition) and extinction angles.

Distinction between the inverter and rectifier buses is made with the DC line record using the sign of the scheduled DC power. The direction of power flow is always from rectifier to inverter, and the criteria assumes positive values from bus 1 to bus 2 on the record. Thus, simple modifications in the line data permit power reversals to be modeled with a minimum of data changes. A sample DC line data coding form and column descriptions follow. See figure and table below.

_images/DC_Line_Data_Input_Format.png

DC Line Data Input Format

Column Description for DC Line Data

Columns

ID Field

Format

Descriptions

1-2

yes

A2

Record code - LD for DC line

3

no

A1

Change code - see System Changes

4-6

no

A3

Ownership code, same as on Bus record

7-14

yes

A8

Converter bus name 1 (conventionally the rectifier)

15-18

yes

F4.0

Base kV 1

20-27

yes

A8

Converter bus name 2 (conventionally the inverter)

29-31

yes

F4.0

Base kV 2

34-37

no

F4.0

I rating (amps) - Maximum DC line current in amperes.

38-43

no

F6.2

R (ohms) - DC line resistance, ohms.

44-49

no

F6.2

L (mH) - DC line inductance, millihenries

50-55

no

F6.2

C (uF) - DC line capacitance, microfarads.

56

no

A1

Inverter or rectifier control - Enter R for rectifier control or I for inverter control (point of DC line in which scheduled power is measured).

57-61

no

F5.1

Schedule DC power (MW) - Scheduled DC power in megawatts from converter 1 to 2 metered at the end indicated by I or R in column 56.

62-66

no

F5.1

Schedule DC line volts (kV) - at rectifier end of DC line.

67-70

no

F4.1

Rectifier (\(\alpha_N\)) - Initial firing angle in degrees at rectifier.

71-74

no

F4.1

Inverter (\(\gamma_0\)) - Minimum margin angle in degrees at inverter.

75-78

no

F4.0

Miles - Descriptive information only.

81-84

no

F4.0

Thermal rating in Amps

85-88

no

F4.0

Bottleneck rating in Amps

Multiterminal DC Line (LM)

This data is used in conjunction with Multi-Terminal DC Bus (BM) records. The line data together with the DC bus data define the DC converter terminals and interconnecting DC lines for a multiterminal DC network. This line data contains only the fields for some of the converter quantities which were included on the two-terminal DC format.

Two-terminal (type LD) and multiterminal (type LM) data may coexist within the same base, but cannot coexist on the same DC circuit.

The following shows the multiterminal DC line data coding form format. It is followed by explanations of its various columns.

_images/Multiterminal_DC_Line_Data_Input_Format.png
Column Description for Multiterminal DC Line Type LM

Column

ID Field

Format

Description

1-2

yes

A2

Record Code - LM for multiterminal DC line

3

no

A1

Change code - see System Changes

4-6

no

A3

Ownership code, same as on bus data record

7-14

yes

A8

DC bus name 1

15-18

yes

F4.0

Base kV 1

19

no

I1

Tie line metering point for area tie lines. 1 in column 19 provides for metering at bus name 1 end. 2 in column 19 provides for metering at bus name 2 end. Blank allows for program assumption as follows:

Metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus name 1 will be the metering point

20-27

yes

A8

DC bus name 2

29-31

yes

F4.0

Base kV 2

34-37

no

F4.0

I Rating (Amps) - Maximum DC line current in amperes

38-43

no

F6.2

R (Ohms) - DC line resistance in ohms

44-49

no

F6.2

L (mH) - DC line inductance in millihenries

50-55

no

F6.2

C (uF) - DC line capacitance in microfarads

71-74

no

F4.0

Miles - Descriptive information only

75-77

no

A1,I2

Energization Date - MYY

M = {1,2,3,4,5,6,7,8,9,O,N,D} YY = last two digits of year

78-80

no

A1,I2

De-energization Data - MYY

M = {0,1,2,3,4,5,6,7,8,9,O,N,D} YY = last two digits of year

Factor Change (PO, PZ, PN, PA, PB, PC, PD)

A specialized change record with a P in column 1 enables the loads and generation for all or part of the network to be changed on a multiplying factor basis. These records follow a /CHANGES statement and any Z records.

Note

These change record types were formerly called “Percentage Changes.” This is a change record and must be preceded with a /CHANGES command or otherwise reside in a change set.

Factor changes are performed before any other bus changes are made; therefore, any subsequent bus changes will be unaffected by factor changes. Separate fields permit both active and reactive generation and the active and reactive load to be changed at independent factor. The formula is:

\[NEW INJECTION = OLD INJECTION * (FACTOR)\]

A blank or 1.0 factor retains the present value of the injection while a factor of 2.0 will double the present value.

There are separate factors for \(P\) and \(Q\). If the \(Q\) factor is blank, it will default to the \(P\) factor. For example, if only the \(P\) is to be changed by 0.95 and the \(Q\) left alone, set the \(P\) factor = .95 and \(Q\) factor = 1.0.

Six different subtypes are permitted. Different subtypes may be submitted together. (Their formats are shown on the following pages.)

Subtype O Factor change by ownerships (20 maximum). All AC bus and continuation bus loads and generation with the given ownership will be changed by the specified factors.

Subtype Z Factor change by zones (20 maximum). All AC bus and continuation bus loads and generation within the depicted zones will be changed by the specified factors.

Subtype N Factor change by zone on all nonindustrial loads and generation (20 maximum). All AC bus and continuation bus data except +A, +F, +I or +P continuation bus data within the designated zones will be changed by the specified factors. All zones may be changed with one record having a key zone 00 (zero-zero).

Subtype A Factor change on all loads and generation on all AC bus and continuation bus data (1 only).

Subtype B Factor change by ownerships (20 maximum). All constant impedance and constant current distributed (+ A01, + *I, + *P) loads with the given ownership will be changed by the specified factor.

Subtype C Factor change by zones (20 maximum). All constant impedance and constant distributed loads (+ A01, + *I, + *P) with the given zone will be changed by the specified factor.

Subtype D Factor change by zones (20 maximum). all non-industrial loads within the given zones and optional ownership will be converted into constant impedance and constant current loads.

_images/Factor_Change_by_Ownerships.png

Factor Changen by Ownerships

_images/Factor_Change_by_Zones.png

Factor Change by Zones

_images/Factor_Change_by_Nonindustrial_Loads.png

Factor Change by Nonindustrial Loads

_images/Factor_Change_on_All_Loads_and_Generation.png

Factor Change on All Loads and Generation

_images/Factor_Change_by_Ownerships_of_Constant_Current_and_Impedance_Loads.png

Factor Change by Ownerships of Constant Current and Impeadance Loads

_images/Factor_Change_by_Zones_of_Constant_Current_and_Impedance_Loads.png

Factor Change by Zones of Constant Current and Impedance Loads

_images/Factor_Change_by_Nonindustrial_Loads_of_Constant_Current_and_Impedance_Loads.png

Factor Change by Nonindustrial Loads of Constant Current and Impedance Loads

Column Description of Factor Change Record

Column

Format

Description

1

yes

A1

Record type - P factor change (P represents its former name Percentage Changes)

2

yes

A1

Subtype

O for ownerships Z for all loads in selected zones N for nonindustrial loads in selected zones A for all loads and generatives B for constant current and constant impedance

loads by ownership

C for constant current and constant impedance

loads by zones

10-14

no

F5.0

P factor (decimal fraction) for load

16-20

no

F5.0

Q factor (decimal fraction) for load

22-26

no

F5.0

P factor (decimal fraction) for generation or constant impedance loads

28-32

no

F5.0

Q factor (decimal fraction) for generation or constant impedance loads

Subtypes O and B - record

4-6

yes

A3

Owner code

35-80

no

(A2,1X)

Optional list of zone codes separated by single blanks. Change will be restricted to these listed zones. If no list, all zones are assumed. Note: Subtype C is restricted to the following types of continuation buses: +A01, +A02, *P, *I.

Subtypes Z, C, and N

4-5

yes

A2

Zone code

35-80

no

(A3,1X)

Optional list of ownership codes separated by single blanks. Change will be restricted to these listed owners, if no list, all owners are assumed. Note: Subtype C is restricted to the following types of continuation buses: +A01, +A02, *P, *I.

Reactive Capability Curves (QP, QX, QN)

Three records are required to define a curve: QP, QX, and QN. They may appear anywhere in the input stream although they normally are put immediately after the bus record to which the curve applies. Each curve applies only to the bus named.

Description

The generator capability curve model is a composite of two representations of a synchronous machine capability curve. The first model consists of a set of 1-14 points depicting a piece-wise linear representation of the Q-P characteristics; the second model consists of an optional, constant MVA representation.

As shown in the figure below, the generator capability curve model consists of a series of 1-15 points on the P-Q diagram and a constant MVA secant. Each point is defined by specifying a value for \(P\) followed by values for \(Q_{max}\) and \(Q_{min}\). The constant MVA is specified with \(MMVA\) (Machine MVA), a leading powerfactor (positive reactive), and a lagging powerfactor (negative reactive). If \(MMVA\) is zero, the reactive capability curve is specified exclusively with \(P\), \(Q_{max}\), and \(Q_{min}\) points

If the optional constant MVA representation is invoked, it takes precedence over any (\(P\), \(Q_{max}\), \(Q_{min}\)) point. (Overlap is determined by \(P_{gen}\).)

If the minimum absolute value for \(P\) is less than the first entered value (\(P_1\)), then the model will set the values for \(Q_{max}\) and \(Q_{min}\) equal to \(Q_{max1}\) and \(Q_{min1}\). For any point \(ABS (P_{gen})\) between \(P_1\) and \(MMVA\), the model will linearly interpolate between the \(Q\) values for \(P_j\) just greater than and \(P_{j-1}\) just less than \(ABS(P_{gen})\). \(P_{gen}\) greater than \(MMVA\) generates a fatal data error.

_images/Generator_Capability_Curve_Model.png

Generator Capability Curve Model

Processing

Before solution of the case, each BE, BG, BQ, BX, and BS bus is checked to see if a PQ curve is to be used to set its Q limits. If not, the \(Q_{min}\) and \(Q_{max}\) already stored are used, that is, those read from the bus record or calculated from a prior solution. If a curve is active, the values calculated using it replace those formerly stored. Original input values from the bus record are not saved.

Column Description for Reactive Capability Curves

Column

ID Field

Format

Description

1-2

yes

A2

Record Code -

QP for Pgen values (positive values only) QX for Qmax values (positive values) QN for Qmin values (negative values)

3

no

A1

Change code - For QP record only:

D = Delete curve for this bus. M = Change p.u. code or activity flag. This cannot be used to alter curve data.

To change curve data, enter a complete new set. It is not necessary to delete the curve first; new data will replace the old. Column 3 must be blank.

4-5

no

A2

Unit ID (for informational purposes)

6

no

A1

Activity flag For QP record only:

Blank = Curve active (default when data is entered). * = Inactivate curve. A = Activate formerly inactive curve.

7-14

yes

A8

Bus name

15-18

yes

F4.0

Base kV

19-20

no

I2

Number of units. Total used is number of units times the values specified ( \(P_{gen}\), \(Q_{max}\), \(Q_{min}\) )

21-25

no

F5.2

QP - Maximum MVA QX - Positive (leading) power factor for Qmax QN - Negative (lagging) power factor for Qmin

26-30

no

F5.2

Maximum Pgen (MW/unit). This is an optional hard limit, designating a maximum operating limit.

31-120

no

15F6.2

Up to 15 values for Pgen, Qmax , or Qmin depending on the card type. The values for Pgen can be in any order, but the related Qmin, Qmax values must correspond. Entries must be in consecutive fields with no blank entries between. Pgen (1) must be 0.0.

_images/Reactive_Capability_Curve_QP_Record.png

Reactive Capability Curve QP Record

Regulating Transformer (R, RV, RQ, RP, RN, RM)

This record gives a fixed transformer or phase shifter automatic regulating or control status, provided the proper LTC options on the LTC control record are specified to activate these controls.

This record defines the range of adjustable taps or angles, identifies the adjustable tap side and specifies the desired control and quantity to be held.

The variable tap side of the LTC transformer can be specified in column 19. It can also be determined by comparing the tap range with the base kV at each terminal. If this fails to encompass either base kV, the variable tap side is assigned to the alphabetically highest terminal.

The tap or angle specified on a T record determines the initial parameter setting. If this setting is not encompassed by the LTC tap range, the R record is temporarily deactivated in the solution routine with diagnostic messages. The default LTC control can also be enabled by the command:

/ SOLUTION
> MISC_CNTRL, ..., LTC=ON, ... (Full LTC control)
                       ON_NV (RP,RQ,RM,RN only)
                       ON_NPS (R,RQ,RN only)
                       ON_DCONL(commutating LTC transformers on)
                       OFF

If an LTC transformer reaches a tap limit, the control is temporarily deactivated.

All regulating transformers have provision for either continuous or discrete tap positions. Discretization occurs automatically after a continuous solution is formed.

Several subtypes are available:

Subtype Blank or Subtype V This specifies LTC voltage control on either of the terminal buses. The controlled voltage is entered on the appropriate bus record. The terminal being controlled may be an subtype except G, X or S. If the controlled bus has local reactive control (subtypes E or Q within its limits) the LTC feature is temporarily deactivated. However, if both terminal buses of the transformer are simultaneously reactively controlled, the LTC transformer assumes a different control to minimize the var exchange between buses. This assumes most effective utilization of local VAR sources.

Subtype Q This specifies an LTC transformer that controls the VAR flow through itself. Positive controlled quantities are from bus 1 to bus 2. However, for simplicity, the control point is taken inside the equivalent pi from the fixed tap side to the variable tap side. The controlled VARs value is \(Q_{scheduled} +/- Q_{tolerance}\) when \(Q_{tolerance}\) is the MIN scheduled field and \(Q_{scheduled}\) is the MAX scheduled field.

Subtype P This subtype defines an LTC phase shifter that controls real power flowing through itself. Positive controlled quantities are from bus 1 to bus 2. However, for simplicity, the control point is taken inside the equivalent pi. The controlled power is \(P_{scheduled} +/- P_{tolerance}\) (\(P_{scheduled}\) = MAX SCHED; \(P_{tolerance}\) = MIN SCHED).

Subtype N This specifies an LTC transformer that provides constraints on the reactive power flow through itself. Ordinarily, it provides no control, but if its reactive flow limits are exceeded, it becomes a type Q LTC transformer and holds the MVAR flow within the inequality constraints assigned. The controlled flow is within \(Q_{min} \leq Q_{max}' (:math:\) = MIN SCHED; \(Q_{max}\) = MAX SCHED).

Subtype M This specifies an LTC phase shifter that provides constraints on the active power flow through itself. Ordinarily, it provides no control, but if its active power limits are exceeded, it becomes a type P LTC phase shifter and holds the MW flow within the inequality constraints assigned. The controlled real power flow is within limits \(P_{min} \leq P_{max}\) (\(P_{min}\) = MIN SCHED; \(P_{max}\) = MAX SCHED).

_images/Regulating_Transformer_Data_Input_Format.png

Regulating Transformer Data Input Input Format

Column Description for Regulating Transformer Data

Column

ID Field

Format

Description

1

yes

A1

Record type - R for LTC and automatic phase-shifter data. A record type T must be in same system to provide full data required.

2

no

A1

Subtype - See regulating transformer and phase-shifter subtypes.

3

no

A1

Change code - see System Changes

4-6

no

A3

Ownership code

7-14

yes

A8

Bus name 1

15-18

yes

F4.0

Base kV 1

19

no

I1

Variable tap side if T_max and T_min cannot orient T_x. 0 - Low alpha is fixed 1 - Bus 1 is variable 2 - Bus 2 is variable

20-27

yes

A8

Bus name 2

29-31

yes

F4.0

Base kV 2

34-45

no

A8,F4.0

Controlled bus name and base kV

Multiple Use of columns 46-67 For subtypes blank, V, Q and N

46-55

no

2F5.2

Maximum and minimum kV taps. Data must be entered.

56-57

no

I2

Total number of LTC taps. If blank, program assumes continuous action.

58-67

no

2F5.0

Scheduled MVAR flow (subtype Q) or maximum and minimum MVAR flow (subtype N) through transformer Metered at bus name 1 on this record.

For subtypes P and M

46-55

no

2F5.2

Maximum and minimum angle in degrees. Data must be entered.

56-57

no

I2

Total number of phase shift positions available. If blank, program assumes continuous action.

58-67

no

2F5.0

Scheduled MW flow (subtype P) or maximum and minimum MW flow (subtype M) through transformer. Metered at bus name 1 on this record.

For all subtypes

75-77

no

A1,I2

Energization Date - MYY

M = {1,2,3,4,5,6,7,8,9,O,N,D} YY = last two digits

78-80

no

A1,I2

De-energization Date - MYY

M = {1,2,3,4,5,6,7,8,9,O,N,D} YY = last two digits

Series Compensated RANI Model (RZ)

RANI stands for Rapid Adjustment of Network Impedance and represents a series connected thyristor which changes its series impedance to control power or voltage. See table below.

_images/RANI_Thyristor_Data_Input_Format.png

RANI Thyristor Data Input Format

Column Description for Series Compensated RANI Model

Column

ID Field

Format

Description

1-2

yes

A2

Record type - RZ

3

no

A1

Change Code

Blank - add M - modify D - delete R - restore

7-14

yes

A8

Bus name 1

15-18

yes

F4.0

Base kV 1

19

no

I1

Variable tap side if T_max and T_min cannot orient T_x. 0 - Low alpha is fixed 1 - Bus 1 is variable 2 - Bus 2 is variable

20-27

yes

A8

Bus name 2

29-31

yes

F4.0

Base kV 2

32

yes

A1

ID

33

yes

I1

SECTION

34

no

A1

TYPE 1, 2, or 3

TYPE 1 - Control Pc using Xij TYPE 2 - Control V using Xij TYPE 3 - Control V using Bis

35-39

no

F5.0

Pcmax(MW)

40-44

no

F5.0

Pcmin(MW)

45-48

no

F4.0

Irate(amps)

49-54

no

F6.5

Xijmax(p.u.)

55-60

no

F6.5

Xijmin(p.u.)

61-66

no

F6.5

Bismax (p.u.)

67-72

no

F6.5

Bismin (p.u.)

Transformer Data (T, TP)

This record is applied to two-winding transformers and phase shifters. An equivalent pi representation depicts the transformer admittance in series with an ideal transformer. The electrical data is specified in terms of the transformer data which is defined as follows:

\(R\) Equivalent resistance due to copper loss.

\(X\) Leakage reactance.

\(G\) Equivalent core loss conductance.

\(B\) Magnetizing susceptance (always assumed negative; any sign is overridden).

Transformer taps are specified as fixed values for each voltage level or variable (LTC) taps with control over voltage, real power or reactive power. Variable tap transformers are defined with the addition of a regulating transformer data record (R) described in Regulating Transformer (R, RV, RQ, RP, RN, RM).

_images/Transformer_Data.png

Transformer Data

The following three assumptions are made:

  • Nominal base kV of transformer is identical to that of the bus.

  • Nominal base MVA of transformer is the same as the system base MVA.

  • \(R\), \(X\), \(G\) and \(B\) are evaluated on the nominal base and not on the tap setting.

The base kV is used to calculate the equivalent pi. Complications arise when step-up/step-down transformers are represented as sections in passive node sequence; there is no means to identify the base of the intermittent terminals. This combination is therefore illegal and will abort with fatal diagnostics.

A transformer is identified by subtype blank and a viable entry for TAP 2. A phase shifter is identified either by a subtype P or by a blank field for TAP 2. However, the program always adds the subtype P for distinction and convenience in data changes. The ANGLE is TAP 1 interpreted in degrees. If TAP 2 is blank, a nominal tap is presumed. A phase shifter assumes a pure voltage rotation and an optional transformation. Increasing the ANGLE will decrease the power flowing from bus 1 and bus 2.

Four MVA ratings are used to flag overloaded transformers: nominal, thermal, emergency, and bottleneck. The latter three are “extended ratings”, which supersede nominal ratings. Other entries are similar to the type L record. A sample of the format and explanations follow.

_images/Transformer_Data_Input_Format.png

Transformer Data Input Format

Column Description for Transformer Data

Column

ID Field

Format

Description

1

yes

A1

Record type - T for transformer or phase shifter

2

no

A1

Blank or P

3

no

A1

Change code - see System Changes

4-6

no

A3

Ownership code - Line and transformer losses will be summarized by ownership at end of final Area Summary.

7-14

yes

A8

Bus name 1

15-18

yes

F4.0

Base kV 1

19

no

I1

Tie line metering point flag for area tie lines. 1 in column 19 provides for metering at bus 1 end. 2 in column 19 provides for metering at bus 2 end.

Blank allows for program assumption as follows: Metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then bus 1 will be the metering point.

20-27

yes

A8

Bus name 2

29-31

yes

F4.0

Base kV 2

32

yes

A1

Circuit identification

33

yes

I1

Section number for making an equivalent for series elements (numeric)

34-37

no

F4.0

Total MVA rating for all transformers represented by this record.

38

no

I1

Number of parallel transformer banks represented by this record, for information purposes only. The equivalent impedance is entered in columns 39-62.

39-44

no

F6.5

Per unit impedance R through transformer from bus 1 to bus 2 on the system base MVA for both windings.

45-50

no

F6.5

Per unit impedance X through transformer from bus 1 to bus 2 on the system base MVA for both windings.

51-56

no

F6.5

Per unit G of iron losses on the system base MVA.

57-62

no

F6.5

Per unit B magnetizing current on the system base MVA. Note that any sign is ignored. This quantity will always be processed as a negative value.

63-67

no

F5.2

Fixed bus 1 TAP or fixed phase shift in degrees which describe bus 1 relative to bus 2.

68-72

no

F5.2

Fixed bus 2 TAP or blank for fixed phase shifter.

75-77

no

A1,I2

Energization Date - MYY

M = {1,2,3,4,5,6,7,8,9,O,N,D} YY = last two digits

78-80

no

A1,I2

De-energization Date - MYY

M = {1,2,3,4,5,6,7,8,9,O,N,D} YY = last two digits

81-84

no

F4.0

Thermal rating in MVA

85-88

no

F4.0

Emergency rating in MVA

89-92

no

F4.0

Bottleneck rating in MVA

Switched Reactance (X)

Normally shunt capacitor or shunt reactor installations are represented in power flow programs as fixed MVAR values. However, there frequently is a need to represent voltage controlled capacitor schemes. This program allows for voltage controlled shunt device installations through use of a switched reactance record type X.

This data record must be used with a type BX bus record. The data on the X record identifies blocks of discrete shunt susceptance available for reactive control. The blocks may be either inductive (negative) or capacitive (positive). If both types exist, negative blocks must be given first. Values are given in MVAR at the rated base kV; the actual MVAR is dependent on the voltage. Discrete reactance units are also referred to as statics.

The discrete segments are specified in steps and increments. Steps defines the number of switchable susceptance units. The MVAR value of each unit is given in increments. Normally, each unit has a unique MVAR value. In general, when both reactive and capacitive blocks coexist, two switching lists are given. The reactors are switched first in the following order: unit 1, unit 2,…, unit k, where k is the unit number of last reactor. Similarly, the capacitors are switched next in the following order: unit k+1, unit k+2,…, unit (last). When reactors are switched in, all capacitors are removed and vice versa. Units are sequentially disconnected in the reverse order. For example, the following one line diagram depicts a capacitor installation requiring discrete switching.

_images/Capacitor_Installation_Requiring_Discrete_Switching.png

Capacitor Installation Requiring Discrete Switching

For this example the sequential operation would be as follows. Increment 1, 10 MVAR, would be added up to the number of steps specified (4). If the bus voltage is below the scheduled value after a total of 40 MVARS have been added to the bus, increment 2 would be added to the number of steps specified, and so on until the scheduled voltage is achieved. These statics would be disconnected in a similar fashion, but in the reverse order, to reduce the bus voltage.

Shunt susceptance on BX records is ignored when X records are present. Any shunt susceptance listed on any following + records is considered fixed and is therefore exempt from the above switching.

The format for inputting switched reactance data follows; and then descriptions of the various columns are given.

Note

Negative MVARs must be listed first

_images/Switched_Reactance_Data_Input_Format.png

Switched Reactance Data Input Format

Column Description for Switched Reactance Data

Column

ID Field

Format

Description

1

yes

A1

Record code - X for switched reactance

2

no

Blank

3

no

A1

Change code - see System Changes

4-6

no

A3

Ownership code

7-14

yes

A8

Bus name 1. This is the bus to which the switched reactances are connected. Must be a type BX bus.

15-18

yes

F4.0

Base kV 1

21-28

yes

A8

Bus name 2. Controlled bus name - This bus may be local or remote.

30-32

yes

F4.0

Base kV 2

Increment 1:

33

no

I1

Number of steps - Number of repetitions (from 1 to 9) to be performed using the value given in columns 34-38.

34-38

no

F5.0

MVAR - Value at base kV of each step of Increment 1.

Increment 2:

39

no

I1

Number of steps - Number of times the value given in columns 40-44 will be connected. (Will not begin until Increment 1 is completed.)

40-44

no

F5.0

MVAR - Value at base kV of each step of Increment 2.

Increment 3:

45

no

I1

Number of steps - Number of times the value given in columns 46-50 will be connected. (Will not begin until Increment 2 is completed.)

46-50

no

F5.0

MVAR - Value at base kV of each step of Increment 3.

Increment 4:

51

no

I1

Number of steps - Number of times the value given in columns 52-56 will be connected. (Will not begin until Increment 3 is completed.)

52-56

no

F5.0

MVAR - Value at base kV of each step of Increment 4.

57-80

no

Add data for Increments 5 through 8 in a similar fashion.

Zone Rename (Z)

This is a specialized change record which permits the bus zones to be permanently renamed. This record has a Z in column 1, followed by a maximum of 15 pairs of old zone names/new zone names. Additional Z records may follow to change a maximum of 150 zones. See table below.

Several old zones may be consolidated into a single new zone name. However, an old zone may not be segregated into two more new zones.

Any Z record must be the first change record encountered. The zones are immediately renamed. Following these records, additional system changes may be entered in the normal way, and all data are assumed to conform with the new zone names.

_images/Zone_Rename_Data_Input_Format.png

Zone Rename Data Input Format

Column Description for Zone Rename

Column

ID Field

Format

Description

1

yes

A1

Record type - Z

2-3

no

A2

Blank

4-5

no

A2

Old zone name - any blank zone to be changed must appear in this column. Otherwise, blank “old zones,” terminate the scan.

6-7

no

A2

New zone name

8

no

A2

Blank

9-10

no

A2

Old zone name

11-12

no

A2

New zone name

13

no

A1

Blank

14-15

no

A2

Old zone name

16-17

no

A2

New zone name

18-77

no

Repeat of the above format sequence: one blank followed by two columns for old zone name and two more columns for new zone name.

Area Rename (ZA)

This is a specialized change record that permits area names to be changed. Each ZA record renames one area.

The new name must be unique. If the new name exists, the rename is ignored. Thus, Area Rename cannot be used to consolidate areas.

_images/Area_Rename_Data_Input_Format.png

Area Rename Data Input Format

Column Description for Area Rename

Column

ID Field

Format

Description

1-2

yes

A2

Record type - ZA

3

NA

4-13

no

A10 Old area name

14-15

NA

16-25

no

A10

New area name

26-80

NA

Bus Rename (ZB)

This is a specialized change record that permits bus names and base kV’s as well to be altered. Each ZB record renames one bus.

The new name must be unique. If the new name exists, the rename is ignored. Thus, Bus Rename cannot be used to consolidate buses.

_images/Bus_Rename_Data_Input_Format.png

Bus Rename Data Input Format

Column Description for Bus Rename

Column

ID Field

Format

Description

1-2

yes

A2

Record type - ZB

3-6

NA

7-14

no

A8

Old bus name

15-18

no

F4.0

Old base kV

19-20

NA

21-28

no

A8

New bus name

29-32

no

F4.0

New base kV

33-80

NA

Power Flow Control (PFC)

Overview

This section describes the batch Power Flow Control (PFC) language and its syntax, commands and subcommands. Command entries follow the PFC description in alphabetical order. The table below helps you turn quickly to a specific command entry. The table also gives you a quick description of all of the commands.

Each command entry explains the meaning of the command and gives its syntax. Some commands have subcommands, which are also described. Many entries have additional discussion, and some have examples, particularly where a command’s usage may not be immediately obvious.

The bpf Control Language

The bpf Power Flow Control language (PFC) consists of a sequence of program control statements, each of which in turn consists of commands, subcommands, keywords, and values. All statements have a reserved symbol in column 1 to identify a command or subcommand.

Every statement is scanned, and each command or subcommand found is compared with a dictionary in the program to find the relevant instructions. With the exception of the identifier in column 1 of each statement, PFC is free-form. All statements must be in the PFC file.

PFC has three levels of control, which are identified by one of three identifiers in column one.

  1. The left parenthesis ( identifies the top (or process) level of control. Only four commands are valid here — (POWERFLOW, (NEXTCASE, and (STOP or (END.

  2. The slash / identifies the second (or command) level of control. Many commands are valid here, and they are listed and described in this chapter. Commands generally enable or disable output options, define parameters needed for the process, etc. Subprocesses are major operations involving considerable processing and additional data. Only optional IPF processes are requested with these commands.

  3. The right angle bracket > identifies the third (or subcommand) level of control. A few commands have subcommands associated with them. These subcommands are described in the associated command entries. These subcommands act as qualifiers for the second-level commands.

In addition to the foregoing syntactic units, a command enabling a microfiche option is available. Its control symbol is the left square bracket ([)

_images/Hierarchical_Levels_of_PFC_Statements.png

Hierarchical Levels of PFC Statements

Almost every PFC statement fits one of the following formats, and the few that do not are very similar.

Note

Spaces can be used for readability. Commas are used to separate syntactic units such as a list of values or keyword/value assignments.

Most statements fit on one line, but some extend over multiple lines. These exceptions are noted. When used, put a hyphen (-) where you want to break and continue the command parameters starting in or after column 2 of the next line, column 1 must be blank.

Each general format is followed by an example.

  • A simple command with no keywords or values:

    / command
    / REDUCTION
    
  • A command assigned a simple keyword. (This is a “telescoped” syntax available for some commands.)

    / command = keyword
    / AI_CONTROL = CON
    
  • A command followed by a comma with a keyword. (This is a “telescoped” syntax available for some commands.)

    / command , keyword
    / F_INPUTLIST,NONE
    
  • A command followed by a comma with a value assigned to a keyword.

    / command , keyword = value
    / P_ANALYSIS_RPT, LEVEL = 4
    
  • A command followed by a comma with multiple values assigned to a keyword. Note optional continuation with hyphen (-).

    / command , keyword = value , value , value ,...
    / P_INPUT_LIST, ZONES=NA,NB,NC,ND,NE,NF, -
             NG,NH,NI,NJ,NK
    
  • A command followed by a comma with multiple value/keyword assignments.

    / command , keyword = value , keyword = value ,...
    / MERGE_OLD_BASE, SUB_SYSTEM_ID = AREA-1, OLD_BASE = TESTDC.BAS
    
  • A command followed by a data record(s).

    / command data record
    / NETWORK_DATA
    B     GEN1 HI    230  2  -0.0  -0.0  0.0 0.0      -0.0 -0.0 -0.0
    B     GEN2 HI    230  1  -0.0  -0.0  0.0 0.0      -0.0 -0.0 -0.0
    B     GEN3 HI    230  2  -0.0  -0.0  0.0 0.0      -0.0 -0.0 -0.0
    
  • A subcommand followed by a comma with multiple comma-separated values.

    >subcommand, value, value, value ,...
    >SAVE_ZONES,NA,NB,NC,ND,NE,NF,NG,NH,NI,NJ,NR
    
  • A subcommand followed by a data record on the next line.

    >subcommand
    data record
    >SAVE_AREAS
    A AREA 2
    

Special Characters

Two special characters are available to document the control stream or to improve readability.

  • A period (.) in column 1 of a record identifies a command comment and the record will be ignored by the processing. It is used to document a PFC file or to improve readability. This comment is only visible in a listing of the PFC file or in the editor used to create it.

  • The underscore symbol _ has no syntactic significance and may be used freely to punctuate a word for visual readability.

Note

The hyphen or minus sign “-” and the underscore “_” symbol are different characters! Thus, P_O_W_E_R_F_L_O_W is the same as POWER_FLOW which is the equivalent of POWERFLOW. OLD_BASE is the same as OLDBASE but not the same as OLD-BASE, etc.

Default Convention

All default values for a command are listed on the first line in the command descriptions. Various keywords are listed below the default values. Default values have been selected to satisfy a majority of users; therefore, their use is to invoke exceptions to standard conventions. Once a default value has been enabled, it remains in force for the duration of the process. There is one exception to this:

/ P_INPUT_LIST

After the first case has been processed, P_INPUT_LIST is set to NONE. This conforms to the default philosophy of selecting all options that fulfill a majority of requirements.

Microfiche Control Statement

``[ FICHE,COPIES = n ]``
``( FICHE,COPIES = n )``

This command requests “n” copies of microfiche listings to be made. If it is omitted, the fiche file is not saved. If “”n” is zero or omitted, no copies are made. When it is used, this control must be first in the job stream.

Level 1 PFC Commands

( POWERFLOW )

This command initiates the processing of the network which is defined with subsequent commands and subcommands.

( NEXTCASE )

This is the same as ( POWERFLOW ) except that the base network to be processed is the current network. Changes are expected; otherwise, the same network is processed again with the same data and controls in memory from the previous case. ( NEXT_CASE ) cannot be the first command in a program control file.

( END ) or ( STOP )

This stops the execution of the IPF program.

Each network is processed with a ( POWERFLOW ) or ( NEXTCASE ) command. The first must always be ( POWERFLOW ). Several cases may be concatenated (stacked) in the following format:

``( POWERFLOW )`` statement for case 1
``( POWERFLOW )`` statement or ``( NEXTCASE )`` statement for case 2
.
.
.
``( POWERFLOW )`` statement or ``( NEXTCASE )`` statement for case n
``( STOP )``

The following control statement and the optional keywords that go with it identify the OLD_BASE file, optionally perform miscellaneous temporary changes to OLDBASE, set solution parameters, and solve the resultant network.

(POWERFLOW CASEID = <casename>, PROJECT = <projname>)

casename is a user-assigned 10-character identification for the case. projname is a user-assigned, 20-character identification for the project or study to which this case applies. (No blanks are allowed; use hyphens instead.)

The following statement is used if the Powerflow solution is to be run starting with data and controls from the previous base case in residence.

( NEXTCASE, CASEID = <casename>, PROJECT = <projname> )

Note that / OLD_BASE is not used with a ( NEXTCASE ) statement since a base data file is already in residence.

Level 2 and 3 PFC Commands

Each Level 2 statement starts with a slash (/) in the first position.

After the slash are keywords and/or values separated by a comma (,). Specific values are assigned to the keywords in the following format:

keyword = value

When a keyword is requesting a list, for example, a zone list, the list may be continued on the next record by leaving column 1 of that record blank or by putting a comma in column 1 and continuing the list.

Level 3 statements consist of subcommands that specify keyword values for second-level commands only. Each subcommand for level 3 statements starts with the right angle bracket (>) in column 1. After the right angle bracket are keywords and/or values separated by commas (,). Most often, specific values are assigned by following a keyword with an equal sign (=) and then the desired value.

PFC Commands

The rest of this chapter discusses all the PFC commands, in alphabetical order. Each command entry includes the details of syntax and usage. The more involved commands show examples of use. Refer to the table below to locate a PFC command quickly.

In the format statement for each command, the keywords and parameter values are all vertically aligned in the same column. The top row is the default value. Alternate value assignments such as ON or OFF are identified by the appropriate symbols and have the syntax keyword=value.

Required text is shown in UPPER-CASE while parameter values specified by the user are printed in lower-case and usually enclosed by angle brackets, thus, <list>. Angle brackets are omitted when they may cause confusion with the Level 3 control symbol.

The optional underscore symbol (_) may be used to break up words for visual readability. The computer will read the words as though they were not broken.

PFC Commands

Command Name

Description

AGC

Emulates automatic generation control.

AI_LIST

Specifies detail in area interchange listing.

ANALYSIS_SELECT

Selects analysis reports for printing or microfiche.

BRANCH_DATA

Specifies a master branch and bus data file for base case.

BUS_SENSITIVITIES

Calculates system response to capacitor switching operations.

CHANGE_BUS_TYPE

Disables voltage control in system.

CHANGE_PARAMETERS

Perturbs parameters for start of new solution.

CHANGES

Specifies system data change records.

COMMENT

Specifies comment records.

COMMON_MODE_ANALYSIS

Analyzes the results from a series of common mode cases in the format of the OUTAGE_SIMULATION

F_ANALYSIS_RPT

Specifies report of zones or owners for microfiche.

F_INPUT_LIST

Lists input data on microfiche.

F_OUTPUT_LIST

Lists output data on microfiche.

GEN_DROP

Balances generation drop by picking up generation.

HEADER

Specifies header information for reports.

INCLUDE_CONTROL

Specifies a file for control commands.

LINE_EFF

Defines minimum percent line loading for report.

LINE_SENSITIVITIES

Determines line sensitivity by controlling LTC and AI_CONTROL.

%LOAD_DISTRIBUTION

Converts constant power, etc., into user-specified MVA, etc.

LOSS_SENSITIVITIES

Gives information about system losses.

MERGE_OLD_BASE and

MERGE_NEW_BASE Extracts information from two subsystems to create a new system.

MVA_BASE

Changes base MVA to an assigned MVA.

NETWORK_DATA

Specifies bus and branch data.

NEW_BASE

Defines the file name for a new case.

OI_LIST

Lists ownership interchange.

OLD_BASE

Specifies a previously existing solved case as the new case to start with.

OUTAGE_SIMULATION

Simulates line outages, load dropping, generator outages and rescheduling.

OVERLOAD_RPT

Specifies overload parameter limits for report.

P_ANALYSIS_RPT

Creates an analysis report.

P_INPUT_LIST

Lists input data on paper.

P_OUTPUT_LIST

Lists output on paper.

REBUILD

Rebuilds all data tables from current OLDBASE file.

REDUCTION

Reduces a network.

RPT_SORT

Sorts output data of solved network.

SAVE_FILE

Creates various output files, including the SIF (Stability Interface File).

SOLUTION

Enables solution options and post-solution processes.

SORT_ANALYSIS

Controls sort order for analysis listings.

TRACE

Monitors data to aid data verification.

TRANSFER_SENSITIVITIES

Causes analysis of transfer sensitivities.

TX_EFF

Compares total and core transformer losses.

USER_ANALYSIS

Generates custom analysis listings

AGC

This command emulates automatic generation control (AGC) in the solution algorithm. Under AGC, real power excursions on several generators from base values are allocated in proportion to their total excursion. This in effect distributes the slack bus real power excursions to a set of selected units. The slack bus excursion, which drives AGC, may be either a system slack bus or an area slack bus.

The individual AGC units are identified with type B (bus) records which follow the / AGC command. columns (1:18) correspond with the original format. Beyond column 18, data is free field.

B  <bus_name,base kV>  Pmin=<##>, Pmax=<##>, Pgen=<##>, %=<##>

where

Pmin Minimum generation in MW. Default value is 0.0.

Pmax Maximum generation in MW. Default is Pmax, which is specified on the bus record.

Pgen Base generation is MW, which is used to compute the excursions. Default is scheduled or actual MW from the base case.

% Percentage. The default allocates% in proportion to Pmax

A maximum of 24 AGC units may be specified. One of the units must be a system or area slack bus. Usually, AGC schemes converge faster than non-AGC. The exception occurs when Pmin or Pmax limits are hit and some readjustment occurs.

General Description

An example illustrates the concept. In Case 1, there are two generators, GEN1 and GEN2, with initial and final values shown in the table below.

Values Without AGC

Bus

Initial P

Final P

Excursion

GEN1 (slack)

1000

1442

442

GEN2

1000

1000

0

TOTAL

2000

2442

442

In Case 2, we apply AGC with 50% on each machine. Presuming that losses are unchanged (for simplicity), the initial and final values are shown in the table below.

Values With AGC

Bus

Initial P

%

Final P

Excursion

GEN1 (slack)

1000

50

1221

221

GEN2

1000

50

1221

221

TOTAL

2000

100

2442

442

Notes and Restrictions A maximum of 24 generators are permitted. One of the generators must be a system slack bus or an area interchange bus. Recall that the dynamics which drive AGC comes from slack bus P excursions.

If any unit hits a limit, the remaining active units redistribute their percentages and continue AGC control.

The results are summarized in the listing AGC Control. This listing is controlled with / ANALYSIS_SELECT command.:

/ ANALYSIS_SELECT
> SUM%VAR

If area interchange control is ON, all AGC units should reside in the same area. Violations of this rule are flagged with warning diagnostics. AGC control will obscure the change in slack bus power shown in the tie line Summary of Area Interchange. The true slack bus effects within the area would be the aggregate effects of all AGC units. The area interchange summary obscures this effect.

When / AGC’s and / GEN_DROP coexist, / AGC operates with a higher priority. In actuality, the two should not coexist.

The validity of AGC can be verified in the analysis summary AGC Control. In normal conditions, the scheduled and actual percentage participation should be equal. If these quantities are not equal, it is usually because Pmax or Pmin limits have been hit. In this instance, a comment appears.

Actual % / Sched % = ****.*

All of the active units should have an individual ratio

AI_LIST

This command controls the level of detail in the area interchange listing.:

/ AI_LIST = FULL

FULL is the default. The options are:

FULL Area interchange matrix, Area slack bus summary, and tie line flows.

MATRIX Area interchange matrix.

TIELINE Tie line flow summary

ANALYSIS_SELECT

This selects individual analysis reports for printing or microfiche. It supersedes / F_ANALYSIS and / P_ANALYSIS. Unlike these commands which select groups of reports according to their “level” the / ANALYSIS_SELECT command selects reports individually.

A solitary / ANALYSIS_SELECT command defaults all analysis listings to no print/no fiche status.

Printing and/or microfiche are enabled with the commands: > FICHE and > PAPER. These commands independently restrict the contents of FICHE or PAPER reports to subsets of Zones, Ownerships or Areas.

The desired analysis reports are individually selected using > commands containing abbreviated report names, e.g., > UNSCH.

Each > (report) command accepts an optional F or P qualifier. This will restrict the selected report to Fiche or Print respectively. If neither appear, both F and P are presumed to be selected. For example, > UNSCH, P will print the unscheduled reactive report.

A special option exists on the > LINEFF report. Its entirety is:

> LINEFF, SORT = BUS_NAME, OUTPUT=filename, FIELD_WIDTH =  132,F,P
                                                            80,F,P
>                VOLTAGE,
                 OWNER,
                 ZONE

All quantities are optional.

SORT Controls sorting by bus kV_name, owner_name, or zone name.

OUTPUT Copies a duplicate report to the named file.

FIELD_WIDTH Controls the report width or the named file.

The following is a full list of the / ANALYSIS_SELECT command set.:

/ ANALYSIS_SELECT
> FICHE,ZONES=<zone1,...>,AREAS=<area1,...>,OWNERS=<owner1,...>
> PAPER,ZONES=<zone1,...>,AREAS=<area1,...>,OWNERS=<owner1,...>
> USERAN - User-defined analysis listing. (Used with / USER_ANALYSIS.)
> UNSCH - Buses With Unscheduled Reactive.
> LOSSOWN - Total System Generations and Loads by Owner.
> SYSTEMZONE - System Generations,Loads,Losses and Shunts by Zones.
> UVOV - Undervoltage-Overvoltage Buses.
> LINELOAD - Transmission Lines Loaded Above xxx.x% of Ratings or with more than 30 degrees of electrical angle.
> TRANLOAD - Transformers Loaded Above xxx.x% of Ratings.
> TRANEX - Transformers Excited Above xxx.x% over Tap.
> XSYSTEMLOSS - Transmission System Losses.
> BPALOADS - BPA Industrial Loads.
> DCSYSTEM - DC System.
> SHUNTSUM - Shunt Reactive Summary.
> SUMLTC - Summary of LTC Transformers. - Summary of LTC Reactive Utilization
> SUMPHASE - Summary of Phase-shifters.
> SUM%VAR - Summary of %Var-controlled buses. - Summary of AGC Control - Summary of Line Drop Compensation
> SUMBX - Summary of Type BX buses. > SUMRAN - Summary of Adjustable Var compensation.
> SERIESCOMP - Transmission Lines Containing Series Compensation.
> BUS - Bus Quantities. > SPIN - Spinning Reserves.
> LINEEFF - Transmission Line Efficiency Analysis. (Lines Loaded  Above xxx.x % of Nominal Ratings).
> TRANEFF - Transformer Efficiency Analysis. - Total Losses Above xx.xx % of Nominal Ratings.
> TRANLOSS - Transformer Efficiency Analysis - Core Losses Above xx.xx % of Nominal Ratings.

BRANCH_DATA

/ BRANCH_DATA, FILE = <filespec>, DATE = <myy>,
               BUSDATA_FILE = *
                             <filespec>

This command specifies that the base case will be established from a master branch data file and associated bus data file. Branch data selected from this file will have an energization date (date in) and a de-energization date (date out) corresponding with the DATE specified on the above command.

If BUSDATA_FILE is not specified or has parameter value *, the program expects bus data to follow in the input stream.

See MERGE_OLD_BASE and MERGE_NEW_BASE for more information about branch data file merging. Using the MERGE_OLD_BASE and MERGE_NEW_BASE commands is preferred.

BUS_SENSITIVITIES

/ BUS_SENSITIVITIES

The primary motive of sensitivity is to calculate the instantaneous system response to sudden capacitor switching operations. This is difficult to model in the Powerflow because all LTCs must be turned off. This may cause solution divergence because LTCs are an integral part of any DC system. This problem is circumvented using sensitivities.

By recalculating the Jacobian matrix, various constraints can be changed. The flexibility of these constraints is evident in the format of the sensitivity command.:

/ BUS_SENSITIVITIES,LTC=ON,AI_CONTROL=CON,Q_SHUNT=ADJ,Q_GEN=ADJ
                        OFF,          OFF         FIXED     FIXED
                                      MON

The top line defines the default values.

The first two options correspond with the standard solution options. The second two options define the conditions in which type BQ and BG buses can operate holding constant voltage.

For example, enabling the option Q_SHUNT = FIXED, type BQ buses have all shunt fixed. If there is no rotating machinery (\(Q_{max}\) and \(Q_{min}\) are zero), then the bus holds constant \(Q\) (\(PQ\)). Since type BG buses always have Q_shunt fixed, this option has no affect on generator buses.

Similarly, by enabling the option Q_GEN = FIXED, type BQ and BG buses have all generation fixed and operate in state \(PQ\). Type BG buses will operate in state \(PQ\). If BQ buses have no shunt, they also will operate in state \(PQ\).

In order of time response, the generators respond within several seconds. Thus, Q_GEN will normally be adjustable. LTC’s, DC LTC’s, and switched capacitors are controlled by time-delayed voltage relays to minimize spurious operation.

LTC’s 0.5 - 3.0 minutes

DC LTC’s 5 seconds

CAP/REACTORS:5 - 30 seconds

The slowest component is area interchange control. Its response time is 0.5 to 10 minutes.

By appropriate selection of options, the Jacobian matrix can represent nearly any time frame of response.

Selected Buses

Following the BUS_SENSITIVITIES record, individual buses are selected for perturbation. These buses are identified by the B formatted records that follow them. A maximum of 50 buses may be specified.

The perturbed quantity is identified by nonzero entities in one of the fields: P_load, Q_load, G_shunt, B_shunt, P_generation or Q_generation.

The fields on the B-blank record determine which sensitivity \(\frac{dP}{d\theta}\), \(\frac{dP}{dV}\), or \(\frac{dQ}{dV}\) is computed.

_images/B-blank_Record_Sensitivity_Fields.png

B-blank Record Sensitivity Fields

Field Values for Sensitivities

Sensitivity

Column 2

PLOAD, PSHUNT, PGEN

QLOAD, QSHUNT, QSCHED

\(\frac{dP}{d\theta}\)

Not required

Required

Not required

\(\frac{dP}{dV}\)

Literal: “V”

Required

Not required

\(\frac{dQ}{dV}\)

Not required

Not required

Required

\(\frac{dQ}{dV}\) *

(blank)

(blank)

(blank)

* This is the default.

Repeat Sensitivities

A powerful feature of the sensitivity process is the ability to refactor the Jacobian matrix under different control schemes. For example, one / BUS_SENSITIVITIES record could enable only the Q_GEN option (exciters on, everything else off) for an instantaneous response. Following the necessary B formatted records a second / BUS_SENSITIVITIES record could enable all options for a long term response. Assuming the same bus list is repeated, then a comparison between the two corresponding sensitivities would yield the short-term and long-term effects of the bus’s injection perturbation.

Example

The following is an actual case. Bus OLYMPIA 230 was specified for a -172 MVAR shunt application. If Q_Load or Q_Generator was specified, the actual Q_Perturbation would be -172 MVAR. For Q_Shunt, the Q_Perturbation is calculated.:

Delta (Q)= Q_Shunt * V**2
= -172 * (1.067)**2
= -195.82 MVAR
New_Voltage (kV) = Old_Voltage (kV) + Sensitivity * Delta_Q
= 245.45 kV + 0.0334 * (-195.82)
= 245.45 kV - 6.54 kV
= 238.91 kV

The correct computed value on the listing is 238.90 kV. The different figures in the example are due to round off.

The correlation with actual Powerflow cases is very close. The calculated voltage excursion -6.54 kV is within two percent of the actual excursion. The accuracy is significant because the actual and estimated voltages will differ 0.001 per unit at most!

Sample Deck Setup

(POWERFLOW,...)
.
.
.
/ CHANGES
.
.
.
/ BUS_SENSITIVITIES,LTC=ON,AI_CON=OFF,Q_SHUNT=ADJ,Q_GEN=ADJ
B    MONROE   500       316

Output

BUS_SENSITIVITIES COMPUTED WITH THE FOLLOWING CONTROLS:

                LTC CONTROL              ( )   OFF
                --- -------              (X)   ON (FULL CONTROL     )
                                         ( )   ON (NO VOLTAGE CONTROL)

                AI CONTROL               (X)   OFF
                -- -------               ( )   CONTROL (DEFAULT)
                                         ( )   MONITOR

                Q_SHUNT CONTROL          (X)   ADJUSTABLE
                ------- -------          ( )   FIXED

                Q_GENERATION CONTROL     (X)   ADJUSTABLE
                ------------ -------     ( )   FIXED

 0 MONROE    500.0 A  316.0 MVAR CHANGE IN SHUNT AT THIS BUS WILL CAUSE THE FOLLOWING VOLTAGE CHANGES

 0       BUS       BASE    BUS       BASE    ----- DVOLT/DQ  -----   ------ BASE VOLTAGE -------    ------ NEW VOLTAGE ------
                                             (P.U./P.U.)   (KV/MVAR) (P.U. KV)             (KV)     (P.U.KV)            (KV)
         MV-SVC    19.6                      -0.0106     -0.0023        1.118             21.92      1.081             21.10
         MONROE   500.0                       0.0061      0.0321        1.052            525.84      1.073            537.05
         WRK 25    25.2                       0.0040      0.0010        1.041             26.22      1.054             26.59
         MONROE   230.0                       0.0039      0.0092        1.037            238.54      1.051            241.77
         GDK 4      4.0                       0.0039      0.0002        1.049              4.20      1.063              4.25
         MONROE T 230.0                       0.0038      0.0090        1.035            237.98      1.048            241.12
         RIM 12    12.6                       0.0037      0.0005        1.041             13.11      1.054             13.29
         RYL 12    12.6                       0.0037      0.0005        0.996             12.55      1.009             12.71
         WRK 60B2  60.0                       0.0037      0.0023        1.020             61.17      1.033             61.97
         WRK 60B1  60.0                       0.0037      0.0023        1.020             61.22      1.033             62.01

CHANGE_BUS_TYPE

/ CHANGE_BUS_TYPE

This command disables voltage control in selected areas of the system and performs bus type changes from a voltage control type to a more passive type. The changes it makes are permanent and apply to the case in residence. If this command appears before any system changes, the bus type changes will apply before the system changes, exempting any new or changed buses. If this command appears after any system changes, any new or changed buses will be subject to bus type changes invoked with this command.

An example is shown below.

/ CHANGE_BUS_TYPE, BQ=B,  BG=BQ, BT=B , BX=B , -
                   LTC = OFF, -
                   AREAS=<area_1,...>, -
                   ZONES=<zone_1,...>, -
                   LIST=ON

Bus type changes

Four types of buses may be changed: BQ, BG, BT and BX. All possible bus type transitions are depicted above using the format <old_type> = <new_type>.

The full repertoire is listed in the table below. (Note that some restrictions apply.)

Bus Type Changes

Change

Restriction

BQ –> B

If PGEN = 0.0 and QGEN =0.0

BQ –> BF

If PGEN <= 0.0.

BQ –> BF*

Unconditional.

BG –> BQ

If PGEN > 0.0.

BG –> B

If PGEN <= 0.0.

BG –> BF

If PGEN = 0.0.

BG –> BF*

Unconditional.

BT –> B

(This deletes any adjacent LTCs which are controlling BT nodes.)

BX –> B

BX –> BF

BX –> BF*

LTC Transformer Control

A bus type change BT=B will delete LTCs only if the controlled bus is type BT. A more general option:

LTC = OFF

disables all LTCs within the specified area except for any dc commutating transformers.

LIST

The LIST parameter accepts two values – ON and OFF. The default is ON. This applies to the CHANGE_BUS_TYPE summary where the initial and final state of each bus affected is depicted. Setting LIST=OFF is recommended for repetitious batch runs.

Excluded Buses

Means are available to exempt individual buses from type changes defined in the / CHANGE_BUS_TYPE command. These buses are excluded with the following command:

>EXCLUDE_BUS
B          name     base
B          name     base
. . .
. . .

Line Drop Compensation

This feature temporarily replaces the ordinary BG -> BC voltage control of a remote bus with a BG control of a compensated voltage, which is specified as a percentage within the step up transformer. This control scheme is valid only for this case, and may be introduced only within context of a CHANGE_BUS_TYPE command. In subsequent cases, these generators revert to their normal control mode

The target compensated voltage is defined with a computed voltage limit. That limit is derived from two base case terminal voltages – the BG bus and the remote BC bus (the remote bus may be another type). The formula used is

\[V_{max} = V_{min} = PCT * V^{base}_{BG} + (1 - PCT) * V^{base}_{BC}\]

Example:

/ CHANGE_BUS_TYPE, BQ = B, BX = B, BG = BQ
...
> LINE_DROP_COMPENSATION
BG COULEE 13.8, 70%
BG CHIEF JO13.8, 80%

Restrictions on Line Drop Compensation The following restrictions apply to line drop compensation:

  • All buses selected for Line Drop Compensation must be type BG. All buses selected are exempt from any bus type change BG -> BQ or BG -> B.

  • The controlled remote bus must be immediately adjacent to the generator.

  • The specified percentage should be between 0 and 100%. A warning is issued if the specified percentage is outside this range.

  • A maximum of 20 generators may be selected for line drop compensation.

  • The line drop compensation is case specific. It defines the base solution, but is not saved on the base history data file.

Reactive Compensation

This feature is similar to Line Drop Compensation; it temporarily replaces the ordinary BG -> BC voltage control of a remote bus with a BG control of a compensated voltage, which is specified as the voltage drop from the bus terminal voltage computed with the generator reactive power in series with a user-specified impedance. This control scheme is valid only for this case, and may be introduced only within context of a CHANGE_BUS_TYPE command. In subsequent cases, these generators revert to their normal control mode

The target compensated voltage is defined with a computed voltage limit. That limit is derived from two base case terminal voltages – the BG bus and the remote BC bus (the remote bus may be another type). The formula used is

\[\begin{split}V_{max} = V_{min} = V^{base}_{BG} - \frac{Q_{BG}}{V_{BG}} * X_{BC} \\ X_{c} = \frac{PCT}{100} * \frac{100}{MVA_{base}}\end{split}\]

where \(PCT\) is the user-specified percentage and \(MVA_{base}\) is the user-specified machine MVA.

Example:

/ CHANGE_BUS_TYPE, BQ = B, BX = B, BG = BQ
...
> REACTIVE_COMPENSATION
BG COULEE  13.8, 5%, 100
BG CHIEF JO13.8, 5%, 100

Restrictions on Reactive Compensation The following restrictions apply to reactive compensation are identical to those which apply to line drop compensation:

  • All buses selected for Reactive Compensation must be type BG. All buses selected are exempt from any bus type change BG -> BQ or BG => B.

  • The controlled remote bus must be immediately adjacent to the generator.

  • The specified percentage is typically in the range 5-6%. It may be negative if the voltage is internal to the machine.

  • A maximum of 20 generators may be selected for reactive compensation.

  • The reactive compensation is case specific. It defines the base solution, but is not saved on the base history data file.

Output Reports A special summary of all line drop compensation buses is listed in the analysis group under the title Summary of Line Drop Compensation. It is available either as a level 4 option on the /P_ANALYSIS or /F_ANALYSIS command or as the SUM%VAR option on the /ANALYSIS_SELECT command.

/ANALYSIS_SELECT
SUM%VAR

Example

An example is shown below.:

( POWERFLOW, ...)
...
...
...
/ CHANGES, ...
...
...
...
/ CHANGE_BUS_TYPE, BG=BQ, BT=B ,BX=B, -
                    LTC = OFF, -
                    AREAS = NORTHWEST, LIST=OFF
/ CHANGE _BUS_TYPES,BQ=B,BX=B,BG=BQ,LTC=OFF,AREAS=NORTHWEST,BC-HYDRO
>EXCLUDE_BUSES
B    CENTRALA20.0
B    BONN PH213.8
B    BONNVIL213.8
B    DALLES 313.8
B    DALLES2113.8
B    DALLES2213.8
/ SOLUTION
( END )

In this example, the disabling of remote voltage control is restricted to area NORTHWEST. Within this area, all BG generators are permanently changed to type BQ; all LTCs are disabled; and all BX buses are frozen to their discrete value.

CHANGE_PARAMETERS

/ CHANGE_PARAMETERS, BUS=<name, base>,V=<set_value>,Q=?
                                      VX=<set_value>,QY=?
                                      Q=<set_value>,V=?
                                      QY=<set_value>,QV=?
                                      P=<set_value>,V=?
                                      P=<set_value>,V=?
> BX = LOCKED
B OSTRNDER 500
B MALIN 500

or

/ CHANGE_PARAMETERS,  BUS=<name, base),V=?, -
          %LOAD_CHANGE,%PY=<##>, %QX=<##,  -
               %PX=<##>, %QY=<##, -
          ZONES=NA, NB, ..., -
          OWNERS=BPA, PSP, ...,  -
          AREAS=NORTHWEST

or

/ CHANGE_PARAMETERS,  BUS=<name, base),V=?, -
           %GEN_CHANGE,%PY=<##>, %QX=<##,  -
              %PX=<##>, %QY=<##, -
              ZONES=NA, NB, ..., -
              OWNERS=BPA, PSP, ..., -
              AREAS=NORTHWEST

Note

This is one of the three commands which are order-dependent on the /SOLUTION command (the other two commands are LINE_SENSITIVITIES and LOSS_SENSITIVITIES). Each of these must follow the /SOLUTION command.

The /CHANGE_PARAMETERS command perturbs a specified network parameter immediately after a successful solution, and initiates a new solution. The process continues until the last /CHANGE_PARAMETERS command has been read. All changed network parameters are permanent in the base case in residence. The output, analysis, and saved base case reflecting the final values of the parameters from the last change.

The /CHANGE_ANALYSIS feature is extremely useful to quickly and accurately generate a set of points for plotting Q-V and P-V curves. When used in conjunction with /USER_ANALYSIS, the values of additional network quantities can be extracted during each /CHANGE_PARAMETERS, enriching the scope of examination into the network.

The distribution VX, VY, etc., designates both the quantity and the axis on the X-Y data file. Default values (V, Q, etc.) are shown in Table 4-6.

BX = LOCKED

Type BX buses selected with this feature emulate the characteristics of mechanically switched shunt capacitors (MSC) controlled by a voltage relay. This voltage relay operates within a voltage deadband (\(V_{min}\), \(V_{max}\)):

  1. If \(V_{min} < V < V_{max}\), then freeze present \(X_{shunt}\) value.

  2. If \(V < V_{min}\), switch in additional capacitor steps or switch out connected reactor steps to raise the voltage, one step at a time.

  3. If \(V > V_{min}\), switch out connected capacitor steps or switch in additional reactor steps to lower the voltage, one step at a time.

For exposition, the feature is called BX Locking. In the absence of this feature, the normal operation is to switch \(X_{shunt}\) one step per iteration to bias the bus voltage to \(V_{max}\).

Restrictions on BX Locking

The following restrictions apply to BX locking:

  • Only bus type BX buses may be selected for BX locking.

  • The feature is limited to a maximum of 10 BX locked buses.

  • This feature can be inserted after any / CHANGE_PARAMETERS command. It defines when BX switching on selected BX buses becomes locked. Once defined, BX locking remains in effect for the duration of the study.

  • The voltage limits may be temporarily modified for BX locking. The new voltage limits are entered in columns (58:65) in the ordinary manner. These limits are temporary. After the solution, the original limits will be used for analysis reports.

  • The BX locking feature is not saved on any generated base case.

Bus Perturbation

Two forms of / CHANGE_PARAMETERS are shown. The first form is bus perturbation. Three types of quantities may be perturbed:

V = <set_value> Perturbs the Bus voltage magnitude (p.u.).

P = <set_value> Perturbs the \(P_{gen}\) (MW).

Q = <set_value> Perturbs the \(Q_{gen}\) (MVAR).

Restrictions

V-perturbations are applied on V-constrained buses: BQ not at Q-limits, BE and BS types. If the bus type is unacceptable, it is automatically changed to a type BE and a warning diagnostic is issued.

Q-perturbations are applied on Q-constrained buses: B, BC, BT and BQ in state Q_min or Q_max. If the bus type is unacceptable, it is automatically changed to a type B and a warning diagnostic is issued.

P-perturbation can only be applied on P-constrained buses: all types except BS, BD, BM, and area slack buses.

Load Perturbation

The second form of / CHANGE_PARAMETERS is LOAD perturbation. Either the P_load or the Q_load, or both, may be perturbed a set percentage.

If no ZONES, OWNERS, or AREAS are specified, the percentage change applies to the entire system.

Note that the %P or %Q quantities in the output file correspond to the load that is changed. It may not be the total system load.

The inclusion of OWNERS with either ZONES or AREAS select candidates that are mutually inclusive.

Note that continuation records are accepted here.

For best results, the %LOAD_CHANGE option should be used in conjunction with GEN_DROP. Otherwise, all increase in load is picked up by the area and system slack buses.

Generation Perturbation

The third form of / CHANGE_PARAMETERS is GENERATION perturbation. Either the P_gen or the Q_gen, or both, may be perturbed a set percentage.

If no ZONES, OWNERS, or AREAS are specified, the percentage change applies to the entire system.

Note that the %P or %Q quantities in the output file correspond to the generation that is changed. It may not be the total system generation.

The inclusion of OWNERS with either ZONES or AREAS select candidates that are mutually inclusive.

Note that continuation records are accepted here.

For best results, the %GEN_CHANGE option should be used in conjunction with GEN_DROP. Otherwise, all increase in generation is compensated by the area and system slack buses.

Bus Monitored Quantities

Two types of bus quantities can be monitored:

V = ? Monitors the voltage magnitude.

Q = ? Monitors the reactive allocation including short and unscheduled VARS.

Restrictions apply. V = ? pertains to a BE bus. Q=? pertains to a B bus. Warning diagnostics flag these conditions.

PLOT File

Each / CHANGE_PARAMETERS command generates an x,y plot point in a file with subtype .QVPT.

The composition of these points is dependent upon the composition of the CHANGE_PARAMETERS command. The table below summarizes the output.

CHANGE_PARAMETERS Values in .QVPT File

Set Point

Monitored Point

X Value

Y Value

V=<##>

Q=?

Q

V

Q=<##>

V=?

Q

V

P=<##>

Q=?

Q

P

P=<##>

V=?

P

V

%P=<##>

V=?

P_Load

V

%P=<##>

Q=?

P_Load

Q

%Q=<##>

V=?

Q_L0ad

V

%Q=<##>

Q=?

Q_Load

Q

Each line in the QVPT file is interpreted in the .PFO (power flow output) file.

Example

PLOT POINT 3 X (Q) = ####   Y (V) = ####

This statement says point \(X_3\) pertains to \(Q\) and \(Y_3\) pertains to \(V\).

User Analysis

To circumvent the limitations of monitoring a single bus’s V or Q, additional quantities may be monitored using a user-defined analysis file defined with the / USER_ANALYSIS command.

The user analysis file is processed for each encountered / CHANGE_PARAMETERS command. Its output is appended into an output file with subtype .USR_REPORT

Example 1

/ CHANGES,FILE= *
.
/ CHANGE_BUS_TYPES,BQ=B,BQ=BQ,BX=B,LTC=OFF,AREA=NORTHWEST
.
/ SOLUTION
.
/ CHANGE_PARAMETERS, BUS = RAVER    500., VY = 1.065, QX = ?
/ CHANGE_PARAMETERS, BUS = RAVER    500., VY = 1.060, QX = ?
/ CHANGE_PARAMETERS, BUS = RAVER    500., VY = 1.055, QX = ?
.
.
.
/ CHANGE_PARAMETERS, BUS = RAVER    500., VY = 1.000, QX = ?
(END)

In this example, buses in area NORTHWEST with types BQ, BG, and BX were changed to bring about a freeze in voltage control. The / SOLUTION command is a dummy command, introduced to illustrate the position of the pure / CHANGE_PARAMETERS commands. If the bus name following the BUS = keyword has imbedded blanks, insert a pound sign (#), for example, BELL#BPA.

At the conclusion of an ordinary successful solution, the / CHANGE_PARAMETERS records are processed, one by one. The first encounter will internally change the bus type of RAVER 500 to BE, if it is another type, and set its voltage to \(V = 1.065 p.u.\) The perturbation will force a new Newton-Raphson solution. The \(Q\) of RAVER is monitored. Its perturbed solved values will be printed out.

Subsequent / CHANGE_PARAMETERS commands will perform additional perturbations.

Example 2

/ USER_ANALYSIS,FILE=DRB2:[EOFBMJL]USANLINE.DAT
/ CHANGE_BUS_TYPES, BQ=B,BX=B,BG=BQ,LTC=OFF,AREA=NORTHWEST,BC-HYDRO
/ CHANGE,FILE= *
.
.   THIS CASE MODELS THE P-V CURVE FOR THE POST TRANSIENT
.   CONDITIONS FOLLOWING
.   LOSS OF THE COULEE - RAVER #1 500 kV LINE.
.   INSTALL LINE DROP COMPENSATORS ON COULEE
.   500 UNITS AND JOHN DAY
.   AND ALL DALLES UNITS (EXCEPT 115 kV) AND
.   BONNEVILLE (EXCEPT 115 kV)
.   AND CENTRALIA AND CHIEF JOE
.   300 MVAR SVC AT KEELER AND MAPLE VALLEY
.
BGM   CENTRALA20.0
BGM   BONN PH213.8
.
/ GEN_DROP, INIT=75,AREA=NORTHWEST,BC-HYDRO
B       LIBBY    13.8,   PMIN= 289.2,  PMAX=289.2
.
/ SOLUTION
>AI_CONTROL=MON
.
.MONITOR RAVER 500 VOLTAGE AND INCREASE ZONE NA LOAD
.
/ CHANGE_PARAMETERS, BUS = RAVER    500., V = ?
                           %LOAD_CHANGE  %P = 0.5, %Q = 0.5, ZONES = NA
/ CHANGE_PARAMETERS, BUS= RAVER     500.,  V= ?
                           %LOAD_CHANGE  %P = 0.5, %Q = 0.5, ZONES = NA
/ CHANGE_PARAMETERS, BUS= RAVER      500., V= ?
                           %LOAD_CHANGE  %P = 0.5, %Q = 0.5, ZONES = NA
.
.
(END)

Miscellaneous Notes

If the system is severely perturbed, / CHANGE_PARAMETERS will cause divergence. If this happens, it is assumed that subsequent perturbations will be severe, so divergence will cause them to be ignored. A diagnostic will be issued.

CHANGES

/ CHANGES, FILE = file_name

This command introduces system data change records. Column 3 on all bus, branch, area interchange and area intertie records contain a change code:

blank Add.

M Modify (non-blank fields are changes).

D Delete.

R Restore (previously deleted, available only on (NEXTCASE) runs).

The following is a list of some specialized change commands.

DA Delete all buses within named areas.

DZ Delete all buses within named zones.

PO, PZ, PN, PA Perform percentage changes according to type.

FILE is optional. If included, records in that file will be processed before any additional change records, which may be in the input stream.

COMMENT

/ COMMENT

This command introduces comment records into the output report. The comments will appear at the beginning of some output listings. The /COMMENT command is optional; all C comments in the bpf control file will be processed.

Comment text must have a C in column 1. Up to 20 comment records are permitted. Comment text is put in columns 2-80. Comments are saved in any NEW_BASE file for use when getting a plot.

When bpf loads a base file, any previous comments are deleted, then all comments in the bpf control file are added. The result is that only the comments in the bpf control file are saved.

COMMON_MODE_ANALYSIS

/COMMON_MODE_ANALYSIS, BASE_FILE = <base_file_name>,
                       COMMON_MODE = <common_mode_file>,
                       OUTAGE_FILE = <outage_file>,
                       OUT_FILE = <output_file>

This command combines features of a common mode file used in the CFLOW program pvcurve with the output reports used in the Outage Simulation program, in effect emulating a “slow outage” program. It was written specifically to accept the pvcurve input file without modification.

The outages, defined as MODE within the script in the COMMON_MODE file, typically consists of a sequence of commands /CHANGE_BUS_TYPES, /CHANGES, /SOLUTION, and /GEN_DROP. The mode itself is defined by name on a leading >MODE record; its composition is defined with the change records following a /CHANGES command.

At the end of each >MODE set contaiined within the file named in the COMMMON_MODE command, the solution results (or divergence state) are analyzed: line overloads and bus under/over voltages are written to the user-specified output file in the same format for the OUTAGE_SIMULATION program.

The capability to restrict the analyzed output to subsystems defined with base kV’s and zones as is now done in the OUTAGE_SIMULATION program also exists in this feature. That is the purpose of the OUTAGE_FILE. The OUTAGE_FILE is a bone fide OUTAGE_SIMULATION file which processes only two of its commands: >OVERLOAD and >OUTAGE. All others are ignored. (The >OUTAGE command is used only if the >OVERLOAD commnad is missing and becomes a clone of an implied >OVERLOAD command.)

Description of Operation

Three phases are involved.

  1. Initialization phase. The /COMMON_MODE_ANALYSIS record is parsed and the relevant input and output files are opened.

  2. The mail loop to process >MODE records. The base case in residence is reloaded and the associated processes within the >MODE set are processed exactly in the manner performed in the batch powerflow program. At the conclusion of a solution the output results (line overloads, bus under/over voltages, and any solution divergence) are tabulated in interrnal arrays.

  3. At the conclusion of the last >MODE command, the tabulated results are cross-compiled and outputted exzactly in the form as is none in the OUTAGE_SIMULATION program.

F_ANALYSIS_RPT

/ F_ANALYSIS_RPT , LEVEL =4 , *
                          1   ZONES = <list>
                          2   OWNERS = <list>
                          3

This command requests that an analysis report for selected zones or owners be added to the microfiche output file. Note that a separate command [FICHE] must be present in order to save anything on microfiche, regardless of printer and analysis options selected.

When <list> is blank, asterisk, or null, ALL is assumed unless limited by a preceding statement.

The level number determines the analysis summaries to be displayed.

For LEVEL=1, the following summaries are included:

  • User-defined analysis (optional).

  • Buses with unscheduled reactive.

For LEVEL=2, the following are displayed with summaries for LEVEL=1:

  • Total system generations and loads by owner.

  • System generations, loads, losses and shunts by zones.

  • Undervoltage-overvoltage buses.

  • Transmission lines loaded above XX.X% of ratings.

  • Transformers loaded above XX.X% of ratings.

  • Transformer excited above 5% over tap.

  • Transmission system losses.

  • BPA industrial loads.

  • dc system.

  • Shunt reactive summary.

  • Summary of LTC transformers.

  • Summary of phase-shifters.

  • Summary of %Var-controlled buses.

  • Summary of type BX buses.

  • Summary of adjustable Var compensation.

  • Transmission lines containing series compensation.

For LEVEL=3, the following is displayed in addition to the LEVEL=2 output:

  • Bus quantities.

For LEVEL=4, the following are displayed in addition to the LEVEL=3 display:

  • Spinning reserves.

  • Transmission line efficiency analysis. Lines loaded above XX.X% of nominal ratings.

  • Transformer efficiency analysis. Total losses above X.XX% of nominal ratings.

  • Transformer efficiency analysis. Core losses above X.XX% of nominal ratings.

Example

/ F_ANALYSIS_RPT, LEVEL=4, OWNERS= BPA,PGE,PPL,WPS
/ P_ANALYSIS_RPT, LEVEL=1, ZONES = NA, NB, NC
/ F_ANALYSIS_RPT, LEVEL=4, *
/ P_ANALYSIS_RPT, LEVEL=1, ZONES = *

F_INPUT_LIST

/ F_INPUT_LIST, FULL,  ERRORS = NO_LIST
                NONE            LIST
                ZONES = <list>
                ZONES = ALL, FULL or NONE

This command lists input data on FICHE. Output can be restricted to individual zones specified in <list> and separated with commas. Note that FULL or NONE may be specified in two forms.

The ERRORS option is set to suppress the input fiche if any fatal (F) errors are encountered. This is the default. It can be overridden by setting ERRORS = LIST.

F_OUTPUT_LIST

/ F_OUTPUT_LIST, FULL, FAILED_SOL = FULL_LIST
                 NONE               PARTIAL_LIST
                 ZONES = <list>     NO_LIST
                 ZONES = ALL, FULL or NONE

This command lists output on FICHE. Output can be restricted to individual zones specified in <list> which are separated with commas. Note that FULL or NONE may be specified in two forms.

The FAILED_SOL option is set to override the output listing if a failed solution occurs. It defaults to a full listing. A PARTIAL_LIST observes zone lists.

GEN_DROP

/ GEN_DROP, ..., INITIAL_DROP=#### ...

This feature picks up generation from selected generators to balance generation drop. Generation is dropped in one of two ways:

  • By system changes with the amount specified under INITIAL_DROP.

  • By PMIN and PMAX limits on selected generators. (These buses are specified with specially formatted B records which follow.)

Generator dropping emulates the short-term characteristics of a system’s response where the generation deficit is automatically picked by other machines. The magnitude is presumed to be proportional to PMAX after the effects of the machine’s transients have damped out.

Candidate generators that pickup are those in the area of interest with a spinning reserve (a surplus of \(P_{max}\) over \(P_{gen}\)). The pickup of an eligible machine “i” is allocated proportionally by the ratio

\[GEN\_PICKUP(i) = P_{max}(i) * (TOTAL_DROPPED / TOTAL_PMAX)\]

where \(TOTAL_DROPPED\) is the sum of dropped MW, and \(TOTAL_PMAX\) is the sum of all candidate machines with spinning reserve.

Some machines may be driven to their \(P_{max}\) limits during reallocation. In this case, the allocation becomes nonlinear and several iterations may be required. A detailed list of each command follows.:

/ GEN_DROP, AI_CONTROL=CON, INITIAL_DROP= ####, TOL=####,
                     MON
                     OFF
          AREAS=<area_1,...> Optional. Do not use with ZONE.
          ZONES=<zone_1,...> Optional. Do not use with AREA.

Note that continuation records are acceptable here.

The individual fields of the GEN_DROP command follow.

Area Interchange Control

If generation dropping and allocation occurs over several areas, intertie flows may be substantially affected, and it is recommended to change the area interchange from control to monitor unless the new interchange schedule is known.:

AI_CONTROL = CON : Control area interchange.
             OFF : Turn off area interchange.
             MON : Monitor area interchange.

Note

One other command also affects area interchange control, the >AI_CONTROL option on the /SOLUTION record. If this follows the /GEN_DROP command above, it may overwrite the selected option.

Initial Dropped Generation

This is necessary if the dropped generators are deleted or modified in a change case.

INITIAL_DROP = ####

The field #### denotes the numerical values in MW.

Initial dropped generation may be specified in an alternate method, called the “computed dropped generation.”

Tolerance

Generation reallocation continues until the mismatch between generation dropped and generation pickup is less than the tolerance. The default value is 10 MW.

TOL = ####

The field #### denotes the numerical values in MW.

Areas or Zones

The generation to be picked up may be either system-wide (the default) or restricted to a set of areas or zones.

AREAS = <area_1,...>

or

ZONES = <zone_1,...>

The individual areas are separated with a comma (,). If the area name contains a blank, temporarily replace the blank field with a pound sign (#). Continuation records may be employed for aesthetics.

For example,:

AREAS =NORTHWEST, -
   BC-HYDRO, -
   IDAHO, -
   MONTANA, -
   TRANSALTA, -
   WKOOTENA

Exclude Buses

Means are available to contract the system or subsystem defined in the /GEN_DROP command. Individual buses may be excluded from participating in generator pick-up. These buses are selected with the following command:

>EXCLUDE_BUS
B name base
B name base

Selected Generators To Be Dropped

The amount of generation is defined as the sum of INITIAL_DROP plus the computed generation to be dropped. The computed generation drop is the amount of violation of P-limits on all specified buses:

PMIN  < PGEN  < PMAX

Obviously, only area and slack buses and AGC candidates permit the P-generation to change. Limits can be placed on these buses by specifying a + or - tolerance, or a PMIN and PMAX (in MWs). PMIN keeps slack buses within a narrow range. The special B records introduce these limits explicitly. This is illustrated with the following example:

B     MORRO 4 18.0, TOL = 20
B     MORRO 4 18.0, PMIN = 147, PMAX = 167

If the key words PTOL, PMIN, or PMAX are omitted, PMAX is taken from the PMAX field on the original or changed bus data record. Recall that on the bus record there is no corresponding field for PMIN. Consequently, PMIN = 0.0. At least one B record must be present.

Example

( POWERFLOW, ...)
...
...
/ CHANGES, ...
...
... (changes which drop 2450 MW of generation in the Northwest)
...
/ GEN_DROP, AI_CONTROL=MON, TOL=1.0, INIT=2450
BX    MORRO 4   18, PMIN = 147, PMAX = 167
/ SOLUTION
( END )

Note

MORRO 4 is held between 147 and 167 MWs. Dropping 2450 MWs and picking it up elsewhere will change the generation flows and, quite likely, will alter the system losses. The system slack bus accommodates these changes in losses.

INCLUDE_CONTROL

/ INCLUDE_CONTROL, file = <filespec>

This command permits the input stream containing commands to be temporarily diverted to the named file. Following an end-of-file, control reverts to the normal input stream. Some restrictions apply. This “included” command file cannot contain any of the following commands:

/ INCLUDE_CON statement

/ MERGE_BASE statement

/ OUTAGE_SIM statement

/ REDUCTION statement

/ CHANGES statement

LINE_EFF

/ LINE_EFF, LOADING = <nn>, OWNERS = <list>

Use this command to list lines that are loaded above the prescribed LOADING. The output can be filtered by owners. BPA is the default if no owners are specified.

LINE_SENSITIVITIES

/ LINE_SENSITIVITIES

Note

Three commands are dependent on the SOLUTION command. The commands are CHANGE_PARAMETERS, LINE_SENSITIVITIES, and LOSS_SENSITIVITIES. These three work correctly only if they immediately follow the SOLUTION command.

Line sensitivities relate line immittances (impedance or admittance) to voltage, real power flow, and system losses. Six types are available.

\(d\frac{P_{ij}}{dX_t}\) Change in lineflow \(P_{ij}\) with respect to change in transfer reactance \(X_t\) .

\(d\frac{P_{ij}}{dB_s}\) Change in lineflow \(P_{ij}\) with respect to change in shunt susceptance \(B_s\) .

\(d\frac{Loss}{dX_t}\) Change in system losses with respect to a change in transfer reactance \(X_t\) .

\(d\frac{Loss}{dB_s}\) Change in system losses with respect to a change in shunt susceptance \(B_s\) .

\(d\frac{V_i}{dX_t}\) Change in bus voltage (\(V_i\)) with respect to a change in transfer reactance \(X_t\).

\(d\frac{V_i}{dB_s}\) Change in bus voltage (\(V_i\)) with respect to a change in shunt susceptance \(B_s\) .

The change in transfer reactance \(X_t\) or shunt susceptance \(B_s\) pertains to an existing line. The command statement which invokes line sensitivities is:

/ LINE_SENSITIVITIES, LTC =ON, AI_CONTROL = CON
                           OFF              MON
                                            OFF

The top line depicts default quantities. The options LTC and AI_CONTROL pertain to LTC transformers and area interchange control.

The second part of the sensitivities is the perturbed quantities \(dX_t\) or \(dB_s\). They are defined with specially formatted > records and are similar to L records.

Line Sensitivities

Columns

Format

Description

(1:3)

A3

>PB: \(\frac{dP_{ij}}{dB_s}\) or \(\frac{dP_{ij}}{dX_t}\) >LB: \(\frac{dLoss}{dB_s}\) or \(\frac{dLoss}{dX_t}\) >VB: \(\frac{dV_i}{dB_s}\) or \(\frac{dV_i}{dX_t}\)

(7:18)

A8,F4.0

Bus1 name and base kV

(20:31)

A8,F4.0

Bus2 name and base kV

A1

Circuit ID

I1

Section number

(45:50)

F6.5

Perturbed \(X_t\)

(57:62)

F6.5

Perturbed \(B_s\)

A maximum of 50 perturbed quantity > records may be present.

The ambiguity \(d(.)/dB_s\) or \(d(.)/dX_t\) is resolved by non-zero entities for \(X_t\) or \(B_s\) . If both are zero, the default is \(X_t\) . Non-zero entities define the magnitude of the perturbed quantity \(Delta X_t\) or \(Delta B_s\). Perturbed flows, losses, or voltages will be computed using these values.

The perturbed branch flows \(P_{ij}\) are identified with the individual L records that follow. If parallel lines are present, \(P_{ij}\) pertains to the total of all parallel flows.

The perturbed voltages are the 20 largest excursions effected by the change in immittance. The perturbed losses are a simple quantity. An example setup follows:

( POWERFLOW, ...)
...
...
...
/ SOLUTION
...
...
...
/ LINE_SENSITIVITIES, AI_CONTROL=ON, LTC=ON
>PB   RAVER    500 TACOMA   500
L     RAVER    500 TACOMA   500
L     GRIZZLY  500 JOHN DAY 500
L     GRIZZLY  500 MALIN    500
L     HANFORD  500 JOHN DAY 500
L     HANFORD  500 LOW MON  500
L     HANFORD  500 OSTRNDER 500
L     HANFORD  500 VANTAGE  500
>LB   RAVER    500 TACOMA   500
>VB   RAVER    500 TACOMA   500
>PB   GRIZZLY  500 JOHN DAY 500
L     RAVER    500 TACOMA   500
L     GRIZZLY  500 JOHN DAY 500
L     GRIZZLY  500 MALIN    500
L     HANFORD  500 JOHN DAY 500
L     HANFORD  500 LOW MON  500
L     HANFORD  500 OSTRNDER 500
L     HANFORD  500 VANTAGE  500
( STOP )

Notes

The first perturbation >PB with blank \(X_t\) and \(B_s\) fields requests \(\frac{dP_{ij}}{dX_t}\) (the default). The individual \(P_{ij}\) records.

The second perturbation >LB with blank \(X_t\) and \(B_s\) fields requests \(\frac{dLoss}{dX_t}\) (the default). No L records follow because the monitored quantities are system losses.

The third perturbation >VB with blank \(X_t\) and \(B_s\) fields requests \(\frac{dV_i}{dX_t}\) (the default). No L records follow because the monitored quantities are perturbed voltages. The 20 largest excursions are listed.

Sample Deck Set-up

(POWERFLOW,...)
. . .
/ CHANGES
. . .
/ SOLUTION
. . .
/ BUS_SENSITIVITIES,LTC=ON,AI_CON=ON,Q_GEN=ON,Q_SHUNT=ON
B    SATSUP  230     -172
B    OLYMPIA 230     -172
/ BUS_SENSITIVITIES,LTC=OFF,AI_CON=OFF,Q_GEN=ON,Q_SHUNT=FIXED
B    SATSUP  230     -172
B    OLYMPIA 230     -172
(END)

%LOAD_DISTRIBUTION

/ %LOAD_DISTRIBUTION, DISTRIBUTED_VOLTAGE = NOMINAL_BASE

This set of commands automatically converts constant power, constant current, or constant impedance loads to a user-specified distribution of constant MVA, constant current, and constant impedance.

The option DISTRIBUTED_VOLTAGE (or DIST for abbreviated form) selects either NOMINAL (all voltages are 1.0 p.u.) or BASE, which is the individual bus’s voltage.

Constant Current and Impedance Loads

Constant current loads and constant impedance loads are defined by continuation bus (+) records using reserved TYPE s and CODE_YR s. Constant impedance loads differ from \(G_{shunt}\) and \(B_{shunt}\) quantities in the sense that these quantities are converted into loads and appear in special analysis summaries. The table below describes these special codes and their interpretations.

Special Continuation Bus Types

Type

Owner

CODE_YR

P_LOAD

Q_LOAD

G_SHUNT

B_SHUNT

+A

\(B_{fixed}\) a

+A

00

\(B_{fixed}\)

+A

01

\(P(I)\) b

\(Q(I)\) c

\(P(G)\) d

\(Q(B)\) e

+A

01

\(P(I)\)

\(Q(I)\)

\(G_{equiv}\) f

\(B_{equiv}\) g

+A

02 *I *P

\(P(I)\)

\(Q(I)\)

\(P(G)\) \(P(G)\) \(P(G)\)

\(Q(B)\) \(Q(B)\) \(Q(B)\)

  1. \(B_{fixed}\) = Shunt is pi_back shunt impedance from / CUTTING.

  2. \(P(I)\) = Power is a function of current (constant current).

  3. \(Q(I)\) = Reactive is a function of current (constant current).

  4. \(P(G)\) = Power is a function of shunt \(G\) (constant impedance).

  5. \(Q(B)\) = Reactive is a function of shunt \(B\) (constant impedance).

  6. \(G_{equiv}\) = Shunt is equivalent shunt impedance from / REDUCTION.

  7. \(B_{equiv}\) = Shunt is equivalent shunt impedance from / REDUCTION.

Description of Constant Current Load Model

For expositional purposes, we will call constant current \(A_{load}\) and \(B_{load}\). This nomenclature is consistent with the expression for complex current:

\(I = A + jB\)

The power at a constant current load is computed with the expression

\(P_{load} + jQ_{load} = complx( V ) * conjg( I )\)

where \(complx(V)\) is the complex voltage and \(conjg(I)\) is the conjugate of the complex current. The use of the conjugate expression is needlessly complicated for this simple application and has been relaxed. The quantity Bload is stored as its conjugate, that is, no sign reversal is needed to interpret the correct sign of the load in MVAR.

Let \(V\) denote the per unit base or nominal voltage magnitude - depending upon the option DISTRIBUTED_VOLTAGE. The distributed constant current loads in MW and MVAR are computed as follows:

\[\begin{split}P_{load} &= A_{load} * V \\ Q_{load} &= B_{load} * V\end{split}\]

Readers may note that this is not true constant current. True constant current loads involve the system phase angle. The modelling here is more lenient: it is constant power factor.

Description of Distribution Factors

Six percentage distribution factors can be specified by the user. The following example illustrates the relation.

\[\begin{split}P_{load} &= 50% P + 25% I + 25% Z \\ Q_{load} &= 50% Q + 25% I + 25% Z\end{split}\]

From this command, the following quantities will be defined:

\[\begin{split}PP (%Constant P_{load}) &= 50% \\ PI (%Constant I_{load}) &= 25% \\ PZ (%Constant Z_{load}) &= 25% \\ QP (%Constant Q_{load}) &= 50% \\ QI (%Constant I_{load}) &= 25% \\ QZ (%Constant Z_{load}) &= 25%\end{split}\]

There are restrictions; the percentage distributions must be complete.

\[\begin{split}PP + PI + PZ &= 100.0 \\ QP + QI + QZ &= 100.0\end{split}\]

This means that if some load is to be unchanged, a value of 100% must be entered for \(P_{load}\) or \(Q_{load}\).

The following relations hold at the base voltages:

\[ \begin{align}\begin{aligned}Constant MVA Constant MVA Constant I Constant Z\\P_{load_{old}} &= P_{load_{new}} + A_{load} * V + G_{shunt} * V^2\\Q_{load_{old}} &= Q_{load_{new}} + B_{load} * V - B_{shunt} * V^2\end{aligned}\end{align} \]

where

\(P_{load_{new}}\) (MW) = \(P_{load_{old}}\) (MW) \(* PP / 100\)

\(Q_{load_{new}}\) (MVAR) = \(Q_{load_{old}}\) (MVAR) \(* QP / 100\)

\(A_{load}\) (MW) = \(P_{load_{old}}\) (MW) \(* PI / (100 * V)\)

\(B_{load}\) (MVAR) = \(Q_{load_{old}}\) (MVAR) \(* QI / (100 * V)\)

\(G_{shunt}\) (MW) = \(P_{load_{old}}\) (MW) \(* PZ / (100 * V^2)\)

\(B_{shunt}\) (MVAR) = \(--Q_{load_{old}}\) (MVAR) \(* QZ / (100 * V^2)\)

The negative sign for \(B_{shunt}\) is correct. The actual expression is

\[P + jQ = conjg (Y) * V^2\]

A positive value of \(G_{shunt}\) is the same sign as load; a positive value of Bshunt is the same sign as generation.

Those buses whose loads can be distributed can be selected either individually or systematically. Individually selected buses require the > CHANGE_BUSES command. Systematically selected buses require the > CHANGE_SYSTEM command.

Systematically Selected Buses

> CHANGE_SYSTEM, PLOAD  = ##% P + ##% I + ##% Z,
                 QLOAD  = ##% Q + ##% I + ##% Z,
                 AREAS  = area_1. ...,
                 ZONES  = zones_1, ...,
                 OWNERS = owner_1,
> EXCLUDE_BUSES
B      name    base
B      name    base
B      name    base

This example redistributes constant power loads according to the specified percentages.

The redistributed constant current and constant impedance loads are transferred to a new +A01 continuation bus record. The redistributed constant power loads replace the original constant power load.

A special feature has been added to redistribute constant current and constant impedance loads that already have been distributed. As such, these loads are restricted to +A01 and +A02 continuation bus records. The table below describes these options.

Constant Power, Current, and Impedance Keywords

Type of Load to Convert

Keyword for Real Part

Keyword for Reactive Part

Constant Power

PLOAD =

QLOAD =

Constant Current

ALOAD =

BLOAD =

Constant Impedance

RLOAD =

XLOAD =

For example, to change constant current loads, the following commands are used:

> CHANGE_SYSTEM, ALOAD = ##%  P + ##% I + ##% Z,
                 BLOAD = ##%  Q + ##% I + ##% Z,

The network affected by the specified load change percentages can be restricted to buses within a given subsystem. This subsystem can be defined by those buses having common attributes in two sets:

{ AREAS, OWNERS }

or:

{ ZONES, OWNERS }

ZONES and AREAS are mutually exclusive; only one of the above can be specified.

If no owners are specified, all ownerships are implied. The selected subsystem can be further defined by excluding specific bases with the >EXCLUDE option.

More than one set of CHANGE_SYSTEM commands is permitted. This would permit buses in different areas or zones to have different percentage distribution factors. In case of overlap, precedence is given to the first definition.

Individually Selected Buses

> CHANGE_BUSES, CHANGE_TYPE = PLOAD
                              ALOAD
                              RLOAD
B    ownname    base    ####  ####   ####  ####   ####  ####  PLOAD
B    ownname    base    ####  ####   ####  ####   ####  ####  ALOAD
+x   ownname    base yr ####  ####   ####  ####   ####  ####
+x   ownname    base yr ####  ####   ####  ####   ####  ####

This command permits unique distribution factors to be specified for individual buses. The buses and their distribution factors are identified on fixed field records. The format of the B % load change record is shown in the figure below. CHANGE_TYPE is optional. ALOAD and RLOAD have the same interpretation given in Table 4-8. Thus, they would apply to + records, but not to B records.

If the ownership field is blank or includes the bus ownership, the percentages apply only to data on the bus B record. Continuation bus data will not be affected.

On the other hand, if the ownership is the magic code ###, the percentages apply to data on the bus B record and also to data on all associated continuation bus records.

_images/CHANGE_BUS_Load_Input_Format_for_B_Records.png

CHANGE_BUS % Load Input Format for B Records

If separate % changes are to apply to bus and continuation bus records, separate + % change records must be used—one for the bus B record and others for the specific + bus records.

The identification fields for + % bus records are identical to those for the + records as in the table below.

Identification Fields for +% Records

Column

Quantity

1

2

Type

3- 6

Ownership

7-18

Bus Name and Base kV

19-20

Code Year

The format of the + % load change records is shown below.

_images/CHANGE_BUS_Load_Input_Format_For_plus_Records.png

CHANGE_BUS % Load Input Format for + Records

Wildcards are permitted in these fields: TYPE, OWNER, and CODE_YR. The wild card character(s) for those fields are #, ###, and ## respectively.

The percentages apply to the distribution of QLOAD and PLOAD to ALOAD and BLOAD, or to RLOAD and XLOAD. They must total 100% each.

If an overlap occurs with the CHANGE_SYSTEM command, precedence is given to the individually specified buses.

A maximum of 2,000 buses may be specified. Once identified, that bus will be unaffected by any subsequent commands.

Example 1

PLOAD, QLOAD distributions applied to a bus record. See figure below.:

PLOAD = % PL + % PI + % PZ
QLOAD = % QL + % QI + % QZ
_images/Original_B_Record.png

Original B Record

  1. Remove PLOAD and QLOAD quantities from bus record above.

  2. Calculate the following quantities

P1 = PLOAD * %PL
Q1 = QLOAD * %QL
P2 = PLOAD * %PI  / VOLTAGE
Q2 = QLOAD * %QI / VOLTAGE
P3 = PLOAD * %PZ / VOLTAGE ** 2
Q3 = QLOAD * %QZ / VOLTAGE ** 2
  1. Replace the load and shunt fields on the B record and on a new +A*I record.

Modified B record and new +A*I record. See below.

_images/Modified_B_Record.png

Modified B Record

Example 2

ALOAD, BLOAD distributions applied on a +X*P bus record.:

ALOAD = %PL + %PI + %PZ
BLOAD = %QL + %QI + %QZ

Note that ALOAD and BLOAD quantities are generated by prior %LOAD_DISTRIBUTION. Thus, this record corresponds to a + record having the same TYPE and CODE_YEAR. See below.

_images/Original_Continuation_Record.png

Original Continuation Record

  1. Remove ALOAD and BLOAD quantities from the +X*I record above. Note that these quantities are constant current. Convert them into constant power:

PLOAD = ALOAD * %PL VOLTAGE QLOAD = BLOAD * %PL VOLTAGE

  1. Calculate the following quantities:

P1 = PLOAD * %PL Q1 = QLOAD * %QL P2 = PLOAD * %PI / VOLTAGE Q2 = QLOAD * %QI / VOLTAGE P3 = PLOAD * %PZ / VOLTAGE ** 2 Q3 = QLOAD * %QZ / VOLTAGE ** 2

  1. Replace the load and shunt fields on the original + record and the load fields on the original type +X record.

Modified +X*I record and new +A*P record. See below.

_images/Modified_Continuation_Record.png

Modified Continuation Record

Limitations, Restrictions, and Assumptions

The load distribution is presumed to apply to a solved base case. At the base solution, the total load in MWs and MVARs is unchanged after distribution. If the system is not otherwise changed, the solution should converge to the base solution.

Each nonzero load on a bus or continuation bus record generates an associated constant current and constant impedance load on an equivalent +A*I continuation bus record. The continuation bus array is currently dimensioned for 3360 records.

The number of generated +*I and +*P records in a typical base case averages 400 (assuming one for each continuation bus) plus one for each number of nonzero load on the bus records.

BPA’s Transient Stability Program in its present form cannot accommodate the Powerflow model of constant current loads.

LOAD_GE

/LOAD_GE, FILE=<file_name>

This command imports an ASCII coded GE-formatted network data file

LOAD_GE qualifiers

REFFILE=<reference_file_name>

This qualifier introduces a reference base case from which to derive missing ownership and mileage information. The GE data set is potentially richer in content than IPF’s base data file, but maybe incomplete if some optional data fields such as mileage or ownerships are omitted.

VERSION=<nnn>

This qualifier defines the version number of the input data. At present, only version 21 is recognized.

RATINGS=(TX=AABC, LN=AAC)

This option correlates the various GE branch ratings with the IPF branch ratings. Four GE transformer ratings (RATEA, RATEB, RATEC, RATED) can be assigned independently to the IPF transformer ratings in the following order – Nominal, Thermal, Emergenty, and Bottleneck, Simarily, three GE line ratings (RATEA, RATEB, RATEC) can be assigned independently to the IPF line ratings in the following order – Nominal, Thermal, and Bottleneck.

The default branch IPF ratings, shown in the example above, are assigned per the table below.

This option defines the remotely controlled bus’ voltage assignments in the form of bus type and scheduled voltage. The table below describes all options

Remotely controlled bus assigned voltages

Type

Conditional bus type

Action taken

HIGH

vmax = vmax_ge vmin = vmax_ge Bb -> BT

AVERAGE

vmax = 0.5 * (vmax_ge + vmin_ge) vmin = 0.5 * (vmax_ge + vmin_ge) Bb -> BT

LOW

BQ

vmax = 0.5 * (vmax_ge + vmin_ge) vmin = 0.5 * (vmax_ge + vmin_ge)T

LOW

All other types

vmax = vmax_ge vmin = vmin_ge

RANGE

Bb

vmax = vmax_ge vmin = vmin_ge

RANGE

All other types

vmax = 0.5 * (vmax_ge + vmin_ge) vmin = 0.5 * (vmax_ge + vmin_ge)

LOAD_PTI

/LOAD_GE, FILE=<file_name>

This command imports an ASCII coded PTI-formatted network data file

LOAD_PTI qualifiers

REFFILE=<reference_file_name>

This qualifier introduces a reference base case from which to derive missing ownership and mileage information.

VERSION=<nnn>

This qualifier defines the version number of the input data. At present, only version 3 and 4 are recognized.

RATINGS=(TX=AABC, LN=AAC)

This option correlates the various PTI branch ratings with the IPF branch ratings. Four PTI transformer ratings (RATEA, RATEB, RATEC, RATED) can be assigned independently to the IPF transformer ratings in the following order – Nominal, Thermal, Emergenty, and Bottleneck, Simarily, three PTI line ratings (RATEA, RATEB, RATEC) can be assigned independently to the IPF line ratings in the following order – Nominal, Thermal, and Bottleneck.

The default branch IPF ratings, shown in the example above, are assigned per the table below.

This option defines the remotely controlled bus’ voltage assignments in the form of bus type and scheduled voltage. The table below describes all options.

Remotely controlled bus assigned voltages

Type

Conditional bus type

Action taken

HIGH

vmax = vmax_pti vmin = vmax_pti Bb -> BT

AVERAGE

vmax = 0.5 * (vmax_pti + vmin_pti) vmin = 0.5 * (vmax_pti + vmin_pti) Bb -> BT

LOW

vmax = vmin_pti vmin = vmin_pti Bb -> BT

RANGE

Bb

vmax = 0.5 * (vmax_pti + vmin_pti) vmin = 0.5 * (vmax_pti + vmin_pti)

RANGE

All other types

vmax = 0.5 * (vmax_pti + vmin_pti) vmin = 0.5 * (vmax_pti + vmin_pti)

LOSS_SENSITIVITIES

/ LOSS_SENSITIVITIES

Note

Three commands are dependent on the SOLUTION command. The commands are CHANGE_PARAMETERS, LINE_SENSITIVITIES, and LOSS_SENSITIVITIES. These three work correctly only if they immediately follow the SOLUTION command.

This feature provides valuable information concerning system losses with respect to scheduled active and reactive generation or loads, and to scheduled voltages. The command statement that invokes loss sensitivities is:

/ LOSS_SENSITIVITIES,LTC=ON,   AI_CONTROL=CON, Q_SHUNT=ADJ,
                         OFF,             OFF          FIXED

                 QGEN=ADJ,
                      FIXED

                 AREAS=<area1,area2,...>,
                 ZONES=<zone1,...>

The top line depicts default quantities. The options LTC, AI_CONTROL, and Q_SHUNT pertain to LTC transformers, area interchange control, and \(B_{shunt}\) on type BQ buses.

Three loss sensitivities are computed: \(\frac{dLoss}{dP_i}\), \(\frac{dLoss}{dQ_i}\), and \(\frac{dLoss}{dV_i}\).

These sensitivity computations are linearized about the solved case. For small changes, the sensitivities are extremely accurate. For larger changes, non-linearities redefine the problem. A rule of thumb is that the sensitivities are sufficiently accurate for a 0.5 per unit (p.u.) change in \(P_i\) or \(Q_i\), and a 0.01 p.u. change in \(V_i\).

Each sensitivity relates changes in the system losses to a hypothetical change of 1.0 p.u. in scheduled active generation \(P_i\), reactive generation \(Q_i\), or voltage \(V_i\).

Ordinarily, a decrease in system losses is anticipated when \(P_i\), \(Q_i\), or \(V_i\) increases, that is, a negative loss sensitivity.

\(\frac{dLoss}{dP_i}\)

An exception often occurs for \(\frac{dLoss}{dP_i}\). Occasionally, \(\frac{dLoss}{dP_i} > 0\), that is, increasing the generation \(P_i\) increases the losses!

Recall the constraint for Area_i:

Area export = Area generation - Area load - Area losses

(Any active bus shunt \(G\) is presumed to be accounted for in area losses.)

Within each area, the generation on the slack bus is adjustable and on all other generators is fixed. Thus, a change of 1.0 p.u. on generator “i” causes two changes in the area slack bus:

  • An immediate transfer of -1.0 p.u. to balance the change in generation.

  • An additional change to reflect the change in system losses, which are affected by the 1.0 p.u. generation transfer.

Note that the system slack bus or area interchange slack bus must pick up any deficit generation needed to supply loads and system losses. Thus, the sensitivity reflects the change in losses if 1.0 p.u. MW of generation is moved from bus “i” to the system or area slack bus. If the system or area slack bus is closer to the load center, the losses will decrease with the reallocation. Consequently, \(\frac{dLoss}{DP_i} < 0\). Otherwise, the losses will increase.

\(\frac{dLoss}{dQ_i}\)

A change in reactive generation is quite different from a change in active generation. Changes in reactive generation strongly affect the voltage profile of the system adjacent to bus “i”. Thus, a change in losses is due primarily to the change in voltage profile.

\(\frac{dLoss}{dV_i}\)

A change in scheduled voltage for types BE, BS, BQ, or BG buses directly affects the voltage profile of the system adjacent to bus “i”. Thus, the change in voltages directly affects system losses. In general, higher voltages are accompanied with lower branch currents and hence, lower line losses. Exceptions may occur in cables where large amounts of inductive shunt are necessary to compensate for the capacitance in cable.

MERGE_OLD_BASE and MERGE_NEW_BASE

/ MERGE_OLD_BASE and / MERGE_NEW_BASE

These subprocesses extract a subsystem from an old base file and merge it with another subsystem to generate a new system. The subsystems are defined by various qualifiers following the MERGE command.:

/ MERGE_OLD_BASE,SUBSYSTEM_ID= <subsystem_label>,
  OLDBASE_FILE = <file_spec>

and:

/ MERGE_NEW_BASE,SUBSYSTEM_ID = <subsystem_label>,
        BRANCH_DATA_FILE = <file_spec>, DATE = <myy>,
        R = <n>, BUS_DATA_FILE = <file_spec>

where:

  • file_spec is the file specification for the pertinent file. If file_spec has the value * for either the BUS_DATA_FILE or BRANCH_DATA_FILE, the data is presumed to be the Powerflow command file.

  • subsystem_label is the identifying label for the merged subsystem.

  • DATE is the branch extraction date. Branches selected will have their energization date on or before DATE and a de-energization date after DATE.

  • The month field (as a digit) also defines winter or summer extended ratings:

    ``m = 1`` selects winter peak ratings.
    ``m = 8`` selects summer peak ratings.
    

    See Table 4-11 for the complete listing.

  • For other values, it is necessary to use an additional parameter R defined in the next section.

  • R specifies extended ratings from the branch data file. See Table 4-15 and Table 4-16. Also, see Figure 4-11 and Figure 4-12. Two modes of operation are available:

** Merge a subsystem from one OLD_BASE file with another subsystem from a different old base file. ** Merge a subsystem from an OLD_BASE file with another subsystem which is newly created from bus and branch records.

The two merge control cards distinguish the source of the subsystem data. / MERGE_OLD_BASE identifies an OLD_BASE file, and / MERGE_NEW_BASE identifies the bus and branch records files from which a new subsystem will be constructed.

The R code indicates which extended ratings from the branch data file should be used. For example, the R=2 code in the following card indicates that extra heavy ratings should be used.

/MERGE_NEW_BASE,SUBSYSID-BR_BUS,BRAN=BDCY89.DAT,DATE=196,R=2,BUSD=J96EH.BUS

Powerflow uses appropriate ratings from the branch data for the peak winter (R=1), peak summer (R=8), extra heavy (R=2), moderate cold (R=3), and spring (R=4) choices.

If the thermal or bottleneck rating on a branch is blank or zero in the columns for extra heavy or moderate cold ratings, the peak winter rating is used (if available). Similarly, if the thermal, bottleneck, or emergency rating on a branch is blank or zero in the columns for spring ratings, the peak summer rating is used (if available).

The chosen ratings are moved to columns 81 through 92 on the branch record in Powerflow.

_images/Extended_Ratings_Fields_for_L_and_E_Records.png

Extended Ratings Fields for L and E Records

L and E Record Extended Fields Column Descriptions

Column

Rating (“R” Selection)

Field Description

81-84

1

Winter Thermal (WT)

85-88

1

Winter Bottleneck (WB)

89-92

(not used)

93-96

8

Summer Thermal (ST)

97-100

8

Summer Bottleneck (SB)

101-104

(not used)

105-108

2

Extra Heavy Thermal (EHT)

109-112

2

Extra Heavy Bottleneck (EHB)

113-116

3

Moderate Cold Thermal (MCT)

117-120

3

Moderate Cold Bottleneck (MCB)

121-124

4

Spring Thermal (SPT)

125-128

4

Spring Bottleneck (SPB)

_images/Extended_Ratings_Fields_for_T_and_TP_Records.png

Extended Ratings Fields for T and TP Records

T and TP Record Extended Fields Column Descriptions

Column

Rating (“R” Selection)

Field Description

81-84

1

Winter Thermal (WT)

85-88

1, 2, 3

Winter Emergency (WE)

89-92

1

Winter Bottleneck (WB)

93-96

8

Summer Thermal (ST)

97-100

8

Summer Emergency (SE)

101-104

8

Summer Bottleneck (SB)

105-108

2

Extra Heavy Thermal (EHT)

109-112

2

Extra Heavy Bottleneck (EHB)

113-116

3

Moderate Cold Thermal (MCT)

117-120

3

Moderate Cold Bottleneck (MCB)

121-124

4

Spring Thermal (SPT)

125-128

4

Spring Emergency (SPE)

129-132

4

Spring Bottleneck (SPB)

MERGE qualifiers

>EXCLUDE_BRANCHES

Use this command to exclude from the subsystem branches following this statement. Each branch is identified with a separate L, E, or T formatted record.

>INCLUDE_BUS

Use this command to identify additional buses which are to be included in the selected subsystem. Each bus is identified with a separate B formatted record.

>INTERFACE_BRANCHES

Use this command to list individual interface branches. Each such interface branch is identified with a separate L, E, or T formatted record.:

>INTERFACE_PREF=COMP
                REJECT
                ACCEPT

This command assigns preference weights on competing interface branches listed following the statement. Two subsystems to be merged are usually topologically complementary and have common branches. These branches are called interface branches. During merging, two sets of competing interface branches vie for selection in the final system. In the absence of any information supplied, the default decision is to select the interface branch with the most detail.

The command above allows the user to assign preferences for the interface branches for each system. Each such interface branch is identified on a standard L, T, or E formatted record. ACCEPT and REJECT must complement each other, or both sets of interface branches will be accepted or rejected.

COMP forces comparison of common interface branches from the two subsystems. Acceptance from one subsystem and rejection from the other is determined on the basis of matching bus and branch ownerships. The assumption is that the bus owner always has better branch data. For BPA users, WSCC data is accepted when branch ownerships cannot be determined from data.:

>MERGE_RPT = SORTED
             UNSORTED

This command requests the specific level of merge report. This feature is not yet implemented.

>RENAME_BUS

This command provides a convenient way to resolve potential conflicts of identically named but topologically distinct buses. This command introduces B-formatted records with the old name in columns 7-18 and the new name in columns 20-31.

>SAVE_AREAS

Use this command to save areas of the subsystem listed following this statement. Each area is identified with a separate A-formatted area record.

>SAVE_BASES <list>

This command saves buses whose base kV’s match the list. Elements of the list are separated by commas (,) and terminated by a period (.).

>SAVE_BUSES

This command saves listed buses of the subsystem. Saved buses are named on separate B-formatted bus records following.

>SAVE_ZONES <list>

This command saves listed zones of the subsystem. Elements of the list are separated with commas. Example: > SAVE_ZONES NA, NB

>USE_AIC

This command specifies that A records should be generated from the old base file defined by the OLD_BASE statement.

MVA_BASE

/ MVA_BASE =    100
              <number>

This command changes the base MVA from the default value of 100 MVA to an assigned value.

NETWORK_DATA

/ NETWORK_DATA ,FILE= *,            RXCHECK = ON
                      <filespec>,             OFF

This introduces network bus and branch data into the program. No old base case is in residence. RXCHECK = ON enables \(R/X\) ratios checking. If the FILE parameter value is asterisk (*), then bus and branch data is assumed to immediately follow this command.

NEW_BASE

/ NEW_BASE , FILE = <filespec>

This command defines the name of the new base file to save the network solved by the case run. It may be the same as the old base file, if you want to overwrite it.

OI_LIST

This command is used to list ownership interchange.:

/ OI_LIST = NONE
            TIELINE
            MATRIX
            FULL

Owners are listed using the expanded owner identifications hard-coded in the program. See below for the complete list of codes and expanded names.

Ownership Code

Ownership Name

AAC

ANACONDA ALUMINUM COMPANY

AEC

ATOMIC ENERGY COMMISSION

AEP

ARIZONA ELECTRIC POWER COOPERATION

ALA

ALABAMA POWER COMPANY

ALC

ALUMINUM COMPANY OF AMERICA

APS

ARIZONA PUBLIC SERVICE COMPANY

ARL

ARKANSAS POWER AND LIGHT COMPANY

ARR

ARROWHEAD ELECTRIC COOPERATIVE, INC.

AVC

AMARGOSA VALLEY COOPERATIVE INC.

BBE

BIG BEND ELECT. COOP

BCH

BRITISH COLUMBIA HYDRO AND POWER AUTHORITY

BEC

BASIN ELECTRIC POWER COOP.

BEP

BASIN ELECTRIC COOPERATIVE

BHP

BLACK HILLS POWER AND LIGHT COMPANY

BPA

BONNEVILLE POWER ADMINISTRATION

BPD

BENTON CO. PUD

BRE

BENTON REA

CAL

CALIFORNIA DEPARTMENT OF WATER RESOURCES

CCC

COOS CURRY ELECTRIC COOP

CCP

COWLITZ COUNTY PUBLIC UTILITY DISTRICT NO.1

CCS

CITY OF COLORADO SPRINGS

CE1

DEP. OF ARMY CORPS OF ENGINEER (REGION 1 AREA)

CE2

DEP. OF ARMY CORPS OF ENGINEER (REGION 2 AREA)

CE3

DEP. OF ARMY CORPS OF ENGINEER (REGION 3 AREA)

CE4

DEP. OF ARMY CORPS OF ENGINEER (REGION 4 AREA)

CE5

DEP. OF ARMY CORPS OF ENGINEER (REGION 5 AREA)

CE6

DEP. OF ARMY CORPS OF ENGINEER (REGION 6 AREA)

CE7

DEP. OF ARMY CORPS OF ENGINEER (REGION 7 AREA)

CEC

COMMONWEALTH EDISON COMPANY (ILLINOIS)

CED

COMMONWEALTH EDISON COMPANY OF INDIANA, INC.

CEN

CENTRAL POWER ELECTRIC COOP., INC. (N. DAKOTA)

CIP

CENTRAL IOWA POWER COOPERATIVE

CIS

CENTRAL ILLINOIS PUBLIC SERVICE COMPANY

CLA

CLALLAM PUD

CLK

CLARK COUNTY PUBLIC UTILITY DISTRICT NO. 1

CLP

CENTRAL LINCOLN PUD

CLT

CLATSKANIE PUD

CMS

CHICAGO, MILWAUKEE, ST.PAUL AND PACIFIC R.R. CO.

CNP

CENTRAL NEBRASKA PUBLIC POWER AND IRRIGATION DIST.

COB

CORN BELT POWER COOPERATIVE, INC.

COE

DEP. OF ARMY CORPS OF ENGINEERS

COR

CITY OF RICHLAND

CPA

COOPERATIVE POWER ADMINISTRATION

CPD

CHELAN COUNTY PUBLIC UTILITY DISTRICT NO. 1

CPI

CONSUMERS POWER INC.

CPL

CALGARY POWER LIMITED

CPN

C P NATIONAL

CPP

CONSUMERS PUBLIC POWER DISTRICT (NEBRASKA)

CPS

COMMUNITY PUBLIC SERVICE CO.

CPU

CALIFORNIA PACIFIC UTILITIES COMPANY

CRP

COLUMBIA RIVER PUD

CU

COLORADO-UTE ELECTRIC ASSOCIATION

DPC

DAIRYLAND POWER COOPERATIVE (WISC., MINN.)

DPD

DOUGLAS COUNTY PUBLIC UTILITIES DISTRICT

EEQ

EASTERN EQUIVALENT

EIL

EASTERN IOWA LIGHT AND POWER COOPERATIVE

ELE

EL PASO ELECTRIC COMPANY

ELP

EL PASO ELECTRIC COMPANY

EMP

EMERALD PUD

EPE

EL PASO ELECTRIC

ERP

EAST RIVER ELECTRIC POWER COOP.,INC.(S. DAKOTA)

EWE

EUGENE WATER AND ELECTRIC BOARD (OREGON)

FRC

FALL RIVER ELEC. COOP

FRK

FRANKLIN CO. PUD

GH

GRAYS HARBOR COUNTY PUBLIC UTILTIY DISTRICT

GPD

GRANT COUNTY PUD NO.2 (WASHINGTON)

GSU

GULF STATE UTILITIES COMPANY (TEXAS, LOUISIANA)

HAR

HARNEY ELECTRIC COOP

HEA

HIGHLINE ELECTRIC ASSOCIATION

HPL

HOUSTON POWER AND LIGHT COMPANY

IDP

IDAHO POWER COMPANY

IEL

IOWA ELECTRIC LIGHT AND POWER

IGE

IOWA ILLINOIS GAS AND ELECTRIC COMPANY

IID

IMPERIAL IRRIGATION DISTRICT (CALIFORNIA)

IIG

IOWA-ILLINOIS GAS & ELECTRIC CO.

ILL

ILLINOIS POWER COMPANY

ILM

ILLINOIS AND EASTERN MISSOURI

IME

INDIANA AND MICHIGAN ELECTRIC COMPANY

INL

INLAND POWER AND LIGHT

INP

INLAND POWER AND LIGHT COMPANY

IPC

IDAHO POWER COMPANY

IPL

IOWA POWER AND LIGHT COMPANY

IPS

IOWA PUBLIC SERVICE COMPANY

IPU

IOWA SOUTHERN UTILITIES CO.

ISP

INTERSTATE POWER COMPANY

ISU

IOWA SOUTHERN UTILITIES COMPANY

KCP

KANSAS CITY POWER AND LIGHT COMPANY

KGE

KANSAS GAS AND ELECTRIC COMPANY

KPL

KANSAS POWER AND LIGHT COMPANY

LA

CITY OF LOS ANGELES DEPARTMENT OF WATER AND POWER

LCR

LOWER COLORADO REGION WESTERN AREA POWER ADMIN.

LEC

LANE CO. ELEC.COOP.

LES

LINCOLN ELECTRIC SYSTEM

LEW

LEWIS CO. PUD.

LPL

LOUISIANA POWER AND LIGHT COMPANY

LSD

LAKE SUPERIOR DISTRICT POWER COMPANY

LVP

LOWER VALLEY POWER AND LIGHT

MAI

MAIN-MID-AMERICA INTERPOOL NETWORK

MCM

MCMINNVILE, CITY OF

MDU

MONTANA-DAKOTA UTILITIES COMPANY

MFR

MILTON-FREEWATER

MH

MANITOVA HYDRO ELECTRIC BOARD

MIN

MINNKOTA POWER COOPERATIVE, INC.

MLC

MISSOURI POWER AND LIGHT COMPANY

MLE

MOON LAKE ELECTRIC ASSOCIATION, INC.

MN1

MASON COUNTY PUD #1

MN3

MASON COUNTY PUD #3

MPC

MONTANA POWER COMPANY

MPL

MINNESOTA POWER AND LIGHT COMPANY

MPO

MISSISSIPPI POWER AND LIGHT COMPANY

MPR

MID PACIFIC REGION - USBR

MPS

MISSOURI PUBLIC SERVICE COMPANY

MPW

MUSCATINE POWER AND WATER

MWD

METROPOLITAN WATER DISTRICT OF SOUTHERN CALIFORNIA

NEP

N.W. ELECTRIC POWER COOP., INC. (MISSOURI,ARK.)

NGT

NEBRASKA ELECTRIC GENERATING AND TRANSMISSION COOP

NIP

NORTHWEST IOWA POWER COOPERATIVE

NLI

NORTHERN LIGHTS,INC.

NPC

NEVADA POWER COMPANY

NPP

NEBRASKA PUBLIC POWER SYSTEM

NPR

NORTH PACIFIC REGION - USBR

NSC

NORTHERN STATES POWER COMPANY, (WISCONSIN)

NSP

NORTHERN STATES POWER COMPANY, (MINN.,N.D.,S.D.)

NWA

NORTHERN WASCO PUD

NWP

NORTHWESTERN PUBLIC SERVICE COMPANY (S. DAKOTA)

OGE

OKLAHOMA GAS AND ELECTRIC COMPANY

OKP

OKANOGAN CO. PUD

OPD

OMAHA PUBLIC POWER DISTRICT

OPP

OMAHA PUBLIC POWER DISTRICT

OTC

OREGON TRAIL COOP

OTP

OTTER TAIL POWER COMPANY

OWI

OROVILLE-WYANDOTTE IRRIGATION DISTRICT, (CALIF.)

PAN

PORT ANGELES

PDO

PEND OREILLE PUD

PEG

PLAINS ELECTRIC G AND T COOP(NEW MEXICO)

PEN

PENINSULA LT. CO.

PG

PORTLAND GENERAL ELECTRIC COMPANY

PGE

PACIFIC GAS AND ELECTRIC COMPANY

PGT

PLAINS ELECTRIC G AND T COOP., (NEW MEXICO)

PNM

PUBLIC SERVICE COMPANY OF NEW MEXICO

PPL

PACIFIC POWER AND LIGHT COMPANY

PPW

PACIFIC POWER AND LIGHT - WYOMING

PRP

PLATTE RIVER POWER AUTHORITY

PSC

PUBLIC SERVICE COMPANY OF COLORADO

PSI

PUBLIC SERVICE COMPANY OF INDIANA

PSO

PUBLIC SERVICE COMPANY OF OKLAHOMA

PSP

PUGET SOUND POWER AND LIGHT COMPANY

R1

WESTERN AREA POWER ADMIN. REGION 1

R2

WESTERN AREA POWER ADMIN. SACRAMENTO AREA

R3

WESTERN AREA POWER ADMIN. REGION 3

R4

WESTERN AREA POWER ADMIN. SALT LAKE CITY AREA

R5

WESTERN AREA POWER ADMIN. REGION 5

R6

WESTERN AREA POWER ADMIN. BILLINGS AREA

R7

WESTERN AREA POWER ADMIN. DENVER AREA

RCP

RURAL COOPERATIVE POWER ASSOCIATION, (MINNESOTA)

RFT

RAFT RIVER RURAL ELECTRIC COOP

SC

SOUTHERN CALIFORNIA EDISON COMPANY

SCE

SOUTHERN CALIFORNIA EDISON COMPANY

SCL

SEATTLE CITY LIGHT COMPANY

SCP

SOUTHEAST COLORADO POWER ASSOCIATION

SDG

SAN DIEGO GAS AND ELECTRIC COMPANY

SJL

SAINT JOSEPH LIGHT AND POWER COMPANY

SMD

SACRAMENTO MUNICIPAL UTILITIES DISTRICT

SPA

SOUTHWESTERN POWER ADMIN.

SPC

SASKATCHAWAN POWER COMPANY

SPD

SNOHOMISH COUNTY PUBLIC UTILITIES DISTRICT

SPP

SIERRA PACIFIC POWER COMPANY

SPS

SOUTHWESTERN PUBLIC SERVICE COMPANY

SRP

SALT RIVER POWER DISTRICT

SUB

SPRINGFIELD UTILITY BOARD

SWP

SOUTHWESTERN POWER ADMINISTRATION

SWR

SOUTHWEST REGION - USBR

TCE

TRI-COUNTY ELECTRIC ASSOCIATION, INC. (WYOMING)

TCL

TACOMA CITY LIGHT COMPANY

TEP

TUSCON ELECTRIC POWER COMPANY

TES

TEXAS ELECTRIC SERVICE COMPANY

TGE

TUCSON GAS AND ELECTRIC COMPANY

TIL

TILLAMOOK PUD

TPL

TEXAS POWER AND LIGHT COMPANY

TRI

TRI-STATE GENERATION AND TRANSMISSION ASSOC.

TSG

TRI-STATE GENERATION AND TRANSMISSION ASSOC.

TVA

TENNESEE VALLEY AUTHORITY

UEC

UNION ELECTRIC COMPANY (IOWA,MISSOURI,ILLLINOIS)

UPA

UNITED POWER ASSOCIATION, INC. (NORTH DAAKOTA)

UPL

UTAH POWER AND LIGHT COMPANY

USN

U.S.NAVY WAP WESTERN AREA POWER ADMINISTRATION-BILLINGS AREA

WEP

WISCONSIN ELECTRIC POWER COMPANY

WIS

WISCONSIN PUBLIC SERVICE CORP.

WKP

WEST KOOTENAY POWER AND LIGHT COMPANY, LTD.

WMP

WISCONSIN MICHIGAN POWER COMPANY

WPD

WHATCOM COUNTY PUD

WPS

WASHINGTON PUBLIC POWER SUPPLY SYSTEM

WRP

WISCONSIN RIVER POWER COMPANY

WRE

WELLS RURAL ELECTRIC CO.

WST

WESTERN POWER AND GAS COMPANY (COLORADO)

WWP

WASHINGTON WATER POWER COMPANY

YWE

YUMA WRAY ELEC.ASSN.,INC.

OLD_BASE

/ OLD_BASE, FILE = <filespec>, REBUILD = OFF
                                         ON

This command specifies that a previously solved Powerflow case is to be loaded from the specified file and used as the base system for the current request.

<filespec> The file specification of the solved network to be re-solved.

The REBUILD switch causes the program to rebuild all of the tables and starts the solution with a “flat start.”

OUTAGE_SIMULATION

/ OUTAGE_SIMULATION

This command simulates the effect of line outages, load dropping, generator outages, and generator rescheduling. It invokes a process which modifies the base case data in residence. For this reason, this process should not be used with any other process.:

/ OUTAGE_SIM
> OLDBASE = filespec
 .......
 .......
 .......   Optional Outage Simulation Required Qualifiers
 .......
 .......

where:

filespec File specification for the base file to be loaded to begin the process.

OUTAGE_SIMULATION Qualifiers

>ANALYSIS = OFF, MINLOADING = 100
            ON                <num>

This command specifies the threshold loading of a line to be included as contingency-caused overloads. This threshold may be raised on individual branches to screen out base case overloads.:

>COMMON_MODE, FILE = *
>COMMON_MODE_ONLY, FILE =*

These two commands introduce a script which defines one or more “common-mode” outages. The second form restricts the outage simulation study to include only common mode outages. In this case, it is still necessary to introduce an associated >OUTAGE record, but it is used only to define the zones and bases of interest.

The simulation and analysis of any common-mode outages complements in a seamless fashion that for the ordinary single-contingency branch outages. The script associated with the common mode study can be either in a separate file (in which case a file name would be specified) or in the input stream (in which case a file name * is specified).

Each common-mode outage consists of two parts: A common-mode identification record (>MODE) and the set of WSCC-formatted bus an/or branch changes which are associated with that common mode outage. It is useful and recommended to annotate this script with comment text. An example will illustrate all the points mentioned.:

> MODE B/D DRISCOLT 230
B D   DRISCOLT 230
. Above common mode outage takes out the following lines:
.       DRISCOLT 230 ALLSTON  230
.       DRISCOLT 230 CLATSOP  230
.       DRISCOLT 230 DRISCOLL 230
.

Here, the name of the introduced common-mode outage is “B/D DRISCOLT 230”. The name is arbitrary; it should be sufficiently distinct to contrast it with entities associated with ordinary single contingency branch outages. The name is 40-characters long, is defined in columns (7:47) on the > MODE records, and is truncated to 31 columns in certain Outage Analysis listings where it must compete with the single contingency branch outages. A maximum of 50 >MODE records are permitted.

Each >MODE record is accompanied with an set of arbitrary change records which specifically define all of the changes in the system that are effected by the common mode. If no change records are submitted, the >MODE record is meaningless, since it would not perturb the system in any manner.

The common mode changes permitted are restricted to the following:

  • Bus deletion (D) and modification (M).

  • Continuation bus deletion (D) and modification (M).

  • Branch deletion (D).

The change methodology is identical with that used elsewhere. A bus deletion, for example, automatically deletes all components associated with it. Implementation, however, expedites the change, but in a manner designed to maximize the computational efficiency. The same bus deletion, to repeat the example, is effected by temporarily changing the impedance of all emanating branches to 10000.0 p.u. X, and preserving a small residual admittance for the bus.

With judicious selection of change records, it is possible to simulate complex scenarios such as the loss of switching CAPs followed with the loss of a transformer. If the common mode changes isolate even a single bus in the system, the outage is skipped and the isolation is noted within the outage analysis reports.

Although every attempt was made to simulate common mode outages as efficiently as possible, the highly efficient line compensation schemes that were utilized in the single contingency branch outages could not be used here. Each common mode outage requires refactorization of the associated network matrices.

>DEBUG = OFF
         ON

This turns on debug dumps.

Note

Caution! These dumps can be enormous.

>DEFAULT_RATING

This command indicates that the following text is line default data. Branches in the specified areas of interest are examined for zero rating (which is an omission of data). If the base kVs of the terminals match the kV in the following default ratings, new ratings are assigned to their branches. They then become candidates for branch overload checking following an outage.

See the table below for the format of default ratings.

This command specifies that all line resistance in the eliminated system is replaced with equivalent current injection. The equivalent network, as modified by this option, is easier to solve.:

>EXPAND_NET = 2
              <nn>

This command specifies that the border of the selected equivalent network should emanate outwards an additional number of buses. The expansion selected should be less than 100.:

>GEN_OUTAGE = NONE
              <nn>

This command specifies the maximum number of generator outages for rescheduling.

>INCLUDE_CON = <filespec>

Use this command to divert the input stream to an auxiliary file that contains / OUTAGE_SIMULATION text. This auxiliary file cannot contain a recursive / INCLUDE_CON statement.:

>LOW_VOLT_SCREEN = 80
                   <num>

This command specifies a contraction for overload values to compensate for effects of voltage changes. It lowers the threshold which tests for overloaded lines.:

>MIN_EQUIV_Y = .02
               <num>

This command specifies minimum admittance of equivalent branches.:

>NO_SOLUTION, ANGLE = 3.0, DELTA_V = .5
                      <num>          <num>

This command specifies conditions for no solution (or no convergence). ANGLE is the largest excursion angle (from one iteration to another) in radians relative to the slack bus.

>OLD_BASE = <filespec>

<filespec> is file specification of the solved network to be re-solved.

Because / OUTAGE_SIMULATION is a stand-alone process, it must begin by loading an old base file which is introduced using this command.:

>OUTAGE, ZONES = *      BASES= *
                 <list>        <list>

This command specifies the ZONES and voltage levels where outages should be taken. Elements of the list should be separated by commas.:

>OUTPUT_SORT , OVER_OUT
               OUT_OVER, OWNER
               BOTH

This command specifies the sort order for output listing in terms of overloads and associated outages. The OWNER option requests ownership-bus sort order.:

>OVERLOAD, ZONES = *      BASES= *
                   <list>        <list>

To specify zones and voltage levels where overload should be monitored, use this command. Entities in list should be separated by commas.:

>PHASE_SHIFT = FIXED_POWER
               FIXED_ANGLE

This command specifies phase-shifter representation constant branch power or constant phase shift angle.:

>REACTIVE_SOL = ON
                OFF

This command invokes the reactive solution feature. Normally, only the P-constraints are held.:

>REALLOCATE = NONE
              LOAD
              LOADGEN

This command specifies that load may be shed, generation changed, or both, in order to relieve overload.:

>REDUCTION = NONE,REI=OFF
             SIMPLE   ON
             OPTIMAL

This command requests the reduction feature and specifies the type of reduction.:

>REDUCTION_DEBUG = NONE
                   MINOR
                   MAJOR

This is used to request the debug feature.:

>RELAX_BR_RATE = ON,PERCENT=5.0
                 OFF        <NUM>

This command requests that the branch ratings be relaxed by a certain percentage.:

>SET_RATINGS, NOMINAL, FILE = <filespec>
              SUMMER
              WINTER

This command specifies the special ratings of branches that are used for overload determinations. The number of branches whose ratings are specified in FILE is given by a records parameter. Specification records follow this qualifier if the file parameter is omitted. Rating records are described in the table below.

Fields for Rating Records

Column Position

Content

7-15

bus name

16-19

base voltage

21-27

bus name

28-31

base voltage

32

parallel identification

34-37

nominal amps rating

39-42

summer amps rating

44-47

winter amps rating

>SOL_ITER, FIXED = 3
                  <nn>

This command sets the solution iteration limit per outage. Divergence is assumed when this limit is exceeded.

>TOLERANCE = .005
             <num>

This specifies the convergence tolerance in per unit power. Convergence is assumed when mismatch is less than this value. Larger values (0.05) yield fast, approximate solutions; smaller values yield slower, more exact solutions.

Debugging techniques

The following method has proved to be a useful tool for debugging the Outage Simulation Program (OSP) interactively. In invoking this option, three events occur.

  1. After the equivalent reduced system is established but before the individual branch outages are taken, the user interactively selects from the full set of branch outages one or more outages. The unselected outages will be ignored.

  2. Debugging switches are turned on.

  3. Salient process and status information about each outage is displayed on the screen.

This is most useful to confine the study to a single questionable outage which them will to be compared with the results of an IPF change case depicting the same outage. To invoke this, enter the two following DCL commands in a terminal window.:

$ DEBUG_OUTAGE_SIMULATION_STUDY :== ON
$ RUN IPF_EXE:FSTOUT.EXE_V321

The second command executes the OSP interactively. After responding to the prompted Power Flow Control file and waiting a few minutes, OSP’s special debugging in invoked.

Enter outage range (n:m), 0=Save, -1=Cancel)

You must select the outage by trial and error using a binary search. Enter a candidate outage branch index (say 127). The dialog continues (using an actual case for an example). 127 outage BELNGM P 115.0 CARILINA 115.0 1 : Select? (Y or N) Selecting “Y” will add this to the outage set’ “N” will ignore it. If the displayed outrage is alphabetically lower than the desired outage, respond with “N” and enter a higher outage number at the next prompt. If it is higher do the opposite. The dialog loops for additional selections or searches.

Enter outage range (n:m), 0=Save, -1=Cancel)

Eventually, when the desired ouages(s) is (are) selected, the process is exited with either option (“0”, saving the selection and continuing or “-1”, ignoring the selection and continuing).

OVERLOAD_RPT

/ OVERLOAD_RPT, TX =        90.  , LINE = 90.
                           <num>         <num>

This command sets the percentage of line and transformer ratings above which line and transformer loadings are listed in the analysis report.

P_ANALYSIS_RPT

/ P_ANALYSIS_RPT , LEVEL =     2 , *
                               1   ZONES=<list>
                               3   OWNERS=<list>
                               4

Use this command to specify the printed analysis report.

When <list> is blank, asterisk or null, ALL is assumed unless limited by a preceding statement.

The level number determines the analysis summaries to be displayed.

For LEVEL=1, the following summaries are included:

  • User-defined analysis (optional).

  • Buses with unscheduled reactive.

For LEVEL=2, the following are displayed with summaries for LEVEL=1:

  • Total system generations and loads by owner.

  • System generations, loads, losses and shunts by zones.

  • Undervoltage-overvoltage buses.

  • Transmission lines loaded above XX.X% of ratings.

  • Transformers loaded above XX.X% of ratings.

  • Transformer excited above 5% over tap.

  • Transmission system losses.

  • BPA industrial loads.

  • dc system.

  • Shunt reactive summary.

  • Summary of LTC transformers.

  • Summary of phase-shifters.

  • Summary of %Var-controlled buses.

  • Summary of type BX buses.

  • Summary of adjustable Var compensation.

  • Transmission lines containing series compensation.

For LEVEL=3, the following is displayed in addition to the LEVEL=2 output:

  • Bus quantities.

For LEVEL=4, the following are displayed in addition to the LEVEL=3 display:

  • Spinning reserves.

  • Transmission line efficiency analysis. Lines loaded above XX.X% of nominal ratings.

  • Transformer efficiency analysis. Total losses above X.XX% of nominal ratings.

  • Transformer efficiency analysis. Core losses above X.XX% of nominal ratings.

Example

/ F_ANALYSIS_RPT, LEVEL=4, OWNERS= BPA,PGE,PPL,WPS
/ P_ANALYSIS_RPT, LEVEL=1, ZONES = NA, NB, NC
/ F_ANALYSIS_RPT, LEVEL=4, *
/ P_ANALYSIS_RPT, LEVEL=1, ZONES = *

P_INPUT_LIST

/ P_INPUT_LIST , NONE
                 FULL,  ERRORS = NO_LIST
                                 LIST
                 ZONES = <list>
                 ZONES = ALL, FULL, or NONE

This command lists input data on PAPER. Output can be restricted to individual zones specified in <list>, which are separated with commas. Note that FULL or NONE may be specified in two forms.

The ERRORS options can be set to NO_LIST to suppress the input listing if any Fatal (F) errors are encountered.

Example:

PWRFLO case: 9BUS proj: TEST-CASE * * * INPUT LISTING * * * 9 BUSSES 8 EQUIVALENT BR PAGE 3 14-JUN-94

 BASIC NINE-BUS CASE
 FOR EXAMPLE REPORTS

BS GEN1 16.5 2 .0PL .0QL .0PS .0QS 240.0PM 306.2PG 150.0QH -100.0QL 1.040VH .0VL
 T 1 GEN1 HI 230.0 0 0 MVA 0 C .00000 R .05760 X .00000 G .00000 B 16.50 230.00 0 T 0 E 0 B 0IN
B GEN1 HI 230.0 2 .0PL .0QL .0PS .0QS .0PM .0PG .0QH .0QL .000VH .000VL
 T 2 GEN1 16.5 0 0 MVA 0 C .00000 R .05760 X .00000 G .00000 B 230.00 16.50 0 T 0 E 0 B 0IN
 L 2 STA A 230.0 0 0 AMP 0 C .01000 R .08500 X .00000 G .08800 B .0 MI 0 T 0 B 0IN
 L 1 STA B 230.0 0 0 AMP 0 C .01700 R .09200 X .00000 G .07900 B .0 MI 0 T 0 B 0IN
BQ GEN2 18.0 1 .0PL .0QL .0PS .0QS 180.0PM 163.0PG 120.0QH -80.0QL 1.025VH .000VL
 T 1 GEN2 HI 230.0 0 0 MVA 0 C .00000 R .06250 X .00000 G .00000 B 18.00 230.00 0 T 0 E 0 B 0IN
B GEN2 HI 230.0 1 230.0PL .0QL .0PS .0QS .0PM .0PG .0QH .0QL .000VH .000VL
 T 2 GEN2 18.0 0 0 MVA 0 C .00000 R .06250 X .00000 G .00000 B 230.00 18.00 0 T 0 E 0 B 0IN
 L 1 STA A 230.0 0 0 AMP 0 C .03200 R .16100 X .00000 G .15300 B .0 MI 0 T 0 B 0IN
BQ GEN3 13.8 2 .0PL .0QL .0PS .0QS 130.0PM 85.0PG 80.0QH -60.0QL 1.025VH .000VL
 T 1 GEN3 HI 230.0 0 0 MVA 0 C .00000 R .05860 X .00000 G .00000 B 13.80 230.00 0 T 0 E 0 B 0IN
B GEN3 HI 230.0 2 .0PL .0QL .0PS .0QS .0PM .0PG .0QH .0QL .000VH .000VL
 T 2 GEN3 13.8 0 0 MVA 0 C .00000 R .05860 X .00000 G .00000 B 230.00 13.80 0 T 0 E 0 B 0IN
 L 1 STA B 230.0 0 0 AMP 0 C .03900 R .17000 X .00000 G .17900 B .0 MI 0 T 0 B 0IN
 L 1 STA C 230.0 0 0 AMP 0 C .01190 R .10080 X .00000 G .10450 B .0 MI 0 T 0 B 0IN
B STA A 230.0 1 125.0PL 50.0QL .0PS .0QS .0PM .0PG .0QH .0QL .000VH .000VL
 L 1 GEN1 HI 230.0 0 0 AMP 0 C .01000 R .08500 X .00000 G .08800 B .0 MI 0 T 0 B 0IN
 L 2 GEN2 HI 230.0 0 0 AMP 0 C .03200 R .16100 X .00000 G .15300 B .0 MI 0 T 0 B 0IN
B STA B 230.0 2 90.0PL 30.0QL .0PS .0QS .0PM .0PG .0QH .0QL .000VH .000VL
 L 2 GEN1 HI 230.0 0 0 AMP 0 C .01700 R .09200 X .00000 G .07900 B .0 MI 0 T 0 B 0IN
 L 2 GEN3 HI 230.0 0 0 AMP 0 C .03900 R .17000 X .00000 G .17900 B .0 MI 0 T 0 B 0IN
B STA C 230.0 2 100.0PL 35.0QL .0PS .0QS .0PM .0PG .0QH .0QL .000VH .000VL
 L 2 GEN3 HI 230.0 0 0 AMP 0 C .01190 R .10080 X .00000 G .10450 B .0 MI 0 T 0 B 0IN

PWRFLO case: 9BUS proj: TEST-CASE * * * INPUT LISTING * * * 9 BUSSES 8 EQUIVALENT BR PAGE 3 14-JUN-94

P_OUTPUT_LIST

/ P_OUTPUT_LIST, NONE,  FAILED_SOL = FULL_LIST
                 FULL                PARTIAL_LIST
                 ZONES = <list>      NO_LIST
                 ZONES = ALL, FULL, or NONE

This command lists output on PAPER. Output can be restricted to individual zones specified in <list>, which are separated with commas. Note that FULL or NONE may be specified in two forms.

The FAILED_SOL option is set to override the output listing if a failed solution occurs. It defaults to a full listing. A PARTIAL_LIST observes zone lists.

Example:

PWRFLO case: 9BUS proj: TEST-CASE * * * * DETAILED OUTPUT LISTING * * * * PAGE 8 14-JUN-94

BASIC NINE-BUS CASE
FOR EXAMPLE REPORTS


A COMPLETE OUTPUT LISTING OF ALL BUSSES WILL BE GIVEN

GEN1    16.5   17.2KV/ .0 ZONE  2 306.2PGE  72.5QCOND  .0PLOAD    .0QLOAD      1.040PU KV      BUS TYPE S       GEN1 HI   230.0                     2 306.2PIN   72.5QIN      0.0PLOSS    52.7QLOSS          16.5/230.0                                               306.2PNET  72.5QNET                                         0.0 SLACK ADJ

REBUILD

/ REBUILD = OFF
            ON

This command requests that all internal data tables be rebuilt using the current specified OLDBASE file. This has the same effect in a case as the REBUILD parameter on the / OLD_BASE statement.

REDUCTION

/ REDUCTION

This command reduces the network in residence to a desired size and solves the reduced network. It can be saved or processed further as an ordinary base case. For more detail on the methods used, see Network Reduction.:

/ REDUCTION
.......
.......
....... Optional Reduction Qualifiers
.......
.......

Reduction Qualifiers

>COHERENT_CLUSTERS, <name> <base kV>

This identifies row-coherent generators (or load) of an REI subsystem. The name must be unique, containing 1-7 characters without blanks and be left-justified. The REI components, which will have their generation and/or load transferred to the coherent generator, are identified with ordinary WSCC-formatted bus (Type B) records which follow.

The named constituent buses which comprise each coherent cluster may be either retained or eliminated buses. In either case, the constituent buses will be eliminated.

Special codes on each bus permit individual dispositions of generator and load quantities. Generation and/or load may be converted to constant current, constant admittance, or converted to an REI coherent unit. The codes are show in the table below.

Reduction Qualifier Codes

Column

Value

3 (Generation)

0 - Constant Current

3 (Generation)

1 - Constant Admittance

3 (Generation)

Blank or 2 - REI

4 (Load)

0 - Constant Current

4 (Load)

1 - Constant Admittance

4 (Load)

Blank or 2 - REI

>DEBUG = NONE
         MINOR
         MAJOR
         ORDERING

Use this to request the debug feature.

Reduction Debug Codes

Debug

Effect

Minor

Minimal debug.

Major

Includes dump of intermittent reduction steps.

Ordering

Includes full dump of reordering arrays during each nodal elimination step.

>ELIM_MODE, GEN = CURRENT, LOAD = CURRENT, SHUNT_Y = ADMITT
                  ADMITT          ADMITT             CURRENT
                  REI,PMIN=<n>    REI                REI

This command determines how the nodal generation, load, and shunt admittance on eliminated nodes is to be processed. It does not affect the original quantities of the interior or envelop (border) nodes. The disposal options are to convert selected quantities to nodal current, to nodal shunt admittance, or to append them to an REI node.

>ENVELOPE_BUSES = BE

This command, when elected, changes the subtypes of all envelope node to type BE. Its primary merit is to secure the voltages of the terminal buses at their base case values an improve the solvability of the reduced equivalent system. The default option is to leave the envelope buses in their original subtype.

>EXCLUDE_BUSES

This command excludes from the retained network the buses listed on the bus-formatted records following this statement. Its purpose is to allow more flexibility in the definition than allowed with a simple SAVE_BASES or SAVE_ZONES. Obviously, the retained system must already be defined by a prior SAVE_BASES or SAVE_ZONES command.

>INCLUDE_BUSES

This command includes in the retained network additional buses listed on the bus-formatted records following this statement. Its purpose is to allow more flexibility in the definition than allowed with a simple SAVE_BASES or SAVE_ZONES. Obviously, the retained system must already be defined by a prior SAVE_BASES or SAVE_ZONES command.

>INCLUDE_CON = <filespec>

Use this command to include a set of user-specified default command qualifiers, which is stored in a file. Such a default command file should not contain this / INCLUDE_CON statement.:

>KEEP_AI_SYS = ON
               OFF

This command requests that the equivalent network will retain all of the attributes of area interchange control. This includes all area slack nodes and all tie line terminal nodes.:

>MIN_EQUIV_Y = .02
               <num>

This command specifies the minimum admittance of equivalent branches that are retained. Its purpose is to reduce the large number of equivalent branches which are generated, some of which have such large impedances that their contribution to the flows are marginal. A smaller value of 1.0 is recommended. Equivalent branches which have lower admittances (or what is the same, higher impedances) will be replaced with equivalent shunt admittances at both terminals.:

>OPTIMAL_REDU = ON
                OFF

This command switches the optimal network determination feature, which precedes the actual network reduction. When the optimal network selection is ON, it may enlarge the user-specified retained system with optimally selected nodes such that the overall size of the reduced system will be minimized. In essence, it expands the boundary into the eliminated system in a manner which will topologically result in an equivalent network having more buses but fewer branches overall. Thus, the user defines a fuzzy retained system containing the minimum desired configuration, and the optimal network selection will enlarge the network if feasible.:

>RETAIN_GEN = OFF, PMIN = 100.0
              ON          <num>

This command selected all generators with generation > PMIN to be in the retained network.:

>REI_CLUSTERS, VOLT_DIFF =.25, ANGLE_DIFF = 20.
                          <num>            <num>

This command works in conjunction with the REI option on the ELIM_MODE command. An attempt is made to automatically consolidate REI clusters which may have only a single node. However, their consolidation may result in an equivalent REI node whose voltages are too bizarre. It is electrically correct, but may cause solution problems since voltages are initialized about 1.0. By restricting the voltage differences of REI consolidation candidates to those whose voltage differences are less than the user-prescribed value, the resultant consolidated REI cluster will have a more feasible voltage.:

>SAVE_BASES = <list>

This command defined the retained network as consisting of those buses which have the base kvs in list. Elements of list are separated with commas (,).:

>SAVE_BUSES

This command defines the retained network as consisting of all buses identified on the following bus-formatted records. It is a brute force method to define the retained network. It cannot be used in conjunction with SAVE_ZONES or SAVE_BASES. See INCLUDE_BUSES.:

>SAVE_ZONES = <list>, BASES = <list>

This command defines the retained network as consisting of those buses which have zones in the first list, with the optional, additional provision that their base kvs must be in the second list. Elements of the list are separated with commas (,).:

>STARTING_VOLTAGES = FLAT
                     HOT

This command defines the starting voltages which will be used in the ensuing rebuilding and solution of the reduced equivalent base. The default is FLAT, meaning that the solution will use flat starting voltages. There are two separate applications for this option. The first application is to verify the integrity of the equivalent bus and branch data structures from the complex reduction processing. When used in conjunction a another solution option:

/ SOLUTION > BASE_SOLUTION

the ensuing convergence checks performed in output report independently verify the validity of the reduced bus and branch data. The second application is to assist in a solution of a reduced equivalent system if such assistance becomes necessary.:

>ULT_MODE, GEN = CURRENT, LOAD = CURRENT, SHUNT_Y = ADMITT
                 ADMITT          ADMITT             CURRENT
                 POWER           POWER              POWER

This command defines the ultimate form which the currents distributed from the eliminated nodes to the border nodes will attain. It affects only the border nodes. Note that before the elimination, the generation, load, and shunt of each eliminated node is disposed as defined by the command ELIM_MODE. Those quantities, which were distributed as three separate current vectors during the network reduction, are now to be transformed into their ultimate form. The distributed currents (generation, load, and shunt) will be encoded into special types of +A continuation buses with ownership ***.

Ultimate Form of Distributed Currents

Option

Meaning

Code year

Comment

CURRENT

Constant current model

01

The load fields are interpreted as constant current, constant power factor

ADMITT

Constant admittance

01

The shunt fields are interpreted in the ordinary manner.

POWER

Constant MVA

02

The generation fields are interpreted in the ordinary manner.

It should be noted that the special continuation records +A with ownership *** will always be generated to hold the equivalent shunt admittance which results from the admittance to ground in the eliminated system.

RPT_SORT

/ RPT_SORT = BUS
             ZONE
             AREA
             OWNER

This command sorts output information of a solved network by bus, zone, area, or ownership. The area sort is by AO records, not by A records. See section Area Output Sort (AO).

SAVE_FILE

/ SAVE_FILE, TYPE = WSCC_ASCII,  FILE = <filespec>
                    WSCC_BINARY

/ SAVE_FILE, TYPE = NEW_BASE, FILE = <filespec>

/ SAVE_FILE, TYPE = NETWORK_DATA, FILE = <filespec>,
             DIALECTS = BPA,
                        WSCC,
                        WSCC1,
                        PTI,
             SIZE = 120,
                     80,
             RATINGS = EXTENDED
                       MINIMUM
                       NOMINAL

/ SAVE_FILE, TYPE = CHANGES, FILE = <filespec>

These commands request that the identified file type be written to the named file. Type = WSCC_ASCII or type = WSCC_BINARY writes an interface file which can be read by the WSCC Stability Program (version 9 or greater) in lieu of an IPS history file. The filename must be specified. The file can be written in either formatted ASCII or unformatted binary format. The binary format is more compact, but the ASCII file can be freely transferred between platforms with unlike hardware and/or operating systems. The file contains only that powerflow information which is required by the Stability Program; it is not a complete base case. Type = NEW_BASE is identical in function to the command /NEW_BASE, file = <filename> Type = NETWORK_DATA writes the complete network data file in various WSCC-formatted dialects.

  • The BPA dialect writes the network data in the form most identical to its originally submitted form.

  • The WSCC dialect ignores Interarea “I” records, consolidates all “+” bus records (with the exception of +A INT records) with the associated B-record; writes types L,E,T,TP,LM, and RZ branch records in the order of their original submittal; writes type R records in the order adjustable tap side to fixed tap side, or hi-low; writes type LD records in the order rectifier-inverter; writes all branch data with a minimum of X = 0.0005 p.u.; sets Vmin on bus types BV, BX, BD, and BM to 0.0, sets non-zero Qmin on bus types B , BC, BV, and BT to zero; changes type BE buses with non-zero Q-limits to type BQ; and changes zero Qmin and Qmax on type BE buses to type B.

  • The WSCC1 dialect includes all of the WSCC dialect mentioned above, and includes consolidating all branches consisting of sections into a single equivalent branch.

  • The PTI dialect ignores Interarea “I” records, consolidates all “+” bus records with the associated B-record; sets Vmin on bus types BV, BX, BD, and BM to 0.0, sets non-zero Qmin on bus types B , BC, BV, and BT to zero; changes type BE buses with non-zero Q-limits to type BQ; and changes zero Qmin and Qmax on type BE buses to type B.writes types L, E, T, TP, and RZ (ignores type LM) branch records in the order of their original submittal; writes type R records in the order adjustable tap side to fixed tap side, or hi-low; writes type LD records in the order rectifier-inverter.

In addition, type = NETWORK_DATA writes the MINIMUM or NOMINAL branch current rating in the NOMINAL field if that option is selected; the EXTENDED ratings are written to columns 81:92 only if the BPA dialect, the EXTENDED rating, and the 120-character record size are all selected (all are defaults). Type = CHANGES writes the complete set of network changes to the named file.

SOLUTION

/ SOLUTION

This command enables solution options and special post-solution processes.:

>AI_CONTROL = CON
              MON
              OFF

This command sets the switches for area interchange to CONtrol, MONitor, or OFF.

The alternate voltages and LTC taps are encoded on type B and T records. See Figure 4-13 and Figure 4-14.

SOLUTION Qualifiers

>BASE_SOLUTION

This command completely bypasses the solution routine and uses the base voltages in residence. It is useful for debugging purposes, such as validating Network Reduction, or for examining the actual old solution quantities directly from a base case.:

>DEBUG,TX=OFF,BUS=OFF,AI=OFF,DCMODEL=OFF
          ON      ON     ON          ON

This command turns on the following various program debug switches. See the table below.

Debug Switches

Switch

Meaning

TX:

LTC

BUS:

Bus Switching

AI:

Area Interchange

DCMODEL:

DC Modeling

>LIMITS, QRES= 0.10 ,PHA= 45.001,DEL_ANG= 1.000, DEL_VOLT= .150
               <num>      <num>           <num>            <num>

To set limits, the statement >LIMITS may be used as many times as is needed.

QRES p.u. MVAR by which a BQ, BG, or BX bus must be perturbed to revert from a state of Q-max control to a state of V control.

PHA Minimum angle in degrees for which fixed-tap phase shifters are modeled as ideal (no loss) devices in the decoupled starting routine.

DEL_ANG Maximum angle adjustment in radians permitted in one Newton-Raphson iteration.

DEL_VOLT Maximum voltage adjustment in per unit permitted in one Newton-Raphson iteration.

> LOAD_SOLUTION, VOLTAGES =RECTANGULAR, FILE = file_name
                           POLAR
                 DEBUG = OFF, SOLUTION = BASE
                         ON              HOTSTART

>LOAD_SOLUTION loads an alternate set of voltages and LTC taps for either the base solution (SOLUTION = BASE) or for a hot start (SOLUTION = HOTSTART). The purpose of this command is to validate other Powerflow programs (PTI, SVSPP) using similar base case data or to assist difficult solutions by providing an alternate starting point. The contents of data in file_name are shown below.

_images/Alternate_Voltages_and_LTC_Taps_for_B_Records.png

Alternate Voltages and LTC Taps for B Records

_images/Alternate_Voltages_and_LTC_Taps_for_T_Records.png

Alternate Voltages and LTC Taps for T Records

The formats of the voltages and taps are “free-field,” meaning that the information must begin at least in the column noted and that additional entities are separated with a blank space.

On the T record, tap is in per unit (TAP1/BASE1)/(TAP2/BASE2) or in radians for an LTC phase shifter.

Restrictions

The following restrictions apply:

  • All sets of B records must include all buses.

  • The voltages must be within global limits.

  • Only LTC transformers can have tap changes.

  • The taps must be within LTC tap limits.

>LTC = ON
       ON_NV
       ON_NPS
       OFF
       ON_DCONLY

This is used with the following to set the control of LTC transformers.

ON Full LTC control.

ON_NV Partial LTC control (P and Q only).

ON_NPS Full LTC voltage control, no LTC phase shifter control.

OFF No LTC control.

ON_DCONLY No LTC control (except for DC commutating transformer).

Note

To obtain meaningful results with the options ON_NV, ON_NPS, or ON_DCONLY, the taps of the other LTC’s should not change. Recall that normally with a flat start (VFLATSTART=ON) all LTC’s, including those turned off, start at the mid tap value. To represent this action, invoke the additional command:

>MISC_CNTRL, VFLATSTART =ON, DCLP = ON, X_BUS = BPA,

OFF OFF WSCC

ITER_SUM = OFF, TSTART =0.5

ON

NUMVSTEPS = 3 PHASE_SHIFTER_BIAS = BPA

WSCC

BRIDGE_CURRENT_RATING = ON

OFF

These commands and options set the solution controls.:

X_BUS = BPA
        VMAX
        WSCC

Solution option for type BX buses. The BPA option accepts any discrete reactance step on a BX bus when its solution voltage \(V\) lies in the range of \(V_{min} \leq V \leq V_{max}\). The VMAX option attempts to find the switched reactance step on each BX such that its solution voltage is the largest voltage \(V \leq V_{max}\). The WSCC option adjusts discrete steps on a BX bus (using as an initial value the B_shunt entered on the input record) only when the voltage violates the limits \(V_{min} or :math:\).

DCLP

DC solution technique for multi-terminal DC lines. OFF uses old version. ON uses linear programming (LP) routines — default is ON, and it should not be changed except in extraordinary circumstances.

``VFLATSTART = ON

OFF``

Starting option. ON = flat start. Initialization under flat start invokes the following conditions.
  • All voltages are set \(V + j0\) where \(V\) is either the controlled voltage or a value between \(V_{min}\) and \(V_{max}\).

  • All special bus types BV, BQ, BG, and BX are in nominal state. (See options X_BUS.)

  • All LTCs are set to a uniform starting value. All LTS phase shifters are set to a value closest to zero, but within top limits. (See option TSTART.)

  • All DC quantities invoke AC terminal conditions.

TSTART = 0.50

This sets the LTC transformer starting tap. The starting tap is based on this value together with the relative magnitude of the variable-tap side and fixed-tap side base kVs.

If Base_varible_tap_side < Base_fixed_tap_side then

Tap = (1-TSTART) * Tmin + TSTART * Tmax

Otherwise, it is

Tap < TSTART * Tmin + (1-TSTART) * Tmax

``ITER_SUM = OFF

ON``

This switch controls printout of the solution iteration detail report.

OFF = Print out report only if a failed solution occurs.

ON = Print out report unconditionally.

``PHASE_SHIFTER_BIAS = BPA

WSCC``

This switch determines the phase shifter angle bias for type RM phase shifters. The BPA option biases the angle to zero degrees (in recognization that non-zero degree phase shifts cause real-power loop flow and that biasing the angle to zero effectively bias the system to lower losses since the additional loses in the loop are minimized). The WSCC option biases the angle to the original angle specified on the TP record):

BRIDGE_CURRENT_RATING = ON OFF

This switch determines whether the converter bridge current rating is applied to the DC circuit rating. ON implies that the bridge current rating does apply; OFF implies that it doesn’t.:

>SOL_ITER, DECOUPLED = 2, NEWTON = 30
                      <n>         <nn>

This command sets the solution and iteration limits with the following:

DECOUPLED Uses decoupled method to iterate from flat start. INITIAL prefixes the solution iteration count.

NEWTON Uses Newton-Raphson method. At least three iterations must be specified. This is the final solution.

>TOLERANCE, BUS = 0.001, AIPOWER = 0.001, TX = 0.001, Q = 0.001, V = 0.001
                  <num>            <num>       <num>      <num>      <num>

This command sets the tolerances in per unit (p.u.) for convergence testing. BUS pertains to both \(P_{net}\) and \(Q_{net}\) (in per unit), AI_POWER to net area interchange export (in per unit), TX to Pkm for type RP or RM LTC phase shifters or for Qkm for type RQ and RN LTC transformers, Q to the violation of \(Q_{max}\) or \(Q_{min}\) for special bus types BQ, BG, and BX, and \(V\) to the desired controlled voltage by type BG buses or by type R transformers.

SORT_ANALYSIS

/ SORT_ANALYSIS , OVERLOAD = < BUS >, OVERVOLTAGE = < BUS >
                             < OWNER >              < OWNER >
                             < ZONE >               < ZONE >
                             < AREA >               < AREA >

This controls the sort order of selected analysis listings:

  • Overloaded transmission lines.

  • Overloaded transformers.

  • Undervoltage/overvoltage buses.

The defaults are determined by RPT_SORT options:

  • Sort by <ZONE> if RPT_SORT = <ZONE>.

  • Sort by <AREA> if RPT_SORT = <AREA>.

  • Sort by <OWNER> if RPT_SORT is defaulted.

TRACE

/ TRACE, REORDER = OFF, X_REF = OFF, AUTO = OFF, Y_MATRIX = OFF, -
                   ON           PART        ON              ON
                                FULL

             OUTPUT = OFF, MERGE = OFF, CHANGE = OFF
                      ON           ON            ON

Use this command to monitor data used by the program in various functional applications. This is an aid to user data verification.

TRANSFER_SENSITIVITIES

/ TRANSFER_SENSITIVITIES
  > OUTAGE
  L  ...
  E  ...  1 to 100 branch records in WSCC format identifying outages
  T  ...
  > OVERLOAD
  L  ...
  E  ...  1 to 100 branch records in WSCC format identifying lines
  T  ...
  checked for overloads.
  > TRANSFER
  I  ...
  I  ...  1 to 100 intertie records identifying transfer between
  I  ...  two areas which will alleviate any line overloads.
  I

This feature is similar to the outage simulation analysis, but with an important difference. Each overloaded line resulting from a contingency is quantified as to the amount of area transfer (shifting of generation from one area to another) that is necessary to alleviate the overload.

Because the problem contains three nested loops (contingency loop, line overload monitoring loop, and inter-area transfer loop), the inter-area transfer loop is restricted to user-specified sets of transfers. Even with the present limits, the number of transfers can be large (100 outages * 100 overloads * 100 transfers = 1,000,000).

Limitations and restrictions.

  • Each / TRANSFER_SENSITIVITIES must include all three components:

    > OVERLOAD > OUTAGE > TRANSFER

  • Each > OVERLOAD, > OUTAGE, and > TRANSFER component must be followed with relevant branch records of type L, E, or T, or relevant intertie records of type I.

The individual limits are:

Limit of OVERLOAD branches: 100 Limit of OUTAGE branches: 100 Limit of inter-area TRANSFER: 100

  • Lines monitored for overload must have rating (nominal) > 0.0. Extended ratings are not used.

  • Lines that are candidates for overloads or outages must have R < X.

TX_EFF

/ TX_EFF, TOTAL_LOSS = <0.04>, CORE_LOSS = <0.02>, OWNERS = < BPA >
                       <nn>                <nn>             < list >

Use this command to compare total and core transformer losses. The output can be filtered by owners. “BPA” is the default if no owners are specified.

USER_ANALYSIS

/ USER_ANALYSIS, FILE = <file_name>, DEBUG = OFF, OUTPUT = <filename>
                                             ON

This command generates customized analysis listings.

USER_ANALYSIS provides a simple macro-like programming language to perform algebraic operations involving quantities available or used in the base case in residence. This capability is not related in any way to the CFLOW programming library, which is much more powerful and flexible. However, USER_ANALYSIS provides an easy way to generate simple reports without C programming.

If FILE in the above command is omitted, or <file_name> is *, the user-defined text follows in the input stream. Otherwise, the named file becomes the input stream for this command.

DEBUG enables the debug switch. Its output appears in an output file with the extension .pfd.

OUTPUT = <filename> places a copy of the user defined output into the file selected in <filename>.

The following quantities are available from the solved base case in residence:

  • Line flows, P_in or Q_in, measured at either bus1 or bus2 terminal.

  • Intertie flows, P_in or Q_in, measured at metering points.

  • Scheduled intertie flow, P_sched.

  • Losses by Zones, Ownerships, Areas or system totals.

  • All bus quantities: P_gen, P_max, Q_gen, Q_max, Q_min, P_load, Q_load, Caps_scheduled, Caps_used, Reactors_scheduled, Reactors_used, Susceptance_used, Susceptance_scheduled, Q_unscheduled. Voltage in per unit or in kV.

Example

A simple example illustrates this concept. The records following the / USER_ANALYSIS have not been introduced. However, the scheme is simple, and the purpose of the records is fairly obvious.

In the example, it is desired to list the sums (P_in and Q_in) of two selected branches.

/ USER_ANALYSIS, FILE = *
.
. The following symbols define P_in.
.
> DEFINE_TYPE BRANCH_P
LET A1 = ELDORADO 500*LUGO        500 1
LET A2 = MOHAVE   500*LUGO        500 1
> DEFINE_TYPE FUNCTION
LET S1 = A1 + A2
.
. The following symbols define Q_in.
.
> DEFINE_TYPE BRANCH_Q
LET B1 = ELDORADO 500*LUGO        500 1
LET B2 = MOHAVE   500*LUGO        500 1
> DEFINE_TYPE FUNCTION
LET S2 = B1 + B2
H
C Branch                        P_in    Q_in
C                               (MW)    (MVAR)
C
C ELDORADO/LUGO        500. 1 = $A1     $B1
C MOHAVE  /LUGO        500. 1 = $A2     $B2
C
C Total                       = $S1     $S2

Notice that this example contains two types of data: definitions and comments.

The definitions > DEFINE_TYPE BRANCH_P, > DEFINE_TYPE BRANCH_Q, and > DEFINE_TYPE FUNCTION identify the type of symbols that follow.

The symbols A1, A2, S1, B1, B2, and S2 are assigned to specific quantities in the network. They are evaluated after the case is solved.

In the analysis phase, the user-defined report is compiled first. The report consists of a single pass through the comment text, substituting symbols for evaluated quantities before the line is printed. The symbols are identified with a leading $ followed by a valid symbol name.

Let us make the assumption that the symbols above are evaluated as follows:

A1 = 859.2
A2 = 901.8
S1 = 1761.0
B1 = 245.1
B2 = 254.2
S2 = 499.3

Immediately before printing, these values are encoded into the symbol fields into the comment text. Their default format is F6.0. The output report appears as follows.:

Branch                      P_in    Q_in
                            (MW)   (MVAR)
ELDORADO/LUGO   500. 1 =    859.    245.
MOHAVE  /LUGO   500. 1 =    902.    254.
Total                  =   1761.    499.

Three types of text follow the / USER_ANALYSIS record: pagination specifications, symbol definitions, and user-defined comment text. They are described in more detail in the following sections and are then illustrated with a second example.

Symbol Definitions

Symbol definitions have either a one-line or multiple-line format.

The one-line format is:

> DEFINE_TYPE <symbol_type><symbol_name>=<id_of_computed_quantity>

The multiple-line format is:

> DEFINE_TYPE <symbol_type> <symbol_name> = <id_of_computed_quantity> <symbol_name> = <id_of_computed_quantity> <symbol_name> = <id_of_computed_quantity>

Some simple rules must be followed:

  • All > DEFINE_TYPE data is free-field. Blanks and commas are delimiters. If a blank character is part of a name, substitute a pound sign (#).

Example: JOHN DAY 500.0 --> JOHN#DAY 500.0

A blank circuit ID in a multicircuit line must also be entered as a pound sign (#).

Example: B = ELDORADO 500 LUGO 500 #

  • All > DEFINE_TYPE data is case-insensitive. No distinction is made between upper and lower case symbol characters. The case, however, is preserved in the analysis report as it was entered.

  • The symbol names are limited to six characters.

  • The symbol quantities are encoded with a default format of F6.0. The field begins in the column position of the $ and continues the necessary field width (default is six) as specified by the format. This default format may be changed by appending the new format to the symbol name using the FORTRAN convention, as shown below.

C Total                   = $S1/F8.1 $S2/F8.1

>DEFINE_TYPE BRANCH_P and >DEFINE_TYPE BRANCH_Q

This defines line flows, both P_in and Q_in, computed at the bus1 terminal (default) or at bus2 if an asterisk (*) immediately follows the base kV. Below, square brackets “[”� and “]”�denote enclosed optional quantities.:

>DEFINE_TYPE BRANCH_P (Branch flow in MW)
LET P1 = BUS1 BASE1[*] BUS2 BASE2[*] ID
LET P2 = BUS3 BASE3[*] BUS3 BASE4[*] ID
...
LET PN = BUSM BASEM[*] BUSN BASEN[*] ID
>DEFINE_TYPE BRANCH_Q (Branch flow in MW)
LET Q1 = BUS1 BASE1[*] BUS2 BASE2[*] ID
LET Q2 = BUS3 BASE3[*] BUS3 BASE4[*] ID
...
LET QN = BUSM BASEM[*] BUSN BASEN[*] ID

>DEFINE_TYPE INTERTIE_P or DEFINE_TYPE INTERTIE_Q

This defines the area interchange flow, either \(P_{in}\) (MW) or \(Q_{in}\) (MVAR). Either quantity is computed at the tie-line metering points.:

>DEFINE_TYPE INTERTIE_P (Interchange flow in MW)
LET I1 = AREA_1 AREA_2
LET I2 = AREA_3 AREA_4
...
LET IN = AREA_M AREA_N
>DEFINE_TYPE INTERTIE_Q (Interchange flow in MVAR)
LET J1 = AREA_1 AREA_2
LET J2 = AREA_3 AREA_4
...
LET JN = AREA_M AREA_N

> DEFINE_TYPE INTERTIE_P_SCHEDULED

This defines the scheduled area intertie flow (I records) as \(P_{in}\) (MW).:

>DEFINE_TYPE INTERTIE_P_SCHEDULED (Scheduled Interchange flow in MW)
LET I1 = AREA_1 AREA_2
LET I2 = AREA_3 AREA_4
...
LET IN = AREA_M AREA_N

>DEFINE_TYPE OWNER_LOSS AREA_LOSS ZONE_LOSS SYSTEM_LOSS

>DEFINE_TYPE OWNER_LOSS
LET O1 = BPA, O2 = PGE,  etc.
>DEFINE_TYPE AREA_LOSS,
LET A1 = NORTHWEST, etc.
>DEFINE_TYPE ZONE_LOSS,
LET Z1 = NA, Z2 = NB, etc.
>DEFINE_TYPE SYSTEM_LOSS,
LET SYSTOT

This defines losses by Area, Zone, Ownership, or total system.

>DEFINE_TYPE FUNCTION

This defines the following records as containing algebraic operators:

+, -, *, /, **, <, >, (, and ).

>DEFINE_TYPE FUNCTION
 LET T1 = (Z1 ** 2 + Z2 ** 2 ) ** 0.5
 LET T2 = (Z1 > 1200.0) * 100.0

T1 evaluates as the square root of the sum of the squares Z1 and Z2. T2 evaluates as 100 times the excess of Z1 over 1200.0. Some simple rules must be followed:

  • All symbols referenced on the right-hand side must be defined prior to reference.

  • Parentheses can be nested to any level. Operation begins inside the innermost level.

  • A single function is limited to 30 symbols and operators.

  • Operators have the following precedence (highest to lowest):

**
*,/
>,<
+,-

FUNCTION admits simple trigonometric (and one absolute value) functions where the relevant arguments or returned values are expressed in radians:

sin(), cos(), tan(), arcsin(), arccos(), arctan(), and abs().

Here is an example: compute the voltage angle difference between two buses, KEELER 500 and PAUL 500.

> DEFINE_TYPE BUS_INDEX
LET A = KEELER  500
LET B = PAUL       500
> DEFINE_TYPE FUNCTION
LET DIF = 57.29578 * (ARCTAN(A.VI/A.VR) - ARCTAN(B.VI/B.VR))

Here, A.VR and A.VI are the real and imaginary components to the per unit voltage at KEELER 500. Similarly, B.VR and B.VI for PAUL 500. The ARCTAN function returns the angle in radians. The difference is then converted to degrees.

>DEFINE_TYPE OLDBASE

This defines pertinent information from the retrieved OLD_BASE data file. An example will demonstrate the use of these symbols.

>DEFINE_TYPE OLDBASE
 LET A = DISK
 LET B = DIR
 LET C = FILE
 LET D = CASE
 LET E = DATE
 LET F = TIME
 LET G = DESC
 LET H = PFVER
 LET I = USER

C OLD_BASE CASE = $D/A10
C DESCRIPTION $G/A20
C
C GENERATED ON $E/A10 $F/A10
C OWNER $I/A10
C POWERFLOW VERSION $H/A10

> DEFINE_TYPE BUS_INDEX

This defines the following records as bus indices. This index is used in conjunction with a coded suffix to obtain specific bus quantities.

Valid suffixes and their associated bus quantities are shown the table below.

Suffixes for Bus Quantities

Suffix

Quantity

.PL

P_load in MW

.QL

Q_load in MVAR

.PG

P_gen in MW

.PM

P_max in MW

.QG

Q_gen in MVAR

.QM

Q_max in MVAR

.QN

Q_min in MVAR

.RKK

Real part of driving point admittance (YKK=RKK+jXKK). Also known as short circuit admittance.

.XKK

Imaginary part of driving point admittance (YKK=RKK+jXKK). Also known as short circuit admittance.

.V

V in per unit

.VA

Voltage angle in degrees

.VR

V in per unit, real component

.VI

V in per unit, imaginary component

.VK

V in kV

.VM

V_max in per unit

.VN

V_min in per unit

.C

Q_caps used in MVAR

.CM

Q_caps scheduled in MVAR

.R

Q_reactors used in MVAR

.RM

Q_reactors scheduled in MVAR

.QU

Q_unscheduled in MVAR

.DVQ

dV/dQ sensitivity kV/MVAR

.DVP

dV/dP sensitivity in kV/MW.

.S

Total reactive used (Capacitors or Reactors) in MVAR.

.SM

Total reactive available (Capacitors or Reactors) in MVAR

An example will demonstrate these concepts.

Compute the generator current (in amps) of Paul 500.0.

> DEFINE_TYPE BUS_INDEX
LET A = PAUL 500.0
> DEFINE_TYPE FUNCTION
LET B = (A.PG ** 2 + A.QG ** 2) ** 0.5
LET C = 1000.0 * B / (3.0 ** 0.5 * A.VK)

Here symbol B contains the generation in MVA, and C contains the current in amps.

> DEFINE_TYPE BRANCH_INDEX

This defines the following records as branch indices. This index is used in conjunction with a coded suffix to obtain specific branch quantities.

Valid suffixes and their associated branch quantities are shown in the table below.

Suffixes for Branch Quantities

Suffix

Quantity

.TAP1

Tap1 in kV for a T or in degrees for a TP record

.TAP2

Tap2 in kV for a T or TP record

.TAP

The discrete tap number (lowest tap = 1) for an LTC transformer.

.TAPS

The total number of discrete taps for a LTC transformer.

An example will demonstrate these concepts.

Show the tap, the discrete tap number, and the number of discrete taps for a transformer FRANKLIN 115/230

>DEFINE_TYPE LINE_INDEX
LET FR = FRANKLIN 115.0 FRANKLIN 230.0
C  TX AT     TAP         TAP #        # OF TAPS
C FRANKLIN $FR.TAP2/F7.3  $FR.TAP/F3.0  $FR.TAPS/F3.0

Here symbol B contains the generation in MVA, and C contains the current in amps.

> DEFINE_TYPE ZONE_INDEX

This defines the following records as zone indices. This index is used in conjunction with a coded suffix to obtain specific zone quantities.

Valid suffixes and their associated zonal quantities are shown in the table below.

Suffixes for Zonal Quantities

Suffix

Zonal Quantity

.PG

P_gen in MW

.QG

Q_gen in MVAR

.PL

P_load in MW

.QL

Q_load in MVAR

.PLS

P_loss in MW

.QLS

Q_loss in MVAR

.PSH

Installed (Scheduled) P_shunt in MW

.QSH

Installed (Scheduled) Q_shunt in MVAR

.SCAP

Installed (Scheduled) Q_cap in MVAR

.SREK

Installed (Scheduled) Q_reactors in MVAR

.UCAP

Used Q_cap in MVAR

.UREK

IUsed Q_reactors in MVAR

The following example illustrates these concepts.

> DEFINE_TYPE ZONE_INDEX
LET  ZA = NA
LET  ZB = NB
LET  TP = ZA.PLS + ZB.PLS
LET TQ = ZA.QLS + ZB.QLS
C
C Zone       Ploss Qloss
C (MW)       (MVAR)
C
C NA        $ZA.PLS   $ZA.QLS
C NB        $ZB.PLS   $ZB.QLS
C- - - - - - - - - - - - - - - - - - - - - - - - -
C Total      $TP       $TQ
C

The symbol ZA.PLS contains the losses in MWs for zone NA.

> DEFINE_TYPE OWNER_INDEX

This defines the following records as owner indices. This index is used in conjunction with a coded suffix to obtain specific owner quantities.

Valid suffixes and their associatedownership quantities are shown in the table below.

Suffixes for Ownership Quantities

Suffix

Onwership Quantity

.PG

P_gen in MW

.QG

Q_gen in MVAR

.PL

P_load in MW

.QL

Q_load in MVAR

.PLS

P_loss in MW

.QLS

Q_loss in MW

.PSH

Installed (Scheduled) P_shunt in MW

.QSH

Installed (Scheduled) Q_shunt in MVAR

.SCAP

Installed (Scheduled) Q_cap in MVAR

.SREK

Installed (Scheduled) Q_reactors in MVAR

.UCAP

Used Q_cap in MVAR

.UREK

IUsed Q_reactors in MVAR

The following example illustrates these concepts.

> DEFINE_TYPE OWNER_INDEX
LET  ZA = BPA
LET  ZB = PPL
   DEFINE_TYPE FUNCTION
   LET TP = ZA.PLS + ZB.PLS
   LET TQ = ZA.QLS + ZB.QLS
C
C Onwer       Ploss Qloss
C (MW)       (MVAR)
C
C BPA       $ZA.PLS   $ZA.QLS
C PPL       $ZB.PLS   $ZB.QLS
C- - - - - - - - - - - - - - - - - - - - - - - - -
C Total      $TP       $TQ
C

The symbol ZA.PLS contains the losses in MWs for owner BPA.

There are three remaining types of indices:

> DEFINE_TYPE SYSTEM
> DEFINE_TYPE INTERTIE_INDEX
> DEFINE_TYPE AREA_INDEX

These commands define following records as system, intertie, and area indices, respectively. Their use is similar to the bus and zone indices.

> DEFINE_TYPE TRANSFER_INDEX

This defines the following records as transfer indices. This index is used in conjunction with a coded suffix to obtain specific transfer quantities.

Valid suffixes and their associated transfer quantities are shown in the table below.

Suffixes for Branch Quantities

Suffix

Quantity

.RKM

Real part of transfer impedance (p.u.)

.XKM

Imaginary part of transfer impedance (p.u.)

.DVP

Sensitivity d(V1-V2)/dP in kV/MW

.DVQ

Sensitivity d(V1-V2)/dQ in kV/MVAR

.DTP

Sensitivity d( )/dP in degrees/MW

The transfer impedance is the point-to-point impedance between two buses. It would represent the incremental (complex) voltage change due to a 1.0 p.u. current injection into bus1 in conjunction with a -1.0 injection out of bus2. It represents the impedance of the entire network with respect to the two terminal nodes.

The transfer sensitivity is the sensitivity of the voltage or angle difference between two buses with respect to a 1 MW or MVAR change in injection between two buses.

The following example obtains the transfer impedance and transfer sensitivities between COULEE 2 13.8 - JOHN DAY 500 and between JOHN DAY 500 - MALIN 500.

> DEFINE_TYPE TRANSFER_INDEX
LET TX1 = COULEE   500 JOHN#DAY  500
LET TX2 = JOHN#DAY 500 MALIN     500
C
C TRANSFER IMPEDANCES       R (P.U.)        X (P.U.)
C
C COULEE   500 JOHN DAY 500 $TX1.RKM/E12.5  $TX1.XKM/E12.5
C JOHN DAY 500 MALIN    500 $TX2.RKM/E12.5  $TX2.XKM/E12.5
C
C TRANSFER SENSITIVITIES    dV/dP (kV/MW)   dV/dQ (kV/MVAR) dT/dP (deg/MW)
C
C COULEE   500 JOHN DAY 500 $TX1.DVP/E12.5  $TX1.DVQ/E12.5  $TX1.DTP/E12.5
C JOHN DAY 500 MALIN    500 $TX2.DVP/E12.5  $TX2.DVQ/E12.5  $TX1.DTP/E12.5

Pagination Specifications

Pagination specifications pertain to headers and subheaders. The Header record is the most important record. It has an H in column 1.

Each user-defined report must begin with a separate header record. The contents of this record become the first subheader. Additional subheaders can be appended to the report.

The header and subheaders are listed at the top of each page on the user-defined analysis report.

Following the header and optional subheader records are 120-character user-formatted comment text, identified with a C in column 1. These records define the user-defined analysis report.

Only columns 3-120 are used. Column 1 (containing the C) is ignored in the report, while column 2 is interpreted as Fortran carriage control:

” ” = single line spacing

“0” = double line spacing

Symbols whose character fields are to be encoded with numerical values computed from the solved case in residence are prefixed with a $ and suffixed optionally with a format specification.

Examples

C WEST-OF-RIVER FLOW/NORTH= $T1/F8.0   WEST-OF RIVER FLOW/SOUTH= $T2/F8.0
C ------------------------             -----------------------
C ELDORADO/LUGO    500. 1 = $A1/F8.0   PALOVRDE/DEVERS  500. 1 = $A9/F8.0

There are two symbol substitutions in the first comment line: T1 and T2. Both elect an optional format, which is F8.0. By coincidence, the symbol field with $T1/F8.0 is eight characters, the same as the Format specification. If the Format was larger, substitution would overwrite additional columns on the right. If the format was smaller, only the left-most characters would be used with a blank fill on the remaining (unused) field.

The second comment line has no substitution. The third has two symbol substitutions, similar to the first comment line.

If no format specification is used, the default (F6.0) is used. In this instance, it would be plausible to use five-character symbol names. When the $ is included, the substituted text is the same field width as the original text. The program limits are 500 comment lines including headers and subheaders. No symbol substitution occurs on headers or subheaders.

If a comment refers to an undefined symbol, a warning is issued, with the questionable fields flagged with a string of ??????``s. The limits are 500 lines of symbol definition and 1000 symbols. Comment text (.`` in column 1) is excluded.

PFC Examples

This section gives several examples of PFC files that can be used with the bpf process.

Base Case Example

Here is a basic powerflow run that contains all data in the control file (ninebus.pfc).

(  POWERFLOW,CASEID=NINEBUS,  PROJECT = EXAMPLES  )
/ HEADER
H    WSCC Nine Bus Base Case
/ COMMENT
C
C  CASEB-1_  NINE-BUS CASE, ON CARDS, THAT IN ADDITION TO TESTING
C             THE FEATURES OF CASE A-1, ALSO FEATURES_TRANSFORMERS
C            AND SUBTYPE "E" BUSES.
C
/ P_INPUT_LIST,FULL
/ P_OUTPUT_LIST,FULL
/ AI_LIST=NONE
/ P_ANALYSIS_RPT,LEVEL = 4
/ F_ANALYSIS_RPT,LEVEL = 1
/ NEW_BASE, FILE = ninebus.bse
/ NETWORK_DATA
B     GEN1 HI    230  2  -0.0  -0.0  0.0 0.0      -0.0 -0.0 -0.0
B     GEN2 HI    230  1  -0.0  -0.0  0.0 0.0      -0.0 -0.0 -0.0
B     GEN3 HI    230  2  -0.0  -0.0  0.0 0.0      -0.0 -0.0 -0.0
B     STA A        230   1125.0  50.0  0.0 0.0    -0.0 -0.0 -0.0
B     STA B        230  2  90.     30.
B     STA C        230  2100.0   35.0 0.0 0.0     -0.0 -0.0  -0.0
BS   GEN1       16.5  2 -0.0    -0.0   0.0 0.0     71.6 -0.0 -0.01040
BE   GEN2       18 1   -0.0      -0.0  0.0 0.0    163.0 -0.0 -0.01025
BE   GEN3       13.8  2 -0.0    -0.0   0.0 0.0     85.0 -0.0 -0.01025
L     GEN1 HI    230 STA B       230  1        1700  9200        7900
L     GEN1 HI    230 STA B       230  2        1700  9200        7900
L     GEN1 HI    2302STA A      230            1         85               88
L     GEN3 HI    230 STA B       230            39       17             179
L     STA C        230 GEN3 HI   230            1190  10080   10450
L     STA A        230 GEN2 HI   230             32      161           153
L     GEN2 HI   2302STA C       230              85       72           745
T     GEN1 HI   230 GEN1        16.5                 5760  23000 1650
T     GEN2 HI   230 GEN2           18                 6250  23000 1800
T     GEN3 HI   230 GEN3        13.8                  5860 23000 1380
(STOP)

A more convenient method to perform the preceding setup is to use a NETWORK_DATA command and provide the network data portion (the power system network) in a separate file and similarly a INCLUDE_CONTROL command and provide the control comands in a separate file as well. The PFC file would look like this:

(  POWERFLOW,CASEID=NINEBUS,  PROJECT = EXAMPLES  )
/ HEADER
H      WSCC Nine Bus Base Case
/ COMMENT
C
C  CASEB-1_  NINE-BUS CASE, ON CARDS, THAT IN ADDITION TO TESTING
C            THE FEATURES OF CASE A-1, ALSO FEATURES TRANSFORMERS
C            AND SUBTYPE "E" BUSES.
C
/ NEW_BASE, FILE= ninebus.bse
/ INCLUDE_CONTROL,FILE = ninebus.ctl
/ NETWORK_DATA, FILE = ninebus.net
(STOP)

Where ninebus.ctl contains:

/ P_INPUT_LIST,FULL
/ P_OUTPUT_LIST,FULL
/ AI_LIST=NONE
/ P_ANALYSIS_RPT,LEVEL = 4
/ F_ANALYSIS_RPT,LEVEL = 1

and ninebus.net contains:

B     GEN1 HI   230  2  -0.0  -0.0 0.0 0.0    -0.0 -0.0 -0.0
B     GEN2 HI   230  1  -0.0 -0.0 0.0 0.0     -0.0 -0.0 -0.0
B     GEN3 HI   230  2  -0.0 -0.0 0.0 0.0     -0.0 -0.0 -0.0
B     STA A       230 1125.0 50.0 0.0 0.0     -0.0 -0.0 -0.0
B     STA B       230 2 90.    30.
B     STA C      230 2100.0  35.0 0.0 0.0    -0.0 -0.0 -0.0
BS    GEN1    16.5  2  -0.0  -0.0 0.0 0.0     71.6 -0.0 -0.01040
BE    GEN2        18 1 -0.0   -0.0 0.0 0.0   163.0 -0.0 -0.01025
BE    GEN3     13.8 2 -0.0   -0.0 0.0 0.0     85.0 -0.0 -0.01025
L     GEN1 HI  230 STA B     230 1      1700  9200        7900
L     GEN1 HI  230 STA B     230 2      1700  9200        7900
L     GEN1 HI  2302STA A    230        1     85          88
L     GEN3 HI  230 STA B     230        39   17          179
L     STA C    230 GEN3 HI   230        1190 10080  10450
L     STA A    230 GEN2 HI   230        32   161         153
L     GEN2 HI  2302STA C   230         85   72          745
T     GEN1 HI  230 GEN1    16.5                5760            23000 1650
T     GEN2 HI  230 GEN2      18                 6250            23000 1800
T     GEN3 HI  230 GEN3    13.8                5860            23000 1380

Change Case Example

Here is an example of loading a system from a solved old base case, and make data changes, and save a new base.:

( POWERFLOW, CASEID = TEST-CHG,  PROJECT = TEST-WSCC-DATA)
/ NEW_BASE, FILE = 9BUSNEW.BSE
/ COMMENTS
C  CASEB-1_  NINE-BUS CASE, ON CARDS, THAT IN ADDITION TO TESTING THE
C             FEATURES OF CASE A-1, ALSO FEATURES  TRANSFORMERS AND
C             SUBTYPE "E" BUSES.
C                THE BUS_BRANCH FILE AND THE CHANGE FILE ARE REMOTE
/ INCLUDE_CONTROLS, FILE = TESTCONT.CTL
/ OLD_BASE, FILE= ninebus.bse
/ CHANGES, FILE = CHANG.DAT
( STOP - END OF TEST )

Note

PFC language commands are not performed in the order they are encountered in the file, but rather in the order the bpf program decides is logical.

Merge Case Example 1

Here is an example of merging two systems defined from sepearate solved old base files.:

( POWERFLOW, CASEID = TEST-MERGE, PROJECT = TEST-MERGE_OLD_BASE )
/COMMENTS
C  CASE 2 - TEST BASE MERGE BY MERGING TWO IDENTICAL BASE SYSTEMS.
C           TWO MUTUALLY EXCLUSIVE SUBSYSTEMS ARE INTEGRATED TO
C           REGENERATE THE ORIGINAL SYSTEM.
C
C    EACH SYSTEM IS BUILT FROM DIFFERENT AREAS OF THE SAME OLDBASE
.
.     control options
.
/ P_INPUTLIST,FULL
/ F_INPUTLIST,NONE
/ P_OUTPUTLIST,FULL
/ F_OUTPUTLIST,NONE
/ AILIST=FULL
.
/ NEW_BASE, FILE = MERGOLD.BAS
.
.      DEFINE SUBSYSTEM "AREA 1"
.
/ MERGE_OLD_BASE, SUB_SYSTEM_ID = AREA-1, OLD_BASE = TESTDC.BAS
> USE_AIC
> SAVE_AREAS
A  AREA 1
.
.      DEFINE SUBSYSTEM "AREA 2"
/ MERGE_OLD_BASE, SUB_SYSTEM_ID = AREA-2,OLD_BASE = TESTDC.BAS
> SAVE_ AREAS
A  AREA 2
.
.      SUBSYSTEMS ARE NOW MERGED
.
.      ( CHANGES ) may now follow
.
( STOP )

Merge Case Example 2

Here is an example of merging two topologically overlapping networks into one consolidated network and solvubg the network, creating a new base to be called J86JFY82. Each of the original networks is to be appropriately modified before the merger. The first network is a WSCC base case saved as 86J201.BSE which must be modified by saving areas, excluding buses, renaming buses and excluding certain branches. The second network is the BPA system which will be extracted from the branch file BDFY82W using the extraction date Jan 1986.:

(POWERFLOW, CASEID = J86FY82, PROJECT = BASEMERGE)
/NEWBASE FILE = [APF]J86FY82.BSE
.
.Note:  composite network will be solved with defaults.
.
/MERGE_OLD_BASE,SUBSYSID = WSCC_NETWORK,OLD_BASE=86J201.BSE
>SAVE_AREAS
.....
..... "A" - records - name fields only
.....
>EXCLUDE_BUSES
.....
..... "B" - records - name fields only
.....
>RENAME_BUSES
.....
..... rename table
.....
>EXCLUDE_BRANCHES
.....
..... "L" - records - name fields only
.....
/MERGE_NEW_BASE,SUBSYSID = BPA_NETWORK,BRANCH_DATA=BDFY84,DATE=186
.....
..... "B" - records for BPA system
.....
/CHANGES
.....
..... change records
.....
(STOP)

Reduction Case Example

Here is an example of reducing an existing network to a desired size and solving the reduced network. Reduction is achieved by retaining only specified zones from the original system. Produce full input/output listings on microfiche. Partial input/output listings (restricted to certain specified zones) will be printed on paper. Give full analysis report on both paper and fiche. In solving the network, regulating transformers will be activated and area-interchange control will be switched to control mode. Provide full listing of area interchange flows.:

(POWERFLOW, CASEID = A86FY81RED, PROJECT = SAMPLE_PCL)
/OLDBASE, FILE = A8601FY81.BA2
/REDUCTION
>SAVE_ZONES,NA,NB,NC,ND,NE,NF,NG,NH,NI,NJ,NR
>SAVE_ZONES 19,17,20,08,PR,27,16
/P_INPUT_LIST, ZONES=NA,NB,NC,ND,NE,NF,NG,NH,NI,NJ,NK
/P_INPUT_LIST, ZONES = 19,17,20,08,PR
/P_OUTPUT_LIST, ZONES= NA,NB,NC,ND,NE,NF,NG,NH,NI,NJ,NK
/P_OUTPUT_LIST, ZONES= 19,17,20,08,PR
/LTC = ON
/AI_CONTROL = CON
/AI_LIST = FULL
/P_ANALYSIS_RPT, LEVEL = 4
(STOP)

Powerflow Command Language (PCL)

Introduction

The commands listed below are those currently available in the Powerflow Command Language (PCL). This language was developed to meet the needs of communication between the GUI and the Powerflow server (ipfsrv), but is also available for direct user entry via the Command Dialog in the GUI or loading of a PCL command file in the GUI, and via the ipfbat command line process, by invoking the same command file. However, since ipfsrv is expecting these commands to have been generated by another program, it expects them to be syntactically perfect and legally ordered. There is no checking of input, or confirmation procedure, or chance to edit and re-enter commands. A typo can easily crash the program.

The GUI process sends these commands in response to various button pushes, and all checking, etc. is done before a command is ever sent. The generated text strings are placed in a buffer which is sent over an interprocess communications channel open to the server process (ipfsrv). The server process on its end interprets these commands and responds by changing its memory resident case data, querying the case data, sending data back to the GUI, etc. CFLOW library routines also send and receive these commands in the same manner.

PCL has some overlap with the PFC command language used in the batch Powerflow (bpf) program. For those commands which do the same things (e.g. OLD_BASE, CHANGES, etc.) the syntax is identical. However, many of the batch commands are not available in PCL, and of course PCL contains many commands which are not needed by bpf. The same conventions on case and spacing apply to both languages.

  • Upper, lower, or mixed case are legal: OLD_BASE, Old_Base, oldbase.

  • Spaces between command elements are ignored: /oldbase,file=std.bse and /   OLD_base  ,   File   =   std.bse are equivalent.

  • Underscore may be used within command words if desired: oldbase, old_base, O_L_D__B_A_S_E.

IPC Commands Quick Descriptions

Command

Description

Section

(END)

Terminates a data stream following a command.

(END)

*[EOM]

Used in the Command Dialog to launch a command stream.

*[EOM]

``CFLOW`

Launches a CFLOW program.

CFLOW

CHANGES

Introduces system data change records.

CHANGES

GET_DATA

Fetches data from the Powerflow process.

GET_DATA

GET_DATA, TYPE = A_DATA

Retrieves all type A input data records in WSCC format.

GET_DATA, TYPE = A_DATA

GET_DATA, TYPE = AREA_DATA

Initializes the user analysis arrays.

pcl-get-data-area-data

GET_DATA, TYPE = AREA_LIST

Loads the area list dialog into the Network Data Edit Dialog and the Reports Dialog.

GET_DATA, TYPE = AREA_LIST

GET_DATA, TYPE = BSEKV_LIST

Loads the base kV list dialog into the Network Data Edit Dialog and Reports Dialog.

GET_DATA, TYPE = BSEKV_LIST

GET_DATA, TYPE = BUS_EXISTS

Inquires whether a given bus exists.

GET_DATA, TYPE = BUS_EXISTS

GET_DATA, TYPE = BUS_LIST

Loads the bus list dialog in the Alpha Search, Network Data Edit, and Reports Dialogs.

GET_DATA, TYPE = BUS_LIST

GET_DATA, TYPE = BUS_VOLTAGES

Returns a list of all bus voltages.

GET_DATA, TYPE = BUS_VOLTAGES

GET_DATA, TYPE = CONNECTION

Retrieves the network connection diagram for a given set of buses.

GET_DATA, TYPE = COUNT

Computes the number of network data records satisfying the filter criteria in a NETWORK_DATA command.

GET_DATA, TYPE = FILE_EXISTS

Inquires whether a named files exists.

GET_DATA, TYPE = INITIALIZE_DEF

Initializes the user analysis arrays.

GET_DATA, TYPE = INPUT

Retrieves the full network data for a bus.

GET_DATA, TYPE = I_DATA

Retrieves all I type data in WSCC format.

GET_DATA, TYPE = LINE_IMPEDANCE_CALCULATION

Computes transmission line impedance data given tower geometry and conductor characteristics.

GET_DATA, TYPE = LOAD_AREA

Initializes arrays associated with area interchange data.

GET_DATA, TYPE = SUB_DEFINE

Loads the user analysis arrays.

GET_DATA, TYPE = LOAD_REF_AREA

Initializes arrays associated with area interchange data.

GET_DATA, TYPE = LOAD_REF_BASE

Loads a reference base case history file for the purpose of base case comparison or plot comparisons.

GET_DATA, TYPE = NETWORK_DATA

Filters network data records.

GET_DATA, TYPE = OUTAGES

Retrieves the list of outaged data for the Report Dialog.

GET_DATA, TYPE = OUTPUT

General purpose command for accessing virtually the entire network data base.

GET_DATA, TYPE = OWNER_LIST

Loads the ownership list dialog into the Reports Dialog and the Network Data Edit Dialog.

GET_DATA, TYPE = RECORD_LIST

Loads the record type list dialog into the Reports Dialog and the Network Data Edit Dialog.

GET_DATA, TYPE = COMMENTS

Obtains the area interchange output data from the WSCC-formatted input area records.

GET_DATA, TYPE = REF_OUTPUT

General purpose command for accessing virtually the entire network data base.

GET_DATA, TYPE = STATUS

Retrieves the case description.

GET_DATA, TYPE = SUB_DEFINE

Performs character string substitution using computed base case quantities.

GET_DATA, TYPE = COMMENTS

Retrieves all IPF system parameters describing the case in residence.

GET_DATA, TYPE = ZONE_LIST

Loads the zone list dialog into the Reports Dialog and the Network Data Edit Dialog.

INITIALIZE

Starts up powerflow engine.

NETWORK_DATA

Specifies that a network data file is to be loaded into the powerflow engine.

NEW_BASE

Saves the solved, resident base case.

OLD_BASE

Loads a previously solved powerflow case file.

PLOT

Plots a powerflow coordinate file

PUT_DATA, TYPE = COMMENTS

Defines IPF system parameters which either describe the case in residence or modify parameters which will influence certain processes (solution, debugging).

QUIT, EXIT

Executes closing procedures and exits the powerflow engine.

REPORTS, SELECT AI_SUMMARY

Retrieves filtered area interchange output data.

REPORTS, SELECT BUS_BR_INPUT

Retrieves filtered WSCC-formatted bus and branch input data records.

REPORTS, SELECT BUS_BR_OUTPUT

Retrieves filtered bus and branch output records.

REPORTS, SELECT BUS_INPUT

Retrieves filtered WSCC-formatted bus input data records.

REPORTS, SELECT BUS_UVOV

Retrieves filtered under/over voltage bus output data.

REPORTS, SELECT LINE_COMPARISON

Retrieves filtered line loading differences between the base case in residence and a selected base case history data file.

REPORTS, SELECT NETWORK_CHANGES

Retrieves the list of all accumulated changes performed on the base case in residence.

REPORTS, SELECT NETWORK_DELETIONS

Retrieves the list of all deleted network data in WSCC format.

REPORTS, SELECT OVERLOADED_LINES

Retrieves filtered overloaded branch output data.

REPORTS, SELECT OVERLOADED_TXS

Retrieves filtered overloaded transformer output data.

REPORTS, SELECT PHASE_SHIFTER

Retrieves the phase shifter report.

REPORTS, SELECT TIE_LINE_SUMMARY

Retrieves filtered area tie line flows.

REPORTS, SELECT VOLTAGE_COMPARISON

Retrieves filtered voltage differences between the resident base case and a selected base case history data file.

SAVE_FILE

Saves the solved resident base case in a named file.

SOLUTION

Causes the powerflow engine to solve the currently resident base case.

SYSCAL

Passes a system command to the operating system.

General

(END)

Use this command to terminate a data stream following a command in a PCL command file. Some commands which would be followed by data are /CHANGES, FILE=* and /PLOT.

Example:

/Network_Data, File = *
B ARAPAHOA115.
BS ARAP1 13.8 3.5 45. 1.05
B SHERIDAN115. 41.5 11.8
T ARAPAHOA115. ARAP1 13.8 .00672.14684.00064-00313115.5 13.2
L ARAPAHOA115. SHERIDAN115. .00261.00657 .0004
(end)

*[EOM]

This is used when entering commands in the Command Dialog of the GUI, to indicated that the line or lines you have entered into the buffer should be send to ipfsrv. When the GUI generates this “End of Message” string, it has all six characters; however, the first two characters are all that are required to be entered.

For Command Dialog usage, this also serves in place of the (END) command above. But unlike it, this must be entered after every command, when using the Command Dialog.

INITIALIZE

This command starts up the powerflow engine, and therefore will never be entered by a GUI user, but is required at the beginning of every ipfbat command file. It calls p_pfinit.f with the following parameters.:

integer function p_pfinit (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/INITIALIZE

QUIT, EXIT

This command in either form executes closing procedures and exits the powerflow engine. It calls p_pfexit.f with the following parameters.:

integer function p_pfexit (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains either of the following lines of information.:

/QUIT
/EXIT

SYSCAL

This command passes a string to the operating system for execution. It is used by the GUI to send a plot to the currently selected print destination, but it will pass any command string.

Example:

/SYSCAL
lp -d COMPAQ20 -T ps 0102hw1.ps
(END)

Warning

This command is effectively a command line injection vulnerability if running separate client and server.

File Opening and Saving

NETWORK_DATA

This command specifies that a network data file is to be loaded into the ipfsrv. It calls p_gtnetdat.f with the following parameters.:

integer function p_gtnetdat (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

Example:

/NETWORK_DATA, FILE=0102hw1.net

For a full description of the command /NETWORK_DATA, see the NETWORK_DATA. Successful execution should return an IPF state of 2.

NEW_BASE

This command saves the solved base case in residence in the named file. It calls p_newbse.f with the following parameters.:

integer function p_newbse (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information:

/NEW_BASE, FILE = <filename>
C < case comments - three records maximum >
C < case comments - three records maximum >
C < case comments - three records maximum >

The comment records in the above command are optional. Successful execution should return an IPF state of 6.

OLD_BASE

This command specifies that a previously solved power flow case is to be loaded from the specified file and used as the base system for the current request. It calls p_gtbase.f with the following parameters.:

integer function p_gtbase (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

Example:

/OLD_BASE, FILE = 97hs1a.bse

Successful execution should return an IPF state of 6.

SAVE_FILE

This command saves the solved base case in residence in the named file in one of four forms. One of these forms is NEW_BASE, described previously, and admits a redundancy into the command procedure.

This command calls p_svfile.f with the following parameters.:

integer function p_svfile (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains any of following information.:

/SAVE_FILE, TYPE = SYSTEM_CHANGES, FILE = <filename>

/SAVE_FILE, TYPE = NEW_BASE, FILE = <filename>

/SAVE_FILE, TYPE = NETWORK_DATA, FILE = <filename>, ...

/SAVE_FILE, TYPE = WSCC_BINARY_STABILITY, FILE = <filename>
                   WSCC_ASCII_STABILITY

 /SAVE_FILE, TYPE = NETWORK_DATA,
  FILE = < filename >,
  DIALECT = < value >, BPA | WSCC | WSCC1 | PTI
  RATINGS = < value >, EXTENDED | NOMINAL | MINIMUM
  SIZE = < value >, 120 | 80

See ipfnet, for a complete description of the Dialect, Ratings, and Size options when saving a network data file.

Processes

CFLOW

This command launches a CFLOW program if it is in your directory search path. The following works on a VAX VMS system if <program name> is defined as a foreign command::

/CFLOW
PROGRAM = my_cflow_program
<program name>:== $dev:[dir]file.exe

ARGS = is required only if the CFLOW program requires command line arguments other than the socket number. Any I/O that the CFLOW program does to standard input or standard output will be to and from the same terminal window that the ipfbat program is run from (intermixed with any I/O from the ipfbat program).

CHANGES

This command introduces system data change records. It calls p_change.f with the following parameters.:

integer function p_change (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

Examples::

/CHANGES, FILE = 0102hw1.chg
/changes, file = *
B D ARAPAHOA115.
BEM ARAP1 13.8 1.05
T M ARAPAHO 115. ARAP1 13.8 .00672.
(end)

PLOT

This command creates a PostScript diagram (map) file, using a coordinate file and the currently loaded base case. It calls plot_load.f, which is the main routine for the batch program ipfplot. The batch program takes three parameters, as shown below, and uses the second case, if provided, to produce difference plots.:

subroutine plot_load (coord_file, base1_file, base2_file)
character * 60 coord-file, base1_file, base2_file

Difference plots are not available from the GUI or ipfbat. The parameters required in the PCL formulation are a coordinate file and the name of a PostScript output file. Records which follow these two file names are interpreted as comments to be placed on the map, following any comments (C records) which occur in the coordinate file. However, if a comment begins with an ampersand (&) or an “at” symbol (@), it will not be printed. The & precedes the name of at most one auxiliary coordinate file to be included on the map. The @ signals the presence of a plot option which will override that option in the coordinate file. See Network Diagrams for complete information on plotting diagrams. See ipfplot for detailed information on use of the ipfplot program.

Example::

/plot
hvmap.cor
98hw3_study.ps
Transfer Study for PAST
Prepared by A. P. Planner
&transfer.cor
@OP Offset=12.7 18.9
(end)

SOLUTION

This command causes the powerflow engine to solve the currently resident base case. It calls p_solton.f with the following parameters.:

integer function p_solton (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information. Normal defaults are shown; optional items are in [ ].:

/SOLUTION
> BASE_SOLUTION ]
> DEBUG,TX=OFF,BUS=OFF,AI=OFF,DCMODEL=OFF           [ON]
> LTC = ON               [OFF, ON_NV, ON_NPS, ON_DCONLY]
> AI_CONTROL = CONtrol          [MON, OFF]
> MISC_CNTRL, -
    X_BUS = BPA,-               [WSCC]
    PHASE_SHIFTER_BIAS = BPA,-  [WSCC]
    DCLP = ON, -                [OFF]
    VFLATSTART = ON, -          [OFF]
    ITER_SUM = OFF, -           [ON]
    TSTART = 0.5, -
    NUMVSTEPS = 3
> SOL_ITER, DECOUPLED = 2, NEWTON = 30
> LIMITS,QRES=0.01,PHA=45.0,DEL_ANG=1.0,DEL_VOLT=0.15
> TOLERANCE, BUSV = 0.005, AIPOWER = 0.001, TX = 0.001, Q = 0.005

GET_DATA

This command with its many different forms fetches data from the powerflow engine. It calls p_gtdata.f with the following parameters.:

integer function p_gtdata (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains any of the following commands.:

/GET_DATA, TYPE = A_DATA
/GET_DATA, TYPE = AREA_DATA
/GET_DATA, TYPE = AREA_LIST
/GET_DATA, TYPE = BSEKV_LIST
/GET_DATA, TYPE = BUS_EXISTS
/GET_DATA, TYPE = BUS_LIST
/GET_DATA, TYPE = BUS_VOLTAGES
/GET_DATA, TYPE = COMMENTS
/GET_DATA, TYPE = CONNECTION
/GET_DATA, TYPE = COUNT
/GET_DATA, TYPE = FILE_EXISTS
/GET_DATA, TYPE = I_DATA
/GET_DATA, TYPE = INITIALIZE_DEF
/GET_DATA, TYPE = INPUT
/GET_DATA, TYPE = LINE_IMPEDANCE_CALCULATION
/GET_DATA, TYPE = LOAD_AREA
/GET_DATA, TYPE = LOAD_DEFINE
/GET_DATA, TYPE = LOAD_REF_AREA
/GET_DATA, TYPE = LOAD_REF_BASE
/GET_DATA, TYPE = NETWORK_DATA
/GET_DATA, TYPE = OUTAGES
/GET_DATA, TYPE = OUTPUT
/GET_DATA, TYPE = OWNER_LIST
/GET_DATA, TYPE = RECORD_LIST
/GET_DATA, TYPE = REF_AREA_DATA
/GET_DATA, TYPE = REF_OUTPUT
/GET_DATA, TYPE = SOL_PAR
/GET_DATA, TYPE = STATUS
/GET_DATA, TYPE = SUB_DEFINE
/GET_DATA, TYPE = SYSTEM
/GET_DATA, TYPE = ZONE_LIST

The routine p_gtdata.f parses these commands and calls a subroutine to perform the specific task, according to the type of data indicated.

GET_DATA, TYPE = A_DATA

This command retrieves in out_buffer all type A input data records in WSCC format. It calls a_data.f with the following parameters.:

integer function a_data (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = A_DATA

Note that no areas are specified in in_buffer; this command just gets a list of the areas in the case.:

.. _pcl-get-data-area-data:

GET_DATA, TYPE = AREA_DATA

This command obtains the area interchange output data from the WSCC-formatted input area records. This command should be preceded with a prior command GET_AREA, TYPE=LOAD_AREA. It calls p_gtbase.f with the following parameters.:

integer function p_gtdata (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = AREA_DATA
A <areaname>

GET_DATA, TYPE = AREA_LIST

This command loads the area list filter window in the Network Data Edit Dialog and the Report Dialog of the GUI. It returns in out_buffer the list of area names in the following format.:

<areaname> LINEFEED

where <areaname> is the area name in A10 format.

It calls area_list.f with the following parameters.:

integer function area_list (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains optional filter data in the following command.:

/GET_DATA, TYPE = AREA_LIST [ FROM BUS_DATA ]
                  WHERE AREAS = <area1>, <area2>, etc AND
                  ZONES = <zone1>, <zone2>, etc AND
                  OWNERS = <own1>, <own2>, etc AND
                  BASEKV = base1
                           < base ( example < 115.0 means all base
                                   kv's less than or equal to 115.0)
                           > base ( example > 115.0 means all base
                                   kv's greater than or equal to 115.0)
                           base1 < base2 (all bases between base1 and
                                           base 2)
                           base2 > base1 (same as above)
                  TYPE = '* ', 'A*', 'A?', 'I ', 'B*', 'L*', 'B?',
                         'B ', 'BE', 'BS', 'BC', 'BD', 'BV', 'BQ',
                         'BG', 'BT', 'BX', 'BM', 'BF', '+ ', 'X ',
                         'Q ', 'LD', 'LM', 'E ', 'T ', 'TP', 'R ',
                         'RZ'
                  ALL

Details of the filter are found in Dynamic Filters.

GET_DATA, TYPE = BSEKV_LIST

This command loads the base kV filter window in the Network Data Edit Dialog and the Reports Dialog of the GUI. It returns in out_buffer the list of filtered base kVs in the following format.:

<basekv> LINEFEED

where <basekv> is the base kV in F6.1 format.

It calls bsekvltt.f with the following parameters.:

integer function bsekvlst (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains optional filter data in the following command.:

/GET_DATA, TYPE = BSEKV_LIST [ FROM BUS_DATA ]
                  WHERE AREAS = <area1>, <area2>, etc AND
                        ZONES = <zone1>, <zone2>, etc AND
                        OWNERS = <own1>, <own2>, etc AND
                        BASEKV = base1
                                 < base ( example < 115.0 means all base
                                        kv's less than or equal to 115.0)
                                 > base ( example > 115.0 means all base
                                         kv's greater than or equal to 115.0)
                                 base1 < base2 (all bases between base1 and
                                               base 2)
                                 base2 > base1 (same as above)
                        TYPE = '* ', 'A*', 'A?', 'I ', 'B*', 'L*', 'B?',
                               'B ', 'BE', 'BS', 'BC', 'BD', 'BV', 'BQ',
                               'BG', 'BT', 'BX', 'BM', 'BF', '+ ', 'X ',
                               'Q ', 'LD', 'LM', 'E ', 'T ', 'TP', 'R ',
                               'RZ'
                        BUS = "<busname>" (quotes are necessary)
                        ALL
                        LOADING = (<min> <max>)

Details of the filter are found in Dynamic Filters.

GET_DATA, TYPE = BUS_EXISTS

This command inquires whether a given bus exists. It calls ex_bus.f with the following parameters.:

integer function ex_bus (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = BUS_EXISTS, BUS = bus_name base_kv

bus_name is an eight character name (blank filled to eight characters) followed by a Fortran F4.0 or F6.1 base kV.

The return status is 0 if the bus exists in the current case or 1 if it does not exist.

GET_DATA, TYPE = BUS_LIST

This command loads the bus list dialog in the Alpha Search Dialog, the Network Data Edit Dialog, and the Reports Dialog of the GUI. It returns in out_buffer the list of filtered bus names and base kVs in the following format.:

<busname><base kv> LINEFEED

where <busname> is the bus name in A8 format; <basekv> is the base kV in F6.1 format.

It calls bus_list.f with the following parameters.:

integer function bus_list (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains optional filter data in the following command.:

/GET_DATA, TYPE = BUS_LIST [ FROM BUS_DATA ]
                  WHERE AREAS = <area1>, <area2>, etc AND
                  ZONES = <zone1>, <zone2>, etc AND
                  OWNERS = <own1>, <own2>, etc AND
                  BASEKV = base1
                           < base ( example < 115.0 means all base
                                  kv's less than or equal to 115.0)
                           > base ( example > 115.0 means all base
                                  kv's greater than or equal to 115.0)
                           base1 < base2 (all bases between base1 and
                                         base 2)
                           base2 > base1 (same as above)
                  TYPE = '* ', 'A*', 'A?', 'I ', 'B*', 'L*', 'B?',
                         'B ', 'BE', 'BS', 'BC', 'BD', 'BV', 'BQ',
                         'BG', 'BT', 'BX', 'BM', 'BF', '+ ', 'X ',
                         'Q ', 'LD', 'LM', 'E ', 'T ', 'TP', 'R ',
                         'RZ'
                  BUS = "<busname>" (quotes are necessary)
                  AFTER_BUS = "<busname>"
                  ALL
                  LOADING = (<min> <max>)

Details of the filter are found in Dynamic Filters.

GET_DATA, TYPE = BUS_VOLTAGES

This command returns in out_buffer the list of all bus voltages in the following format.:

<busname><base kv><voltage><angle> LINEFEED

where <busname> is the bus name in (A8),
      <basekv> is the base kV in (F4.0),
      <voltage> is the actual voltage magnitude in kV in (I4), and
      <angle> is the angle in degrees in (I4).

It calls gtbsvolt.f with the following parameters.:

integer function gtbsvolt (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = BUS_VOLTAGES

GET_DATA, TYPE = COMMENTS

This command obtains case comments, along with case ID, project name, and headers.

There is a related command:

/PUT_DATA, TYPE = COMMENTS

which modifies the corresponding data except for header 1 which is not modifiable. Header 1 is formatted to include case name, case description, program version, date, etc. Up to 20 comments are returned. The three header records are always returned.

The returned values are encoded in the character array out_buffer in free field, C-formatted strings. The quantities enclosed in angle brackets “< … >” denote variables returned. Headers may be up to 130 characters; comments may be up to 120 characters, not including the H or C in column 1.:

/GET_DATA, TYPE = COMMENTS
CASE_ID = "< case name >"               10 chars
CASE_DS = "< case description >"        20 chars
H< header 1 information >
H< header 2 information >
H< header 3 information >
C< comment text >
...
C< comment text >
return status: status = 0 : success
                        1 : error

GET_DATA, TYPE = CONNECTION

This command retrieves network connection information for given buses. Its main usage is to draw the display network diagram. It calls gtconnect.f with the following parameters.:

integer function gtconnect (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = CONNECTION
B     <busname, etc> returns all connection data associated with bus
B     <busname, etc> returns all connection data associated with bus

The connection data is returned in out_buffer in the following format.:

B <busname><basekv> LINEFEED
L <busname><basekv> <busname><basekv> LINEFEED
T <busname><basekv> <busname><basekv> LINEFEED

Specifically,:

"B" records: (1:2) = "B "
             (3:14) = <bus1><base1>.
"L" records: (1:2) = "L "
             (3:14) = <bus1><basekv1>
             (16:27) = <bus2><base2>.
             (28:29) = <number of parallel circuits>
"T" records: (1:2) = "T "
             (3:14) = <bus1><basekv1>
             (16:27) = <bus2><base2>.
             (28:29) = <number of parallel circuits>

GET_DATA, TYPE = COUNT

This command computes the number of network data records that would be retrieved using a subsequent /GET_DATA,TYPE=NETWORK_DATA command using the same filter which is defined with this command. The output appears in a dialog field in the Network Data Edit Dialog of the GUI. It returns the count in out_buffer in the following format.:

count = cccccc

cccccc is the count in I6 format. This command calls gtcount.f with the following parameters.:

integer function gtcount (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains filter data in the following command.:

/GET_DATA, TYPE = COUNT [ FROM BUS_DATA ]
                  WHERE AREAS = <area1>, <area2>, etc AND
                  ZONES = <zone1>, <zone2>, etc AND
                  OWNERS = <own1>, <own2>, etc AND
                  BASEKV = base1
                           < base ( example < 115.0 means all base
                                  kv's less than or equal to 115.0)
                           > base ( example > 115.0 means all base
                                  kv's greater than or equal to 115.0)
                           base1 < base2 (all bases between base1 and
                                          base 2)
                           base2 > base1 (same as above)
                  TYPE = '* ', 'A*', 'A?', 'I ', 'B*', 'L*', 'B?',
                         'B ', 'BE', 'BS', 'BC', 'BD', 'BV', 'BQ',
                         'BG', 'BT', 'BX', 'BM', 'BF', '+ ', 'X ',
                         'Q ', 'LD', 'LM', 'E ', 'T ', 'TP', 'R ',
                         'RZ'
                  BUS = "<busname>" (quotes are necessary)
                  AFTER_BUS = "<busname>"
                  ALL
                  LOADING = (<min> <max>)

GET_DATA, TYPE = FILE_EXISTS

This command inquires whether a named file exists on the platform where ipvsrv is running. It calls ex_file.f with the following parameters.:

integer function ex_file (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = FILE_EXISTS, FILE = <file_name>

The return status is 0 if the bus exists, or 1 if it does not exist.

GET_DATA, TYPE = I_DATA

This command retrieves in out_buffer all type I records in WSCC format. It calls i_data.f with the following parameters.:

integer function i_data (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information:

/GET_DATA, TYPE = I_DATA

GET_DATA, TYPE = INITIALIZE_DEF

This command initializes the user analysis arrays. It should be called prior to a USER_ANALYSIS command. It calls p_initdef.f with the following parameters.:

integer function p_initdef (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = INITIALIZE_DEF

GET_DATA, TYPE = INPUT

This command retrieves the full network data given the identification of that record in WSCC format. If the record is type B, all data relevant to that bus is retrieved. It calls gtinput.f with the following parameters.:

integer function gtinput (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains WSCC-formatted records following the command /GET_DATA.:

/GET_DATA, TYPE = INPUT
A <areaname>
I <area1 area2>
B <busname, etc> returns all data associated with bus
+ <busname, etc> returns all data if id fields have wild cards
                 (type - column 2, owner, columns 3-5, and code-year
                 columns 20-21)
X <busname, etc>
L <bus1 bus2, etc> returns all parallels if id is wild card (*)
                   returns all sections if section is 0
T <bus1 bus2, etc>
R <bus1 bus2, etc>
E <bus1 bus2, etc>

The character array in_buffer is passed through p_gtdata.f to gtinput.f.

GET_DATA, TYPE = LINE_IMPEDANCE_CALCULATION

This command computes transmission line impedance data given tower geometry and conductor characteristics. It calls a stand-alone module p_lic.f and associated routines, which are completely separate from the powerflow data base. (It was added to ipfsrv to keep the GUI free from any FORTRAN modules.):

integer function p_lic (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information:

/GET_DATA, TYPE = LINE_IMPEDANCE_CALCULATION
           UNITS = < ENGLISH | METRIC >,
           DISTANCE = < miles | km >
           BASEKV = <basekv>,
           BASEMVA = <basemva>,
           FREQUENCY = <freq>
CONDUCTOR = 1 .3636 .05215 1.602 -20.75 50. 50. 0.0 0.0 0
CONDUCTOR = 1 .3636 .05215 1.602 -19.25 50. 50. 0.0 0.0 0
CONDUCTOR = 2 .3636 .05215 1.602 -0.75 77.5 77.5 0.0 0.0 0
CONDUCTOR = 2 .3636 .05215 1.602 0.75 77.5 77.5 0.0 0.0 0
CONDUCTOR = 3 .3636 .05215 1.602 19.25 50. 50. 0.0 0.0 0
CONDUCTOR = 3 .3636 .05215 1.602 20.75 50. 50. 0.0 0.0 0
CONDUCTOR = 0 .5 2.61 0.386 -12.9 98.5 98.5 0.0 0.0 0
CONDUCTOR = 0 .5 2.61 0.386 12.9 98.5 98.5 0.0 0.0 0

The returned line impedance data in character array out_buffer has the following format.:

LIC = <r> <x> <g/2> <b/2>

<r>, <x>, <g/2>, and <b/2> are the corresponding per unit line quantities encoded as F14.8 fields.

GET_DATA, TYPE = LOAD_AREA

This command initializes arrays associated with area interchange data. It should be called prior to any requests for area output. It calls ldardata.f with the following parameters,:

integer function ldardata (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = LOAD_AREA

GET_DATA, TYPE = LOAD_DEFINE

This command loads the user analysis arrays. It calls p_loaddef.f with the following parameters.:

integer function p_loaddef (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = LOAD_DEFINE
> DEFINE ...
> DEFINE ...
> DEFINE ...
C ...
C ...
C ...

GET_DATA, TYPE = LOAD_REF_AREA

This command initializes arrays associated with area interchange data using the data from the reference base case. Prior to this call, the reference base case should be loaded. It calls P_ldxardta.f with the following parameters.:

integer function p_ldxardta (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = LOAD_REF_AREA

GET_DATA, TYPE = LOAD_REF_BASE

This command loads a reference base case history file for the purpose of base case comparison or plot comparisons. The requested base case must be in the IPF format. It calls p_gtdata.f with the following parameters.:

integer function p_gtdata (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information:

/GET_DATA, TYPE = LOAD_REF_BASE, FILE = <file_name>

GET_DATA, TYPE = NETWORK_DATA

This command gets filtered network data records. The output appears in the scrollable edit list on the Network Data Edit Dialog in the GUI. This command calls gtnetdat.f with the following parameters.:

integer function gtnetdat (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains filter data in the following command.:

/GET_DATA, TYPE = NETWORK_DATA [ FROM BUS_DATA ]
                  WHERE AREAS = <area1>, <area2>, etc AND
                        ZONES = <zone1>, <zone2>, etc AND
                        OWNERS = <own1>, <own2>, etc AND
                        BASEKV = base1
                                 < base ( example < 115.0 means all base
                                        kv's less than or equal to 115.0)
                                 > base ( example > 115.0 means all base
                                        kv's greater than or equal to 115.0)
                                 base1 < base2 (all bases between base1 and
                                               base 2)
                                 base2 > base1 (same as above)
                        TYPE = '* ', 'A*', 'A?', 'I ', 'B*', 'L*', 'B?',
                               'B ', 'BE', 'BS', 'BC', 'BD', 'BV', 'BQ',
                               'BG', 'BT', 'BX', 'BM', 'BF', '+ ', 'X ',
                               'Q ', 'LD', 'LM', 'E ', 'T ', 'TP', 'R ',
                               'RZ'
                        BUS = "<busname>" (quotes are necessary)
                        AFTER_BUS = "<busname>"
                        ALL
                        LOADING = (<min> <max>)

Details of the filter are found in Dynamic Filters.

GET_DATA, TYPE = OUTAGES

This command retrieves the list of outaged data for the Report Dialog (under Bone Pile). It calls gtoutage.f with the following parameters.:

integer function gtoutage (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = OUTAGES

The returned outage data returned in character array out_buffer is WSCC-formatted network data that has been deleted.

GET_DATA, TYPE = OUTPUT

This command can access virtually the entire network data base. It calls gtoutput.f with the following parameters.:

integer function gtoutput (in_buffer, out_buffer)
parameter (MAXBUFFER = 6600)
character in_buffer * (MAXBUFFER)
character out_buffer * (MAXBUFFER)

The character array in_buffer contains the following information.:

/GET_DATA, TYPE = OUTPUT
A <areaname> returns all data associated with area
I <area1 area2> returns all intertie data between the areas
B <busname, etc> returns all data associated with bus
+ <busname, etc> returns all data if id fields have wild cards
                 (type - column 2, owner, columns 3-5, and code-year
                 columns 20-21)
X <busname, etc>
L <bus1 bus2, etc> returns all parallels if id is wild card (*)
                   returns all sections if section is wild card (0)
T <bus1 bus2, etc>
R <bus1 bus2, etc>
E <bus1 bus2, etc>

The returned values in out_buffer correspond with the input record in in_buffer.

Area A Record

Column

Format

Description

1

A1

A — Area Identifier

2

1X

Blank

3-12

A10

Area name

13

1X

Blank

14-28

E15.7

Total Area Generation (MW)

29-43

E15.7

Total Area Load (MW)

44-58

E15.7

Total Area Losses (MW)

59-73

E15.7

Net Area Export (MW)

AC Buses (Types B, BE, BS, BC, BD, BV, BQ, BG, BT, BX)

Column

Format

Description

1

A1

Bus code “B”

2

A1

Bus type (” “, “E”, “S”, “D”, etc.)

3

1X

(Not used)

4-6

A3

Ownership

7-14

A8

Bus name

15-18

F4.0

Bus base KV

19-20

A2

Zone

21-35

E15.7

P_gen (MW)

36-50

E15.7

Q_gen (MVAR)

51-65

E15.7

Voltage (KV)

66-80

E15.7

Angle (degrees)

81-95

E15.7

P_load (MW)

96-110

E15.7

Q_load (MVAR)

111-125

E15.7

B_shunt used (MVAR)

126-140

E15.7

B_shunt scheduled (MVAR)

141-155

E15.7

B_shunt (capacitors) used (MVAR)

156-170

E15.7

B_shunt (capacitors) scheduled (MVAR)

171-185

E15.7

B_shunt (reactors) used (MVAR)

186-200

E15.7

B_shunt (reactors) scheduled (MVAR)

201-215

E15.7

Q unscheduled (MVAR)

DC Buses (Type BD and BM)

Column

Format

Description

1

A1

Bus code “B”

2

A1

Bus type (“D” or “M”)

3

1X

(Not used)

4-6

A3

Ownership

7-14

A8

Bus name

15-18

F4.0

Bus base KV

19-20

A2

Zone

21-35

E15.7

P_d-c (MW)

36-50

E15.7

Q_d-c (MVAR)

51-65

E15.7

D_C Voltage (KV)

66-80

E15.7

Converter angle (degrees)

81-95

E15.7

P_valve losses (MW)

96-110

E15.7

Q_valve losses (MVAR)

2-6 5X (Not used) 4-6 A3 Ownership 7-14 A8 Bus name 15-18 F4.0 Bus base KV 19-20 2X (not used) 21 I1 Group No. 1 scheduled units 22 I1 Group No. 1 used units 23-37 E15.7 Group No. 1 reactance (MVAR) / unit 38 I1 Group No. 2 scheduled units 39 I1 Group No. 2 used units 40-54 E15.7 Group No. 2 reactance (MVAR) / unit 55 I1 Group No. 3 scheduled units 56 I1 Group No. 3 used units 57-71 E15.7 Group No.3 reactance (MVAR) / unit 72 I1 Group No. 4 scheduled units 73 I1 Group No. 4 used units 74-88 E15.7 Group No. 4 reactance (MVAR) / unit 89 I1 Group No. 5 scheduled units 90 I1 Group No.5 used units 91-105 E15.7 Group No. 5 reactance (MVAR) / unit 106 I1 Group No. 6 scheduled units 107 I1 Group No. 6 used units 108-122 E15.7 Group No. 6 reactance (MVAR) / unit 123 I1 Group No. 7 scheduled units 124 I1 Group No. 7 scheduled units 125-139 E15.7 Group No. 7 reactance (MVAR) / unit 140 I1 Group No. 8 scheduled units 141 I1 Group No. 8 used units 142-156 E15.7 Group No. 8 reactance (MVAR) / unit

2 A1 Continuation bus subtype (A,C,F,I,N,P,S) 3 1X (Not used) 4-6 A3 Ownership 7-14 A8 Bus name 15-18 F4.0 Bus base KV 19-20 A2 Classification code year, * I — constant current loads, * Z — constant impedance loads, * P — constant MVA loads, 21-35 E15.7 P_gen (MW) 36-50 E15.7 Q_gen (MVAR) 51-65 E15.7 P_load (MW) 66-80 E15.7 Q_load(MVAR) 81-95 E15.7 G_shunt (MW) 96-110 E15.7 B_shunt (MVAR)

2 A1 Line subtype (LD, LM, or TP) 3 1X (Not used) 4-6 A3 Ownership 7-14 A8 Bus1 name 15-18 F4.0 Bus1 base KV 19 I1 Interchange metering point (0, 1, or 2) 20-27 A8 Bus 2 name 28-31 F4.0 Bus 2 base KV 32 A1 Parallel ID ( * (asterisk) means all parallels) 33 I1 Number of circuits 34-48 E15.7 P_in (MW) 49-63 E15.7 Q_in (MVAR) 64-78 E15.7 P_out (MW) 79-93 E15.7 Q_out (MVAR) 94-108 E15.7 P_loss (MW) 109-123 E15.7 Q_loss (MW) 124-138 E15.7 Critical line loading (amps) 139-146 F8.1 Critical line rating (amps) 147 A1 Critical line rating code (N,T,B) 148 I1 Critical line loading terminal (0,1,2) 149-163 E15.7 Critical transformer loading (MVA) 164-171 F8.1 Critical transformer rating (MVA) 172 A1 Critical transformer rating code (N,T,E,B) 173 I1 Critical transformer loading terminal (0,1,2) 174-188 E15.7 Total Line loading (percent) 189-203 E15.7 Total Line loading (amps) 204-218 E15.7 Total Transformer loading (percent) 219-233 E15.7 Total Transformer loading (MVA) 234-241 F8.2 Tap1 in kV (Type T or TP) or %Compensation (L or E.) 242-249 F8.2 Tap2 in kV 250-256 A7 (Reserved for difference plotting)

GET_DATA, TYPE = OWNER_LIST

This command loads the ownership list dialog in the Reports Dialog and in the Network Data Edit Dialog of the GUI. It returns in out_buffer the list of filtered ownership names in the following format. <ownership>LINEFEED <ownership> is the ownership name in A3 format. It calls owner_list.f with the following parameters. integer function owner_list (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) The character array in_buffer contains optional filter data in the following command. /GET_DATA, TYPE = OWNER_LIST [ FROM BUS_DATA ]

WHERE AREAS = <area1>, <area2>, etc AND ZONES = <zone1>, <zone2>, etc AND OWNERS = <own1>, <own2>, etc AND BASEKV = base1 < base ( example < 115.0 means all base kv’s less than or equal to 115.0) > base ( example > 115.0 means all base kv’s greater than or equal to 115.0) base1 < base2 (all bases between base1 and base 2) base2 > base1 (same as above) TYPE = ’* ’, ’A*’, ’A?’, ’I ’, ’B*’, ’L*’, ’B?’,

’B ’, ’BE’, ’BS’, ’BC’, ’BD’, ’BV’, ’BQ’,

’BG’, ’BT’, ’BX’, ’BM’, ’BF’, ’+ ’, ’X ’, ’Q ’, ’LD’, ’LM’, ’E ’, ’T ’, ’TP’, ’R ’, ’RZ’ BUS = “<busname>” (quotes are necessary) AFTER_BUS = “<busname>” ALL LOADING = (<min> <max>)

Details of the filter are found in Dynamic Filters.

GET_DATA, TYPE = RECORD_LIST

This command loads the record type list dialog in the Reports Dialog and in the Network Data Edit Dialogof the GUI. It returns in out_buffer the hard-coded list of various record type codes in the following format. <record_type>LINEFEED <record_type> is the record type code in A2 format. This command calls type_list.f with the following parameters. integer function type_list (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) The character array in_buffer contains optional filter data in the following command. /GET_DATA, TYPE = RECORD_LIST [ FROM BUS_DATA ]

WHERE AREAS = <area1>, <area2>, etc AND ZONES = <zone1>, <zone2>, etc AND OWNERS = <own1>, <own2>, etc AND BASEKV = base1 < base ( example < 115.0 means all base kv’s less than or equal to 115.0) > base ( example > 115.0 means all base kv’s greater than or equal to 115.0) base1 < base2 (all bases between base1 and base 2) base2 > base1 (same as above) TYPE = ’* ’, ’A*’, ’A?’, ’I ’, ’B*’, ’L*’, ’B?’,

’B ’, ’BE’, ’BS’, ’BC’, ’BD’, ’BV’, ’BQ’,

’BG’, ’BT’, ’BX’, ’BM’, ’BF’, ’+ ’, ’X ’, ’Q ’, ’LD’, ’LM’, ’E ’, ’T ’, ’TP’, ’R ’, ’RZ’ BUS = “<busname>” (quotes are necessary) AFTER_BUS = “<busname>” ALL LOADING = (<min> <max>)

In this instance only, the filter has no impact upon the contents of the returned data. Details of the filter are found in the IPF Basic User’s Guide under the section on “Dynamic Filters.” GET_DATA, TYPE = REF_AREA_DATA This command obtains the area interchange output data from the WSCC-formatted input area records using the reference base case data. This command should be preceded with a prior command GET_AREA, TYPE=LOAD_REF_AREA. It calls p_gtxardta.f with the following parameters. integer function p_gtxardta (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) The character array in_buffer contains the following information. /GET_DATA, TYPE = AREA_REF_DATA A <areaname>

GET_DATA, TYPE = REF_OUTPUT This command can access virtually the entire network data from the reference base. It calls gtaltopt.f with the following parameters. integer function gtaltopt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) The character array in_buffer contains the following information. /GET_DATA, TYPE = OUTPUT A <areaname> returns all data associated with area I <area1 area2> returns all interties between the two areas B <busname, etc> returns all data associated with bus + <busname, etc> returns all data if id fields have wild cards

(type - column 2, owner, columns 3-5, and code-year columns 20-21)

X <busname, etc> L <bus1 bus2, etc> returns all parallels if id is wild card (*)

returns all sections if section is wild card (0)

T <bus1 bus2, etc> R <bus1 bus2, etc> E <bus1 bus2, etc> The returned values in out_buffer correspond with the input record in in_buffer.

2 1X Blank 3-12 A10 Area name 13 1X Blank 14-28 E15.7 Total Area Generation (MW) 29-43 E15.7 Total Area Load (MW) 44-58 E15.7 Total Area Losses (MW) 59-73 E15.7 Net Area Export (MW)

2 1X Blank 3-12 A10 Area 1 name 13 1X Blank 14-23 A10 Area 2 name 24 1X Blank 25-39 E15.7 Scheduled Area1-Area2 Export (MW) 40-54 E15.7 Actual Area1-Area2 Export (MW) 55-69 E15.7 “Circulating” Flow (MW) 70 1X Blank 71 I1 0 — No Area1-Area2 I record exists 1 — Area1-Area2 I record exists

2 A1 Bus type 3 1X (Not used) 4-6 A3 Ownership 7-14 A8 Bus name 15-18 F4.0 Bus base KV 19-20 A2 Zone 21-35 E15.7 P_gen (MW) 36-50 E15.7 Q_gen (MVAR) 51-65 E15.7 Voltage (KV)) 66-80 E15.7 Angle (degrees) 81-95 E15.7 P_load (MW) 96-110 E15.7 Q_load (MVAR) 111-125 E15.7 B_shunt used (MVAR) 126-140 E15.7 B_shunt scheduled (MVAR) 141-155 E15.7 B_shunt (capacitors) used (MVAR) 156-170 E15.7 B_shunt (capacitors) scheduled (MVAR) 171-185 E15.7 B_shunt (reactors) used (MVAR) 186-200 E15.7 B_shunt (reactors) scheduled (MVAR) 201-215 E15.7 Q unscheduled (MVAR)

2 A1 Bus type (“D” or “M)” 3 1X (Not used) 4-6 A3 Ownership 7-14 A8 Bus name 15-18 F4.0 Bus base KV 19-20 A2 Zone 21-35 E15.7 P_d-c (MW) 36-50 E15.7 Q_d-c (MVAR) 51-65 E15.7 D_C Voltage (KV) 66-80 E15.7 Converter angle (degrees) 81-95 E15.7 P_valve losses (MW) 96-110 E15.7 Q_valve losses (MVAR)

2-6 5X (Not used) 4-6 A3 Ownership 7-14 A8 Bus name 15-18 F4.0 Bus base kV 19-20 2X (not used) 21 I1 Group No. 1 scheduled units 22 I1 Group No. 1 used units 23-37 E15.7 Group No. 1 reactance (MVAR) / unit 38 I1 Group No. 2 scheduled units 39 I1 Group No. 2 used units 40-54 E15.7 Group No. 2 reactance (MVAR) / unit 55 I1 Group No. 3 scheduled units 56 I1 Group No. 3 used units 57-71 E15.7 Group No.3 reactance (MVAR) / unit 72 I1 Group No. 4 scheduled units 73 I1 Group No. 4 used units 74-88 E15.7 Group No. 4 reactance (MVAR) / unit 89 I1 Group No. 5 scheduled units 90 I1 Group No.5 used units 91-105 E15.7 Group No. 5 reactance (MVAR) / unit 106 I1 Group No. 6 scheduled units 107 I1 Group No. 6 used units 108-122 E15.7 Group No. 6 reactance (MVAR) / unit 123 I1 Group No. 7 scheduled units 124 I1 Group No. 7 scheduled units 125-139 E15.7 Group No. 7 reactance (MVAR) / unit 91 I1 Group No. 8 scheduled units 92 I1 Group No. 8 used units 93-100 E15.7 Group No. 8 reactance (MVAR) / unit

2 A1 Continuation bus subtype (A,C,F,I,N,P,S) 3 1X (Not used) 4-6 A3 Ownership 7-14 A8 Bus name 15-18 F4.0 Bus base KV 19-20 A2 Classification code year, *I — constant current loads, *Z — constant impedance loads, *P — constant MVA loads, 21-35 E15.7 P_gen (MW) 36-50 E15.7 Q_gen (MVAR) 51-65 E15.7 P_load (MW) 66-80 E15.7 Q_load(MVAR) 81-95 E15.7 G_shunt (MW) 96-110 E15.7 B_shunt (MVAR)

2 A1 Line subtype (LD, LM, or TP) 3 1X (Not used) 4-6 A3 Ownership 7-14 A8 Bus1 name 15-18 F4.0 Bus1 base KV 19 I1 Interchange metering point (0, 1, or 2) 20-27 A8 Bus 2 name 28-31 F4.0 Bus 2 base KV 32 A1 Parallel ID ( * (asterisk) means all parallels) 33 I1 Number of circuits 34-48 E15.7 P_in (MW) 49-63 E15.7 Q_in (MVAR) 64-78 E15.7 P_out (MW) 79-93 E15.7 Q_out (MVAR) 94-108 E15.7 P_loss (MW) 109-123 E15.7 Q_loss (MW) 124-138 E15.7 Critical line loading (amps) 139-146 F8.1 Critical line rating (amps) 147 A1 Critical line rating code (N,T,B) 148 I1 Critical line loading terminal (0,1,2) 149-163 E15.7 Critical transformer loading (MVA) 164-171 F8.1 Critical transformer rating (MVA) 172 A1 Critical transformer rating code (N,T,E,B) 173 I1 Critical transformer loading terminal (0,1,2) 174-188 E15.7 Total Line loading (percent) 189-203 E15.7 Total Line loading (amps) 204-218 E15.7 Total Transformer loading (percent) 219-233 E15.7 Total Transformer loading (MVA) 234-241 F8.2 Tap1 in kV (Type T or TP) or %Compensation (L or E.) 242-249 F8.2 Tap2 in kV 250-256 A7 (Reserved for difference plotting)

GET_DATA, TYPE = SOL_PAR This command obtains solution tolerances, controls, or switches that influence the processing of the case in residence. The obtained system data is identical to the set of data modified by the related command /SOLUTION. The returned values are encoded in the character array in_buffer in free field, C-formatted strings. The quantities enclosed in angle brackets “< … >” denote variables quantitied; < status > denotes a logical on or off; < value > denotes an integer, floating point, or character quantity. /GET_DATA, TYPE = SOL_PAR, > AI_CONTROL = < value > { CON | MOD | OFF } > BASE_SOLUTION = < status > > DEBUG_TX = < status > > DEBUG_BUS = < status > > DEBUG_AI = < status > > DEBUG_DC = < status > > LIMITS_QRES = < value > > LIMITS_PHA = < value > > LIMITS_DA = < value > > LIMITS_DV = < value > > LTC = < value> { ON | ON_NV | ON_NPS | OFF | ON_DCONLY } > MISC_XBUS = < value > { BPA | VMAX | WSCC } > MISC_DCLP = < status > > MISC_VFLAT = < status > > MISC_TSTART = < value > > MISC_ITER_SUM = < status > > MISC_PHA_SHIFT_BIAS = < value > { BPA | WSCC } > SOL_ITER_DECOUP = < value > > SOL_ITER_NEWTON = < value > > TOL_BUSV = < value > > TOL_AIPOWER = < value > > TOL_TX = < value > > TOL_Q = < value > return status: status = 0 : success 1 : errors GET_DATA, TYPE = SUB_DEFINE This command performs character string substitution using computed base case quantities upon the tokens defined with the >DEFINE statement within comment records in the USER_ANALYSIS command. It calls p_subdef.f with the following parameters. integer function p_subdef (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) The character array in_buffer contains the following information. /GET_DATA, TYPE = SUB_DEFINE, SOURCE = BASE

ALTERNATE_BASE

GET_DATA, TYPE = STATUS This command retrieves the case description. It calls gtstatus.f with the following parameters. integer function gtstatus out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) The character array in_buffer contains the following information. /GET_DATA, TYPE = STATUS The character array out_buffer contains the following information. c c Program: <n> version <n> date <n> c Program size: max buses <n> max branches c Case: <name> status <n> base file <n> c <n> buses <n> branches <n> areas <n> d-c lines c <n> changes c c comments c c comments c c comments c

GET_DATA, TYPE = SYSTEM This command obtains system-specific information pertaining to parameters which describe general characteristics of the base case in residence. The returned values are encoded in the character array out_buffer in free field, C-formatted strings. The quantities enclosed in angle brackets “< … >” denote variables returned; < status > denotes a logical on or off and < value > denotes an integer or floating point quantity. /GET_DATA, TYPE = SYSTEM, CASE_DT = < case date > OLD_BASE = < file name > NEW_BASE = < file name > OLD_NETD = < file name > NEW_NETD = < file name > OLD_CHGF = < file name > NEW_CHGF = < file name > PRG_VERS = < program version > BASE_MVA = < base MVA > NUM_DC_SYS = < number of DC systems > NUM_AREA = < number of areas> NUM_ITIE = < number of interties> NUM_ZONE = < number of zones> NUM_OWN = < number of owners> NUM_BUS = < number of buses > NUM_AREA_SBUS = < number of area slack buses> NUM_DC_BUS = < number of DC buses > NUM_AGC_BUS = < number of AGC buses> NUM_BX_BUS = < number of BX buses> NUM_ADJ_BUS = < number of adjustable buses > NUM_PCT_VAR_BUS = < number of % VAR controlled buses > NUM_BRN = < number of branch records> NUM_CKT = < number of circuits > NUM_DC_LINE = < number of DC lines > NUM_LTC = < number of LTC transformers > NUM_PHAS = < number of phase shifters > SOLN_STATUS = < solution status > NUM_KV = < number of different KVs > NUM_REC_TYP = < number of record types > return status: status = 0 : success 1 : errors GET_DATA, TYPE = ZONE_LIST This command loads the zone list dialog in the Reports Dialog and the Network Data Edit Dialog. See the IPF Basic User’s Guide. It returns in out_buffer the list of filtered zones in the following format. <zone>LINEFEED

<zone> is the zone name in A2 format. It calls zone_list.f with the following parameters. integer function zone_list (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) The character array in_buffer contains optional filter data in the following command. /GET_DATA, TYPE = ZONE_LIST [ FROM BUS_DATA ]

WHERE AREAS = <area1>, <area2>, etc AND ZONES = <zone1>, <zone2>, etc AND OWNERS = <own1>, <own2>, etc AND BASEKV = base1 < base ( example < 115.0 means all base kv’s less than or equal to 115.0) > base ( example > 115.0 means all base kv’s greater than or equal to 115.0) base1 < base2 (all bases between base1 and base 2) base2 > base1 (same as above) TYPE = ’* ’, ’A*’, ’A?’, ’I ’, ’B*’, ’L*’, ’B?’,

’B ’, ’BE’, ’BS’, ’BC’, ’BD’, ’BV’, ’BQ’,

’BG’, ’BT’, ’BX’, ’BM’, ’BF’, ’+ ’, ’X ’, ’Q ’, ’LD’, ’LM’, ’E ’, ’T ’, ’TP’, ’R ’, ’RZ’ BUS = “<busname>” (quotes are necessary) AFTER_BUS = “<busname>” ALL LOADING = (<min> <max>)

Details of the filter are found in the IPF Basic User’s Guide under the section on “Dynamic Filters.”

PUT_DATA

PUT_DATA, TYPE = COMMENTS This command replaces case comments, along with caseid, case description, and headers. There is a related command

/GET_DATA, TYPE = COMMENTS

which obtains the corresponding data including header 1 which is not modifiable. Header 1 is formatted to include case name, case description, program version, date, etc. Up to 20 comments are allowed. The two header records must be present even if blank. For all blank “H” or “C” records (blank “C” records are accepted, but optional) include at least one blank character after the “H” or “C”. The sent values are encoded in the character array out_buffer in free field, C-formatted strings. The quantities enclosed in angle brackets “< … >” denote variables. Headers may be up to 130 characters; comments may be up to 120 characters, not including the “H” or “C” in column 1. /PUT_DATA, TYPE = COMMENTS CASE_ID = “< case name >” 10 chars CASE_DS = “< case description >” 20 chars H< header 2 information > H< header 3 information > C< comment text > … C< comment text >

Report Generation

The /REPORTS command with its many different forms fetches data from the Powerflow process for display in the Reports Dialog. It calls p_report.f with the following parameters. integer function p_report (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) The character array in_buffer contains any of the following commands. /REPORTS, SELECT AI_SUMMARY /REPORTS, SELECT BUS_INPUT /REPORTS, SELECT BUS_BR_INPUT /REPORTS, SELECT BUS_BR_OUTPUT /REPORTS, SELECT BUS_UVOV /REPORTS, SELECT LINE_COMPARISON /REPORTS, SELECT NETWORK_CHANGES /REPORTS, SELECT NETWORK_DELETIONS /REPORTS, SELECT OVERLOADED_LINES /REPORTS, SELECT OVERLOADED_TXS /REPORTS, SELECT PHASE_SHIFTER /REPORTS, SELECT TIE_LINE_SUMMARY /REPORTS, SELECT VOLTAGE_COMPARISON The routine p_report.f parses these command and calls a subroutine to perform the specific task. The modules are listed below.

REPORTS, SELECT AI_SUMMARY

This command retrieves filtered area interchange output data. It calls areaintrpt.f with the following parameters. integer function areaintrpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string AI_SUMMARY. The character array in_buffer contains the following information. /REPORTS, SELECT AI_SUMMARY

[ OUTPUT = <filename> ]

The output is placed in out_buffer. The report dialog is shown below.

_images/Area_Interchange_Summary_Report_Dialog.png

Area Interchange Summary Report Dialog

REPORTS, SELECT BUS_INPUT

This command retrieves filtered WSCC-formatted bus input data records. It calls businrpt.f with the following parameters. integer function businrpt(in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string BUS_INPUT. The character array in_buffer contains the following information. /REPORTS, SELECT BUS_INPUT [ FROM BUS_DATA ]

[ OUTPUT = <filename> ] WHERE (repeat filter from BUS_LIST)

The output is placed in out_buffer. The report dialog is shown below.

_images/Bus_Input_Data_Report_Example.png

Bus Input Data Report Dialog

REPORTS, SELECT BUS_BR_INPUT

This command retrieves filtered WSCC-formatted bus and branch input data records. It calls busbrinrpt.f with the following parameters. integer function busbrinrpt(in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string BUS_BR_INPUT. The character array in_buffer contains the following information. /REPORTS, SELECT BUS_BR_INPUT [ FROM BUS_DATA ]

[ OUTPUT = <filename> ] WHERE (repeat filter from BUS_LIST)

The output is placed in out_buffer. The report dialog is shown below.

_images/Bus_Branch_Input_Example2.png

Bus Branch Input Report Dialog

REPORTS, SELECT BUS_BR_OUTPUT

This command retrieves filtered bus and branch output records. It calls busbrotrpt.f with the following parameters. integer function busbrotrpt(in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string BUS_BR_OUTPUT. The character array in_buffer contains the following information. /REPORTS, SELECT BUS_BR_OUTPUT [ FROM BUS_DATA ]

[ OUTPUT = <filename> ] WHERE (repeat filter from BUS_LIST)

The output is placed in out_buffer.The report dialog is shown below.

_images/Bus_Branch_Output_Example2.png

Bus Branch Output Report Dialog

REPORTS, SELECT BUS_UVOV

This command retrieves filtered under/over voltage bus output data. It calls busuvovrpt.f with the following parameters. integer function busuvovrpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer positioned to the first character following the string BUS_UVOV. The character array in_buffer contains the following information. /REPORTS, SELECT BUS_UVOV [ FROM BUS_DATA ]

[ OUTPUT = <filename> ] WHERE (repeat filter from BUS_LIST)

The output is placed in out_buffer.The report dialog is shown below.

img/Overvoltage_Undervoltage_Report_Dialog.png.png

Overvoltage Undervoltage Report Dialog

REPORTS, SELECT LINE_COMPARISON

This command retrieves filtered line loading differences between the base case in residence and a selected base case history data file. It calls lfodifrpt.f with the following parameters. (Not currently working.) integer function lfodifrpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string LINE_COMPARISON. The character array in_buffer contains the following information. /REPORTS, SELECT LINE_COMPARISON

[ OUTPUT = <filename> ] FILE = <filename> WHERE (repeat filter from BUS_LIST)

The output is placed in out_buffer.

REPORTS, SELECT NETWORK_CHANGES

This command retrieves the list of all accumulated changes performed on the base case in residence. It calls chglisrpt.f with the following parameters. integer function chglilsrpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string NETWORK_CHANGES. The character array in_buffer contains the following information. /REPORTS, SELECT NETWORK_CHANGES

[ OUTPUT = <filename> ]

The output is placed in out_buffer.The report dialog is shown below.

_images/Network_Changes_Report_Dialog.png

Network Changes Remote Dialog

REPORTS, SELECT NETWORK_DELETIONS

This command retrieves the list of all deleted network data in WSCC format. It calls deleterpt.f with the following parameters. integer function deleterpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string NETWORK_DELETIONS. The character array in_buffer contains the following information. /REPORTS, SELECT NETWORK_DELETIONS

[ OUTPUT = <filename> ]

The output is placed in out_buffer.The report dialog is shown below. (This is the report accessed under Bone Pile.)

_images/Bonepile_Output_Report_Dialog.png

Bonepile Output Report Dialog

REPORTS, SELECT OVERLOADED_LINES

This command retrieves filtered overloaded branch output data. It calls ovldlnsrpt.f with the following parameters. integer function ovldlnsrpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer positioned to the first character following the string OVERLOADED_LINES. The character array in_buffer contains the following information. /REPORTS, SELECT OVERLOADED_LINES [ FROM BUS_DATA ]

[ OUTPUT = <filename> ] WHERE (repeat filter from BUS_LIST)

The output is placed in out_buffer.The report dialog is shown below.

_images/Overvoltage_Lines_Report_Dialog.png

Overvoltage Lines Report Dialog

REPORTS, SELECT OVERLOADED_TXS

This command retrieves filtered overloaded transformer output data. It calls ovldtxsrpt.f with the following parameters. integer function ovldtxsrpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string OVERLOADED_TXS. The character array in_buffer contains the following information. /REPORTS, SELECT OVERLOADED_TXS [ FROM BUS_DATA ]

[ OUTPUT = <filename> ] WHERE (repeat filter from BUS_LIST)

The output is placed in out_buffer.The report dialog is shown below

_images/Overloaded_Transformers_Report_Dialog.png

Overloaded Transformers Report Dialog

REPORTS, SELECT PHASE_SHIFTER

This command retrieves the phase shifter report. It calls phshftrpt.f with the following parameters. integer function phshftrpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string PHASE_SHIFTER The character array in_buffer contains the following information. /REPORTS, SELECT PHASE_SHIFTER

[ OUTPUT = <filename> ]

The output is placed in out_buffer.The report dialog is shown below.

_images/Phase_Shifter_Report_Dialog.png

Phase Shifter Report Dialog

REPORTS, SELECT TIE_LINE_SUMMARY

This command retrieves filtered area tie line flows. It calls inttierpt.f with the following parameters. integer function inttierpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string TIE_LINE_SUMMARY. The character array in_buffer contains the following information. /REPORTS, SELECT TIE_LINE_SUMMARY

[ OUTPUT = <filename> ] WHERE (repeat filter from BUS_LIST)

The output is placed in out_buffer.The report dialog is shown below.

_images/Tie_Line_Summary_Report_Example2.png

Tie Line Summary Report Dialog

REPORTS, SELECT VOLTAGE_COMPARISON

This command retrieves filtered voltage differences between the base case in residence and a selected base case history data file. It calls vltdifrpt.f with the following parameters. (Not currently working.) integer function vltdifrpt (in_buffer, out_buffer) parameter (MAXBUFFER = 6600) character in_buffer * (MAXBUFFER) character out_buffer * (MAXBUFFER) in_buffer is positioned to the first character following the string VOLTAGE_COMPARISON. The character array in_buffer contains the following information. /REPORTS, SELECT VOLTAGE_COMPARISON

[ OUTPUT = <filename> ] FILE = <filename> WHERE (repeat filter from BUS_LIST)

The output is placed in out_buffer.

Command Line Tools

bpf

Command line interface that performs power flow. It executes using commands from a Power Flow Control (PFC) file. Example usage: bpf bench.pfc. The PFC commands (.pfc) used with bpf allow for complete power flow runs including defining the network model and commands to perform various operations such as evaluating outages. The Record Formats section describes the network model records available and the Power Flow Control (PFC) section describes the PFC syntax and commands available.

In order to process a case, bpf requires a program control file and a valid set of base case data, which may be a composite of NETWORK_DATA and BRANCH_DATA formatted ASCII files or an OLD_BASE file from a previous run of bpf, and a CHANGE file.

The PFC file either contains data used for the solution, or names files containing such data. The solution data is optionally saved on the file named in the NEW_BASE command.

Types of Processing

Input files used vary with the type of IPF processing, so it is important that you have a good understanding of the purpose of each type of file. Different program functions use the files to perform specific processes. Some major processes are:

  • Basic Processing (POWER FLOW)

  • Merge Base /MERGE_BASE

  • Network Reduction /REDUCTION

  • Outage Simulation /OUTAGE_SIM

Sample PFC file setups for each of the following solution processes are given in ??.

Creating a New Base Case

The figure below depicts the initial way an IPF case is processed and how the output is saved on a NEW_BASE file, which may then become an OLD_BASE file for subsequent change studies. The contents of the print file (PFO) are defined by the P_INPUT, P_OUTPUT, and P_ANALYSIS commands. Likewise, the contents of the fiche file (PFF) are defined by the F_INPUT, F_OUTPUT, and F_ANALYSIS commands.

_images/New_Base_Creation_Process.png

New Base Creation Process

Changing an Old Base Case

The figure below shows the most commonly used bpf process. A change case is created from an OLD_BASE file using a CHANGE file. The modified case data is saved on the NEW_BASE file. The output files PFO and PFF can be printed to paper or fiche or both.

_images/Old_Base_Case_With_Changes.png

Old Base Case With Changes

Merging Subsystems

The figure below shows a NEW_BASE file being created by merging a subsystem from a case on an OLD_BASE file with another subsystem from either a second OLD_BASE or from a BRANCH_DATA and a NETWORK_DATA file. The output files PFO and PFF can be printed to paper and/or fiche.

_images/Merging_Two_or_More_Subsystems.png

Merging Two or More Subsystems

Reducing a Network

In the figure below, a network reduction is specified in the PFC file. Commands within this file define the retained system. The actual network reduction dynamically changes the base data in memory, and the reduced base case is saved on the NEW_BASE file. These output files (.PFO and .PFF) can be printed to paper and/or fiche.

_images/Reducing_a_Network.png

Reducing a Network

For static reduction, you can use the ipfcut program. It is described in ??.

Simulating Outages

The figure below shows an outage simulation being processed directly from an OLD_BASE file. Only printed analysis is output; no data files are generated. This printed output can be directed to either fiche or paper. Simulating outages is a special power flow function that subjects a subsystem of interest to a series of single contingency branch outages and tabulates the consequences of each outage or the cause of each overload.

_images/An_Outage_Simulation.png

An Outage Simulation

ipf_reports

ipf_reports is a command line tool that can be used to get information on an existing base case (.bse) file.

ipfplot

ipfplot is a batch plotting program to produce printed maps. The program accepts a coordinate file (.cor) and a base case file (.bse) on the command line, as well as an optional second base case file. When the second base case file is specified, a difference plot is produced. You can also use IPFPLOT to produce bubble diagrams. The same coordinate files are used for both GUI and IPFPLOT, but not all capabilities are available in the GUI.

netdat

netdat is a command line program that converts a binary base file (.bse) created by bpf to an ASCII network data file. It provides similar function to ipfnet, but ipfnet generates a network data file based on the currently loaded case in the GUI, rather than from a .bse file.

ipfcut

ipfcut is a command line program that cuts out a subsystem from a solved base case file. The full system resides in a base case file; the cut system is a card image Bus/Branch data file. Flows at the cut branches are converted into equivalent generation or load on specially formatted +A continuation bus records. An ensuing power flow run should solve with internal branch flows and bus voltages which are identical to those quantities in the original base case.

  • Several methods are available to define the cut system: specifying individual buses, zones, base kVs, or individual branches.

  • A pi-back feature replaces selected buses with a passive-node sequence (lines consisting of sections) with the original loads, generation, and shunts, pi-backed in proportion to the line admittances.

The function of CUTTING and REDUCTION are similar, but their methodologies are different. Both generate subsystems whose internal composition and characteristics are identical to that of the base case. REDUCTION generates equivalent branches, shunt admittances, and injections such that internal nodes still “see” the full system. CUTTING generates equivalent shunt admittances and injections such that internal nodes can determine that the boundary has changed and the external system has been cut out, even though the internal flows and nodal voltages are identical.

The CUTTING program mandates that the flow into the cut-out system is constant. This is valid for eliminating radial feeder circuits, but not for eliminating a strongly interconnected external network. In the latter case, REDUCTION yields a more responsive equivalent.

A simple criterion can be used to determine whether CUTTING or REDUCTION is more appropriate.

  • Will a line outage or other major perturbation near the boundary of the retained subsystem and eliminated system significantly alter the flow between the two systems?

If the answer is no, the flow will not be significantly altered, then CUTTING is acceptable. (It is the author’s opinion that REDUCTION is always superior.)

The CUTTING program is initiated by entering ipfcut at the keyboard after the computer displays the system prompt.

From this point on the operation is interactive. You should respond to the questions as they are asked.

Cutting Methodologies

Two simple techniques are employed. Both may be used.

  • Cutting the eliminated branches. In cutting, the active and reactive power flowing into a cut branch is replaced with an equivalent but fictitious load, which is appended to the terminal bus with continuation buses (+A).

  • Pi-backing loads of retained buses. In pi-back, the loads and shunt susceptances on selected pi-back buses are distributed to neighboring terminal buses in proportion to their branch admittances. Only branch transfer susceptance is used (a good approximation when X >> R). Also, the pi-back bus may contain at most two branches. This corresponds with early reduction schemes. The quantities pi-backed are appended to the terminal buses on specially coded continuation cards (+A ***).

Input Commands

The syntax of CUT commands conform to the convention that has been adopted for the other IPF programs that use commands.

[FICHE, copies=n]
(CUTTING, Project=name, case ID=name)

The qualifiers that select the subsystem and enable special options are listed below:

>DEBUG<
>EXCLUDE_BUSES<
>INCLUDE_BUSES<
>PI_BACK_BUSES<
>SAVE_BUSES...<
>CUT_BRANCHES<
>SAVE_ZONES...,SAVE_BUSES...<
>WSCC<

>WSCC< Enables the WSCC option. The default is no WSCC. Special processing is effected with this option:

  1. Active power flowing from a cut branch into a bus is treated as a bus load under the WSCC option. Otherwise, it is treated as a load or generation depending upon the sign of the quantity.

  2. Base kV fields omit the decimal point without the WSCC option. For example, a 115.0 KV appears as “115”. Under the WSCC option, the same field appears as “115.”. The WSCC Powerflow program interprets the base fields as character instead of decimal, and those two fields are unique! Lane 115. is in New Mexico but LANE 115 is in Oregon!

  3. Line sections created from pi-back are consolidated into a single equivalent pi branch with the WSCC option enabled. Otherwise, the branch records are preserved (with the necessary name changes). There is one exception: If a step-up/step-down transformer-line transformer occurs, the branch is unconditionally made into an equivalent section.

  4. Any branch in the cut list that has an INT in the ownership field has its flow transferred to a +A INT continuation bus instead of a +A *** bus.

>DEBUG< Opens the program debug file. Output appears on a file with extension .pfd. This is used only by the program developers.

>SAVE_ZONES...,SAVE_BUSES...< Defines the retained network as all buses whose bases and zones both match the specified list. If SAVE_BUSES is null or omitted, only zones are considered. Continuation cards begin with a + in column 1.

For example: >SAVE_ZONES NA,NB,NC,ND,NE,NF,NG,NH, NI,NJ,NK,RM<

Any number of >SAVE_ZONE...SAVE_BASE< commands may be submitted. >SAVE_BASES...< defines the retained network as all bases whose buses match the specified list. It is not necessary to type a decimal part unless it is part of the base kV, for example, 13.8 but not 3.46. Continuation cards begin with a + in column 1.

The system is initialized as an eliminated network. The following commands define the composition of the retained system. With the exception of

>CUT_BRANCHES<, the effect of the commands may be repeated in any order. Their effects are overlaid.

>INCLUDE_BUSES< >EXCLUDE_BUSES< >SAVE_BUSES< These commands introduce buses that are specified on bus records that follow (B in column 1). >SAVE_BUSES is used to specify the entire cut system, bus by bus.

>INCLUDE_BUSES is used to expand the cut system with individually named buses. This is used in context with >SAVE_ZONES or >SAVE_BUSES to provide more flexibility in the cut system.

>EXCLUDE_BUSES is used to contract the cut system with individually named buses. This is used in context with >SAVE_ZONES or >SAVE_BUSES to provide more flexibility in the cut system.

A maximum of 1000 records are permitted. In the unlikely event that this is insufficient, the above command(s) may be simply repeated with an additional block of bus records.

>CUT_BRANCHES< This command introduces branches that are specified on line records that follow (L, T, or E in column 1). A maximum of 500 cut branch records is permitted.

The CUT_BRANCHES are oriented in the following order: retained bus, cut bus.

The cut system is defined in the following manner. Starting from the set of all cut branches, each bus on the cut side, which is in the eliminated system, is expanded one-adjacent by examining each branch connected to that bus. All branches that are not connected to any bus on the retained bus side are in the cut system. Those terminal buses are eliminated.

The first pass determines all buses 1-adjacent that are in the cut system. The process is repeated, starting with all buses 1-adjacent to the cut boundary to find all buses 2-adjacent. This process is repeated until no further expansion occurs in either system. The major advantage of this approach is that any incomplete cut enclosure is properly diagnosed near the missing branch.

If the WSCC qualifier is selected, any branch in the cut list that has an INT in the ownership field will have its flow transferred to a +A INT continuation bus instead of a +A *** bus. This is done so that if this cut system is to be reintegrated into another system the cut points can be easily identified and discarded.

Unlike other >...< commands, CUT_BRANCH cannot be repeated.

>PI_BACK_BUSES< This process replaces a bus having one or two branches with an equivalent consisting of bus generation, load, and shunt admittances on the adjacent terminal buses.

If the bus originally had two branches, the new system has the following changes:

  • The buses’ generation, load, and shunt admittance are proportioned by the branch admittance to each terminal node.

  • The bus is eliminated.

  • The subsystem consisting of a bus and two branches is replaced with a single branch spanning the two terminal buses.

If the bus originally had one branch, the new system has the following changes:

  • The buses’ generation, load, and shunt admittance are transferred to the terminal node.

  • The bus and its branch are eliminated.

In essence, a pi-backed bus becomes a passive node in a branch that now consists of sections. Since the quantities are pied-back in proportion to their branch admittances, the redistribution approximates the effects of REDUCTION. A maximum of 1000 pi-back records may follow. If this limit is insufficient, the remaining pi-back records may follow another >PI_BACK< command.

Interactive Approach

The following is an example of the dialogue that occurs during an interactive execution.

* command file is: J8301FY84.CUT
ENTER NAME for BUS/BRANCH output file > J83CUT.DAT
ENTER file name for OLD_BASE > A8301FY84.BSE

pvcurve

pvcurve is a command line program that automates production of power (P) voltage (V) curve plot files and plot routine setup files for multiple base cases and outages.

post_pvcurve

post_pvcurve is a command line program that ?

qvcurve

qvcurve is a command line program that generates power-reactance curves.

findout

Command line interface that Generates a table of outages and corresponding branch overloads or bus voltage violations from power flow output (.pfo) files. Works with the .pfo output files of bpf runs that contain an /OUTAGE_SIMULATION command. Runs as a post-processor to filter and sort the results and present them in tabular form. Tables of ‘Outages and Overloads’ or ‘Outages and Bus Violations’ can be produced. Entries in these tables can be filtered according to Zone, Owner, Base kV, Loading and Bus Voltage.

Tables can be sorted by Zone, Owner, Base kV, or alphabetically. The idea is to allow the user to automate the creation of a report detailing the results of outages instead of having to do manually which generally includes cut and paste operation with a text editor. Data fields in the output report table are character delimited to ease importing to Microsoft Excel or DECwrite.

lineflow

lineflow is a command line program that generates a table of values showing the requested branch quantities for multiple base cases. Selects lines by branch list, bus, kV, owner, zone, loading level, or matches to ‘wild card’ input. Sorts alphabetically, or by owner, zone, kV, loading (in percent), or according to input order of branches in a list. Generates a control script that allows repetitive similar studies to be performed automatically. Reports the following quantities: loading in Amps or MVA and percent of critical rating; or, power in, power out, and losses in MW. Data fields in the output report table are character delimited to ease importing to Microsoft Excel or DECwrite.

mimic

mimic is a command line program that generates new cases given a list of base cases and a list of change files. Check the new cases for over and under voltages, overloads, and excessive voltage and loading changes.

ipfsrv

ipfsrv is a service daemon which acts as the power flow server backend component of the X Window Graphical Interface (gui). It executes Powerflow Command Language (PCL) commands dispatched from the gui. It gets launched automatically by the gui.

ipfbat

Overview

ipfbat is a command line program that is the batch version of ipfsrv. It accepts a Powerflow Control Language (.pcl) file. Plotting can be done with a control file; however, for most plots ipfplot is easier to use. Example of use: ipfbat bench.pcl. The PCL commands used with ipfsrv and ipfbat are described in Powerflow Command Language (PCL).

Batch Mode Plotting

Batch mode plotting can be used when a coordinate file already exists, and the user simply wants a hard copy diagram based on that file and Powerflow data. If the Powerflow data is on a saved base case (*.bse) file, the simplest method is to use the ipfplot program. However, ipfbat offers more flexibility and control. For example, with ipfbat you can load, solve, and plot a netdata file.

This technique can be used to produce diagrams that are generally produced through the GUI or for access to features that have not yet been implemented in the GUI. These features include plotting bubble diagrams, plotting difference diagrams, and plotting diagrams from a master list of coordinate files.

An example of batch mode plotting is accomplished through the ipfbat program as follows:

ipfbat bubble.pcl

where the .pcl file is a control file with the IPF commands and data necessary to produce a hard copy diagram.

Commands in the examples are record groups starting with a / (slash) command and ending with the next / (slash) command or (end) for the last command in the file.

Under the command /plot, the first line must name the coordinate file to be used, and the second must name the output PostScript file to be produced. Any subsequent records following, before the next /command, are interpreted as comments, and will be placed in the standard position following the last comment defined in the coordinate file.

Two special uses for comment records must be noted. If the record begins with an ampersand (&), it will be interpreted as an instruction to append the auxiliary coordinate file named on the record. At most one such file may be named. If the record begins with an ‘at’ symbol (@), it will be interpreted as an option record. Any diagram option indicated on this type of record will override the option specified in the coordinate file. Multiple @ records are allowed and will not be printed on the diagram.

Example 1

Make a “standard” diagram (similar to the GUI operation).:

/network_data,file=a92cy91.dat        ! Load the powerflow network data
/solution                             ! Solve the powerflow case
/plot                                 ! Make a hard copy diagram
aberdeenmetric.cor                    ! using this coordinate file
diagram.ps                            ! to build this postscript file.
Case prepared by: A. Perfect Planner  ! Include this comment
Priority of study: RWI                ! and this comment
&aberdeeninset.cor                    ! and this additional coordinate file.
@OPtion DIagram_type=Pq_flow          ! Supplement/Override *.cor options.
/syscal                               ! Hello operating system ...
lpr diagram.ps                        ! ... send this file to the printer.
/exit                                 ! This job is finished.
(end)
Example 2

Make a bubble diagram.

/old_base,file=j94cy91.bse ! Load the powerflow saved base case /plot ! Make a hard copy diagram bubble.cor ! using this coordinate file diagram.ps ! to build this postscript file. BUBBLE PLOT EXAMPLE ! Include this comment. /syscal ! Hello operating system … lpr diagram.ps ! … send this file to the printer. /exit ! This job is finished. (end)

Example 3

Make a difference diagram.:

/old_base,file=9_bus_test.bse                   ! Load the powerflow saved base case
/get_data,type=load_ref_base,file=bus_alt1.bse  ! Load a reference
                                                ! saved base case
/ get_data, type = load_ref_area                ! load reference solution data in tables
/plot                                           ! Make a hard copy diagram
9bus_metricdif.cor                              ! using this coordinate file
diagram.ps                                      ! to build this postscript file.
Case prepared by: A. Perfect Planner            ! Include this comment
Priority of study: RWI                          ! and this comment
Difference plot between two cases               ! and this comment.
/syscal                                         ! Hello operating system ...
lpr diagram.ps                                  ! ... send this file to the printer.
/exit                                           ! This job is finished.
(end)
Example 4

Make a series of diagrams from a list of coordinate files.:

/old_base,file=/shr5/j96cy89.bse       ! Load the powerflow saved base case
/plot                                  ! Make a hard copy diagram
master.cor                             ! using all the coordinate files
                                       ! listed in this file
diagram.ps                             ! to build this postscript file.
Case prepared by: A. Perfect Planner   ! Include this comment
Priority of study: RWI                 ! and this comment on each diagram.
/syscal                                ! Hello operating system ...
lpr diagram.ps                         ! ... send this file to the printer.
/exit                                  ! This job is finished.
(end)
Example 5

Here is an example of a master coordinate file (master.cor).:

master
/home/dave/cor/3rdac.cor
/home/dave/cor/500bus.cor
/home/dave/cor/bubble.cor
/home/dave/cor/sworegon.cor
/home/dave/cor/nwmont.cor

ipf_test

ipf_test is a command line program that provides an interactive way to run Powerflow Control Language commands. It is similar to ipfbat but prompts the user for input data rather than reading the power flow commands from a file.

ipfnet

ipfnet is the batch version of the “save netdata file” function built into the GUI / ipfsrv. This program generates a WSCC-formatted network data file in any of the following dialects: BPA, WSCC, or PTI. The GUI allows you to save a network data file describing the case you currently have loaded. This should not be confused with the netdat program, which performs very similar function by loading a saved base case (.bse) file and writing it out in an ASCII network (.net) file.

Both programs generate a WSCC-formatted network data file in any of the following dialects: BPA, WSCC1, or PTI. “Dialects” means that although the file is still WSCC format, the data is generated with special processing or restrictions and is destined for use with other programs. In the case of the PTI dialect, that data is intended to be processed by the PTI-proprietary conversion program wscfor.

This program extracts network data from a Powerflow “old base” history file. Table F-1 below summarizes the effects of each dialect.

Effect of Dialects on Network Data File

Record or Field

Dialect

Effects

Header comments

PTI

Three header records:

“<case_name> ” “<case_name> ” “<case_name> “

BPA, WSCC, WSCC1

./CASE_ID = <case_name> ./CASE_DS = <case_description> ./H1 <header 1 text (auto-generated)> ./H2 <header 2 text (user input)> ./H3 <header 3 text (user input)> ./C001 <comment 1 text> … ./Cnnn <comment nnn text

Area “A” records

BPA, PTI

Encode zones 1-10 in “A” record, zones 11-20 in “A1” record, etc. Note: Voltage limits on “A” records are not encoded. They are specified by a default array that establishes limits using base kV and zones.

WSCC, WSCC1

Encode only “A” record (any zones 11-50 will be lost). Note: Voltage limits on “A” records are not encoded.They are specified by a default array that establishes limits using base kV and zones.

Intertie “I” records

BPA, PTI

Single entry (low alpha to high alpha) associated “I” records follow each “A” record.

WSCC, WSCC1

No “I” records encoded.

Default percentages on type BG buses

BPA

BG percentages are not changed.

PTI, WSCC, WSCC1

BG percentages are calculated if their default value is invalid.

Continuation “+”” bus records

BPA

“+” records are encoded.

PTI, WSCC, WSCC1

“+” records are consolidated with “B” records.

Reactive capability “Q” records

BPA

“Q” records are encoded.

PTI, WSCC, WSCC1

“Q” records are not encoded.

Minimum branch impedance

BPA, PTI

Branch impedances are not changed.

WSCC, WSCC1

Minimum branch impedances are set to 0.0003 p.u.

Branch ratings

BPA

Options: 1. Use extended ratings (120-character records). 2. Replace nominal rating with minimum (Emergency, Thermal, or Bottleneck). 3. Use nominal rating only.

PTI, WSCC, WSCC1

Options: 1. Replace nominal rating with minimum (Emergency, Thermal, or Bottleneck). 2. Use nominal rating only.

Branch sections

BPA

Encode as originally submitted.

PTI, WSCC

Encode all branch sections in a consistent orientation.

WSCC1

Consolidate all sections into an equivalent branch

Regulating “R” records

BPA

Encode as originally submitted.

PTI, WSCC

  1. Encode as adjustable tap side-fixed tap side.

2. Consolidate parallel LTC transformers into a single, equivalent parallel LTC transformer.

WSCC1

  1. Encode as adjustable tap side-fixed tap side.

2. Consolidate parallel LTC transformers into a single, equivalent parallel LTC transformer. 3. Convert taps into steps (STEPS = TAPS - 1).

D-C “LD” record

BPA PTI, WSCC, WSCC1

Encode as originally submitted. Encode as rectifier side-inverter side.

The resultant output is an ASCII file. Two formats are available for the resulting output. The BPA format retains all of the extra features that are available in the BPA Powerflow program without making any modifications to the data, while the WSCC format option consolidates and restricts the features in order to be used with WSCC’s IPS Powerflow program.

The CASEID of the power flow case data being extracted is used to create a file named CASEID.DAT. Any changes made to the data for WSCC (IPS) compatibility will be flagged on file CASEID.MES.

Input

The ipfnet program prompts with the following requests:

  • File name of the Powerflow “old base” history filename.

  • Select output format desired: BPA, BPA1, BPA2, WSCC (IPS), or WSCC1 (IPS1).

Sample Run

Type ipfnet at the system prompt and press the <RETURN> key. Answer the questions appropriately. An example is given below.

$ ipfnet
> Enter OLD_BASE file name (or Q to quit): ../dat/43bus.bse
> Enter name of network file (default is "../dat/43bus.net"): new.net
> Enter dialect (BPA, WSCC, WSCC1 or PTI): WSCC
> Enter record size (80 or 120): 80
> Nominal rating replacement code
    T = Thermal  E = Emergency  B = Bottleneck
    T: Transformers = T, Lines = T
    E: Transformers = E, Lines = T
    B: Transformers = B, Lines = B
    ET: Transformers = E, Lines = T
    EB: Transformers = E, Lines = B
    M: Transformers = min(TEB), Lines = min(TB)
> Enter rating replacement code: T
* Options selected - dialect = WSCC
                       size  = 80
                      rating = T
> Are above options correct (Y or N)? Y

Note

The codes for dialect and rating must be upper case. ipfnet formats commands which are sent to ipfsrv. Some input checking is done, but invalid values may cause unexpected results.

ips2ipf

The Record Formats used by IPF are defined in ASCII format and consists of area, bus, and branch records. This format is very similar to the format used by the Western Systems Coordinating

Council (WSCC) back in the 1990s in their similarly named Interactive Powerflow System (IPS) application. However, note that IPF supports many record types which are not recognized by IPS, and in some cases the interpretation and application of the data values entered is different.

The ips2ipf command line program is designed to ease the burden of converting an IPS data deck into one which can be input to the IPF program with the expectation of getting the same powerflow solution results, within normal engineering tolerances. However, the conversion is not 100% automatic. See IPS IPF Differences section for more detail on the data input and internal modeling differences between the two programs.

Before running ips2ipf on an IPS data file, you should remove from the file all COPE commands (TITLE, NEW, ATTACH, etc.) The program will handle the standard ‘control cards’ HDG, BAS, and ZZ. Title records may be retained by putting an HDG in front of them, or by putting a period (.) in column 1 of each. An unlimited number of (.) comments are is allowed, but these only annotate the data; they are not printed anywhere in the output.

ips2ipf performs the following tasks:

  1. Renames duplicate buses.

    IPS uses a 12-character bus name, which includes the base kV. IPF uses only 8 characters, plus the real value of the base kV. To IPS, SAMPLE 230. and SAMPLE 230 are two different buses; to IPF they are the same bus.

    ips2ipf identifies duplicate names and generates a different name for one of them. It reports any changed names; if you don’t like the name it generated, you can change it after the fact.

  2. Makes the system swing bus a BS bus, if given its name.

  3. Transfers non-zero shunt vars from BE and BQ records to +A records.

In IPS, the shunt vars value entered for a bus which has variable var output is considered to be a fixed component of the total vars. In order to retain this philosophy in IPF, it is necessary to put the shunt on a +A (continuation bus) record. Shunt vars entered on the BE or BQ record are considered by IPF to be continuously variable.

  1. Converts non-zero ‘steps’ on R records to ’taps’ (by adding one).

    IPS uses the number of steps available between TCUL taps; IPF uses the number of actual taps. If you run the conversion on an already converted file, another one will be added, which is probably not desirable.

  2. Converts IPS comments (C in column 1) to IPF comments (. in column 1).

    Unlike IPS, which prints the comments in the input data listing, IPF does not print them at all. But they can remain in the data file itself for information as long as they have a period in column 1 instead of a C.

  3. Copies the controlled bus name from each X record to the corresponding BX record, to ensure that the proper bus is being controlled.

  4. Copies the voltage limits from a BX record controlling a remote bus, to the remote bus record.

  5. Corrects blank section id’s in multi-section lines.

    Blank is acceptable to IPF as a section identification only on single-section lines. ips2ipf identifies multi-section lines, and changes blank to 1, 1``to ``2 etc. If there are actually 10 sections (IPS limit), then sections 8 and 9 will be combined and labeled 9.

  6. Gives bus ties a small impedance.

    IPF does not allow bus ties (0.0 impedance produces a fatal error.) ips2ipf changes this to (\(0.0 + j0.00001\)), the same impedance IPF gives you when you sectionalize a bus and create a “bus tie” between the new bus and the old one. However, you should note that this may cause difficulties in getting a solution. (There are no zero impedance lines in standard WSCC study cases.)

  7. IPF has no RF model. Any RF records in your deck will be ignored.

Items which are not handled by ips2ipf, which you need to look out for, are the following:

  1. In IPS, line and bridge current ratings on DC are not processed, but only passed on to the Stability program. IPF actually uses them. You may find that the bridge current rating on the Intermountain DC line is too low.

IPS IPF Differences

  1. Powerflow Command Differences: All IPF commands are different from those in IPS. When you are using the GUI, you will not have to worry about any of these, but there are some things you will need to do to your input data deck, such as deleting all the IPS control records and COPE commands (HDG, BAS, TITLE, ATTACH, $DONE, END, etc.).

  2. Terminology: The IPF Base Case (.bse) file is a binary file equivalent to the IPS History (.HIS) file. However, the Base Case file does not contain any mapping data, and only one case per file is permitted. The IPF Network (.net) file is an ASCII file equivalent to the IPS base case or base data file (.IPS). However, this file must not contain any modification records (’M’ or ’D’ in column 3). Changes go in a different file, which must be loaded separately. All mapping data is saved (in PostScript format) in a Coordinate file (.cor). Only buses which have a match in the currently loaded system data will be displayed.

  3. Case Title: IPF builds the first line of a three-line IPS style title from the 10 character Caseid and the 20 character case description fields, and the other two lines from the two HEADER records. All of these are printed on standard BPA output listings, saved on the base case (history) file, and printed on hardcopy maps.

  4. Structure: The IPF Changes file (.chg) contains new and modification records you want to apply in bulk to your base case (e.g. your own local system representation). You will use the GUI to make individual touch-up or particular study changes. The system slack bus must be specified as a ’BS’ bus in the Network file; there is no GUI provision for selecting a slack bus (other than by changing the type of some bus to BS).

  5. Data Differences: IPF system data is very similar to that for IPS, but is not identical. If you try to read in a WSCC base case deck as an IPF network file, you can expect numerous data errors and no solution. If you charge ahead, fixing fatal errors as you stumble over them, you will still probably not get the answers to match, because of modeling differences. The data conversion program handles most of these. There are two categories of differences between BPA and WSCC power flow models:

  1. Modeling differences (including BPA extensions).

  2. Input data differences

WSCC’s IPS

BPA’s IPF

1

The DC line current rating is used only as a base by IPS. Both line current and bridge current ratings are passed to the Stability program; they are not used as limits in the powerflow solution.

The minimum of the bridge current rating and the line current rating is used as a limit by the DC system solution

2

Type RM phase shifters (controlling :math: P_{km} between \(P_{min}\) and \(P_{max}\)) will bias the phase shift angle towards the original phase shift angle.

Type RM phase shifters (controlling \(P_km\) between \(P_min\) and \(Pmax\)) will bias the phase shift angle to zero degrees to minimize circulating real power flow.

WSCC bias is available as a solution option on the GUI.

3

A type BG generator may control only bus type BC.

A type BG generator may control bus types BC, B , BQ, BV, and BT.

2

An LTC may control only bus type BT.

An LTC may control bus types BC, B , BQ, BV, and BT.

5

Only one voltage control strategy per bus.

A generator and an LTC may simultaneously control a common bus. If a degree of freedom exists, the LTC will control \(Q_km\) directly to minimize transformer var flow between terminal buses.

6

Type BX buses will bias the solution towards the original \(X_shunt\).

Type BX buses bias the solution to \(V_max\). WSCC bias is available as a solution option on the GUI.

7

Infinite default limits are assigned to type BG buses.

Default global voltage limits are assigned to all buses, including type BG buses, by base voltage level.

8

The bus shunt reactive on type BQ buses is fixed.

The bus shunt reactive on type BQ buses is continuously adjustable (0 to 100%).

To make that quantity fixed, it must be entered on an accompanying +A continuation bus record.

The conversion program automates this.

9

Inductance (G-jB) is applied to only one end of a transformer branch.

One half of G-jB is applied to each end of both transformers and balanced pi lines.

10

Model RF phase shifter takes several iterations to get from an initial angle to its final (fixed) phase shift angle.

No such model. Problems in solving phase shifters are handled internally.

11

Phase shifter must have same base kV at both terminals.

Step up phase shifter. Tap2 field is off-nominal tap2.

12

Phase shifter cannot be a section.

Phase shifting transformer can be a section.

13

Bus ties (zero impedance lines) receive special handling in solution and reporting.

No special bus tie model. A ‘bus tie’ is defined as a very low impedance line (0.0 + j0.00001).

14

Not available.

+ continuation bus records. Except for constant current load models, these records are used mainly for accounting purposes to differentiate generation, load, and shunt with unique ownerships.

15

Not available.

I area intertie records. These records compute net area export on accompanying A records.

16

Not available.

A area record may be accompanied with A1, A2, A3, and A4 continuation records to accept a maximum of 50 zones per area.

17

Not available.

Branch records accept extended line current ratings:

For types L and E records, thermal and bottleneck ratings.

For types T and TP records, thermal, bottleneck and emergency ratings.

18

Not available.

Types BM and LM multi-terminal DC data.

19

Not available.

Type RZ RANI devices.

20*

Base kV field interpreted as A4 for identification purposes. SAMPLE 20.0 and SAMPLE      20 are different buses.

Base kV field interpreted as F4.0. SAMPLE 20.0 and SAMPLE      20 are the same bus.

21*

The number of steps on R records are interpreted as steps, where STEPS = TAPS - 1

The number of steps on R records are interpreted as number of taps, where TAPS = STEPS + 1

22*

A parallel branch consisting of sections will accept section numbers in the set [0-9]. (Blank is interpreted as a zero.)

A parallel branch consisting of sections will accept section numbers in the set [1-9]. Zero or blank can be used as a section number only be used on delete, to remove all sections of one circuit.

23*

Remotely controlled bus for a BX bus is specified on the X record.

Remotely controlled bus for a BX bus is specified on the BX record.

24*

Voltage limits for a bus remotely controlled by a BX bus are specified on the BC record.

Voltage limits for any bus, no matter how it is controlled, are specified on the controlled bus record.

25

Voltage limits (for reporting over and under voltage buses) are specified on A records

Default voltage limits (for all purposes) are specified by a default array which establishes limits using base KV and zones.

26*

Branches entered with both R and X equal to zero receive special handling as ‘bus ties’.

Zero impedance is not allowed - no bus tie simulation.

27*

The system slack bus can be designated as a BS type bus, but very often is specified in the SOLVE options instead.

System slack bus must be specified as a ``BS `` bus.

28*

IPS accepts various types of comment records (CB, CL, CR) which annotate the data file, and are printed in the (batch) input listing.

IPF uses a .` (period) in column 1 to designate a comment. These annotate only the data file; they are never printed.

  • The conversion program will handle this item.

Transient Stability Program (tsp)

The tsp program performs dynamic (e.g. generator rotor angle, governor output, power system stabilizer output, etc.) simulation of a power system when disturbed from its steady-state condition under various perturbations such as three phase faults, line to line faults, line to ground faults, loss of generation, etc.

Program Description

There are basically two methods of simulation used in this program. All differential equations are linear and solved by the trapezoidal rule of integration. The network equations are solved iteratively using the triangularized admittence matrix. Both of these methods are described in the paper Fast Transient Stability Solutions (IEEE Transactions on Power Apparatus and Systems, July/August 1972) written by Hermann Dommel and Nobuo Sato.

The diagram ?? shows that the swing program is divided into solution and output portions. The solution portion creates a swing solution file which saves all output data for all busses in the study. This structure allows the user to run the solution portion and save the swing solution file. Then, using the swing solution file, the power flow output file, and the swing output data file, the user can run any number of output jobs without resolving the solution.

The program is designed to run in conjunction with the IPF power flow program (bpf). The diagram ?? shows the interconnection between the power flow and transient stability program. Note that both the soution and output portions of the swing program require a power flow output file (.bse) as input.

The program also has a save data feature which allows the user to enter the majority of the swing input data via a save data file and enter only the line switching and FF records in the swing input file. This is useful when a series of swing studies are run using the same basic data but with different system perturbations.

Appendix C shows examples of how to create a save data file, how to run a study using a save data file, and how to run an output only job using the swing output file. The command files show how to make the necessary logical file assignments.

The DEBUG and COMMENT records are optional. Any information on the COMMENT records appears on the output listing as well as on the plot headings.

The switching records (LS) contain a variety of features and enable the user to properly define each event in chronological order. Several examples in preparing LS records are covered in ??.

The LZ record is used with the LS record and permits changing branch admittance quantities in the transient stability program.

The MZ record has the special feature which permits remote control signals for power system stabilizers and excitation systems. This card also inputs the generation transformer data for low-side generator bus determination not represented in the power flow but required for the excitation system.

Several control parameters and codes are available to the user and are entered in the DEBUG, CASE, FF, and 99 records. The CASE record and the 99 record have print options and the FF record contains several control parameters and codes for proper operation.

The output portion of the program provides the output data in the form of listings and/or plots. The plotting routines were written for a VERSATEC plotter and this code is not very portable.

If line impedances were modified during the solution portion of the program, to correctly output data for these lines the output portiong of the program must be given the modified impedances via line modifiation (LM) records. ?? gives an example of how to use LM records.

The remaining information for the Transient Stability Program has not yet been migrated to ReadTheDocs format. See TSP Users Guide PDF for details.

X Window Graphical Interface (gui)

This section presents information about the X Window graphical user interface (gui) for IPF.

_images/IPF_GUI.png

Interactive Power Flow X Window GUI

IPF’s X Window GUI interface makes data entry and modification easy. It also simplifies the running of base case solutions and the printing of network diagrams. This guide shows how to use the major features of IPF. Users who need details about data input record formats or system models should consult the Record Formats section.

IPF’s GUI uses the X Window System and the OSF/Motif window manager interface. The graphical user interface features an interface that will be familiar to people who use an X Window System before, but it will feel a bit cumbersome compared to modern day applications.

Audience

You will be expected to already know the basics of power flow programs in general. You will find that small changes in bus and branch values are easier to make in the GUI than trying to manage through ASCII text files and running bpf commands on the terminal. For example, users will get a feel for how changes to the input data affect the solution voltages in a network much more quickly with the GUI than by using a terminal style interaction.

User Interface

The X Window System and the OSF/Motif window manager use certain descriptive terms for actions performed with the mouse. These terms are defined here. In addition, some keyboard actions are also defined. See the table below.

Keyboard Conventions

The following conventions are used for key strokes. Generally, a hyphen (-) connects key names that should be pressed and held, starting from left to right. For example, the key sequence Control-c Shift-E means to press and hold the Control key and then press c. Release this combination and press and hold the Shift key and then the E key. Then release these keys. A different example: Esc f means to press and release the Esc key followed by the f key.

In general, the mouse operation and keyboard operation follow the conventions of the Motif interaction style guidelines. These are found in the OSF/Motif Style Guide. Many aftermarket books about Motif cover these conventions also.

X Window System

This chapter provides a quick introduction to the X Window System and X window managers with emphasis on the OSF/Motif window manager. The treatment here is certainly not exhaustive or even complete. But it is intended to give you enough background to successfully use the Interactive Powerflow (IPF) program.

If you have not used an X Window based GUI before, be sure to go through this chapter for some pointers so that you’ll be headed in the right direction. If you would like more information, refer to the following books resources the X Window System and OSF/Motif.

  • Open Software Foundation. OSF/Motif Style Guide Revision 1.1. Prentice Hall, 1991. This provides the official description of OSF/Motif look, feel, and behavior for OSF/Motif software developers. Though not oriented toward OSF/Motif users, this book does give precise descriptions of all OSF/Motif components and behavior.

  • Quercia, Valerie and Tim O’Reilly. X Window System User’s Guide OSF/Motif Edition. O’Reilly & Associates, Inc., 1991. This is a good, general introduction to X and OSF/Motif.

  • Motif Programming Manual

Broadly speaking, the X Window System is designed to deliver mouse-driven menu/window user interface applications over a local area network.

The X Window System specifies that the “look and feel” of its user interface be “policy free.” Because of this, programmers are free to create their own look and feel within broad limits. Over the past few years, Sun Microsystems, AT&T, and the Open Software Foundation have all created GUIs for the X Window System with a distinct look and feel. The Open Software Foundation offers OSF/Motif.

Like most large software systems, X and its environment have a jargon of their own. Here are a few terms you should know:

Server

The part of X resident in your local computer (or X terminal) memory. The server has three main tasks. First, the server takes care of communicating with the mouse and keyboard. Second, it takes care of managing X resources, such as fonts and colors. Third, it communicates with X applications.

Client

A stand-alone X program. Clients are the X programs that you use to accomplish your work, such as drawing graphs, preparing text, making power flow calculations, etc. Clients usually reside in a computer across the local area network, but they can also reside in the same memory as the server itself. Clients and servers communicate through a special language (“protocol”) that is especially efficient for communication over a Local Area Network (LAN).

Resources

X components that are held and managed in common for X clients by the server. X resources reside in your local computer (or X terminal) memory just like the server. X resources are things like fonts, color “pixmaps,” font information, etc.

Window manager

A special X client that handles the window services of other X clients. There are a number of different X window managers, not just one, but you only use one window manager at a time.

X terminal

A special purpose computer having a built-in X server, and connection hardware and software for a LAN.

LAN

A Local Area Network usually based on the hardware and low-level software standard of Ethernet. For Unix computers, the software communication protocols are usually based on the TCP/IP standard. PC networks may use different hardware and software network communication standards.

The GUI portion of IPF is a server; the powerflow portion is a client. These two programs may reside on different computers, in which case the GUI will be running on the machine you are sitting in front of, and the powerflow will be running on a workstation somewhere else, perhaps a network server. Note that the X Window terminology for “client” and “server” is reversed from the network communication terminology. It is also possible for both client and server applications to be running on the same computer.

_images/A_Server_Some_Clients_and_a_LAN.png

A Server, Some Clients, and a LAN

The figure above shows you the basic architecture and communication model of the X Window System. Something you should note is that the client (application) program may be physically residing on a completely different computer from the one that your keyboard, mouse, and display are attached to. To access the remote application, you only have to know the name of the computer your client is on. (You also must have permission to use the other computer, of course, and it must be connected properly to the LAN.) The X Window System was designed from the ground up to run in a distributed computing environment.

When you are running a client, such as IPF, over the network, in contrast to running it in your own computer’s local memory, you will ordinarily notice very little performance degradation due to network traffic, though there may be some depending on how busy the network is. X is designed to minimize network communication.

The server side of X resides in your own computer’s (or X terminal’s) memory. There is one X server for each user’s keyboard, mouse, and display. The server is dedicated to you. However, your server may communicate simultaneously with many different X clients, not just IPF. And again, these other clients may be anywhere out on the LAN. Thus, in any one X session (between “login” and “logout”), you may run many X clients on many different computers. The server manages all this.

When your client requests a certain font, the server delivers it. When your client requests different colors for graphical objects, the server consults the color map for that client and delivers the correct colors. Fonts, colors, and certain other server-managed software components are termedresources. Some resources such as colors and fonts you can change in your own account’s IPF resources file, XGUI. See Customizing the GUI (XGUI) if you would like to learn more about this.

A Summary of Motif Basics

IPF is designed to run and look best with the Motif window manager. This section introduces you to some Motif window manager basics. However, for detailed information, turn to the books cited at the beginning of this section.

Motif Windows

Motif windows are rectangular areas of the display. Various Motif components surround a central area where text and/or pictures appear. See example below. These components are controlled by the Motif window manager. However, the central area is controlled by an X client, which is a completely separate program from the Motif window manager. IPF gui is an X client, so it controls only the interior of Motif-managed windows. Because of this separation, you may notice that IPF’s windows can still be moved, iconized, etc., even though the IPF client may not be responding.

In the figure below, the Terminal Emulator client controls the central display (where the text is), the Menu Bar, and the Scroll Bar. The Motif window manager (client) controls all the rest of the window.

_images/Motif_Window_Components.png

Motif Window Components

Motif Resources

Like the X Window System, Motif has resources that you can change. Resources are system controlled components such as fonts, colors, initial size and position of windows, etc. Many X clients (application programs) have customizable resources. Since the Motif window manager is just another client, it has customizable resources, too.

Resources can be changed in two ways:

  • Change the dedicated client resource file with an ASCII text editor. On Unix systems, the Motif resource file is named .mwmrc and the X resources file is .Xdefaults

  • Use a dedicated X application that provides a regular GUI interface for changing the resource file.

Since interpreting the meaning of the resource specifications is not always easy or straightforward, it is recommended that you look for a dedicated X client for changing resources. Your Motif system probably has this X client already available, so that all you have to do is choose the Motif resource editor as a command on a system menu. Possible names to look for are System Setup, Configuration, User Preferences, or something similar. The editing of the many resources may be broken out on your system menus as separate commands, such as Colors, Fonts, Sizes, etc.

As a second choice, use a Motif book to help you interpret the meaning of the resource specifiers in the .mwmrc file and edit them with an ASCII editor such as the vi ASCII editor. Nearly all Unix systems have vi.

Common Windows Tasks

This section goes through a few common window and menu tasks to give you a feel for the Motif interface. Some tasks can be done through a menu command and through direct manipulation of a graphic component. And, in addition, many tasks can be accomplished through a sequence of keys without recourse to mouse movement or button clicks. The following brief descriptions concentrate on direct graphic component manipulation since this is usually the quickest way to get something done in Motif.

To move a window

Motif windows have a title area at the top. The window shown above has “Terminal Emulator” in the title area. You move Motif windows by “grasping” the window in this area and dragging it to a new location.

  1. Move the mouse cursor to any point within the title area.

  2. Press and hold the left mouse button.

  3. Move the window to another location of the display. You will note that an outline box of the window shows you the dimensions of the window as you are moving.

  4. Release the button. The window appears at the new location.

To reduce a window to an icon

Icons are small, rectangular graphic objects that represent the main windows of Motif applications. Icons have many, but not all of the same attributes as windows - for example, they can be moved like windows. Icons are used to organize the display and reduce clutter. You are free to put icons wherever you like on the display. Some Motif systems organize icons in a special window, which looks like a desktop.

  1. Click the Minimize button at the top right of a window. This shrinks the window to an icon and automatically places the icon at a predetermined place on the display. (Note that this place may be obscured by other windows!)

  2. Move the icon as you would a window by placing the cursor over the icon, pressing the left mouse button, moving, and releasing the button.

To change an icon into its window

An icon can be changed back into its windows by double clicking on it. The window will “remember” where its previous position was. Sometimes the timing between clicks is important, so make sure you do it fast enough.

  1. Find an icon (or create one) and move the mouse cursor over the icon. Double-click the left mouse button. Be sure to keep the mouse cursor stationary between clicks; otherwise, Motif may interpret your actions as a “move icon” operation.

  2. If you find that a menu pops up, select the Restore command by moving the cursor over the word and clicking once.

To resize a window

Motif windows have a narrow border that acts as a “handle” for resizing operations. There are eight parts to the border — four corners and four sides. The corners are used to resize simultaneously both adjacent sides, and the sides are used to resize just one side at a time. The following procedure describes a common resizing operation.

  1. Move the mouse cursor over the lower right corner. Note that this corner is demarcated by two cross cuts on the border a short distance away from the corner. The cursor may change its appearance when it is in this area, indicating that it is in the right position.

  2. Press and hold the left mouse button on the lower right corner.

  3. Move the mouse to the inside or outside of the current window.

  4. Release the mouse button when you are satisfied with the size.

The opposite (upper left corner) remains stationary while you move the mouse around. A border line for two sides shows up to give you an idea of the size of the window as you move. Also, a pixel counter of the vertical and horizontal dimensions shows up to give you feedback if you need it.

If the corner or side the you want to grab is not visible on the screen, move the window until it is.

To enlarge a window quickly

The Maximize button in the upper right corner is a quick way to enlarge a window to the maximum size of your display.

  1. Move the mouse cursor over the Maximize button in the upper right corner of a window.

  2. Click the button. Note that the window now covers the maximum area of the display. (All other windows should be covered.) You can resize the window using the directions above.

To pop up a window’s menu

All Motif windows have a minimum set of window management functions available in the upper left corner via the Window Menu button. Many of the functions described above are available through this menu. Some additional ones are there too, such as Close, Restore, and Lower.

  1. Move the mouse cursor over the Window Menu button in the upper left corner.

  2. Press and hold the left mouse button. Note that a menu pops up. Select one of the commands on the menu by moving the mouse cursor over the command and releasing. Only commands that are clearly visible are selectable. Those which are “grayed out” are not accessible or appropriate in the current context.

Closing a window causes the window to disappear from the display, so be careful because it can also quit the application. In the beginning, you may not know how to restart an application! (Look for a Motif window called the Session Manager. Your system operator has probably set up your account with a Session Manager. See if you can find the closed application on a menu in your Session Manager, so that you can re-open the application if you accidentally close it.)

Lowering a window means to cause it to go to the bottom of the windows “stack.” Think of Motif windows as pieces of rectangular paper on a desk. The ones that overlap have an order from top to bottom. The Lower command causes movement of windows in the stack from top to bottom. Experiment with the command to see how it works. You bring “buried” windows to the top by pushing visible ones down with the Lower command. Note, however, that if you see any piece of a Motif window, you can just click on or inside the border to bring it immediately to the top.

IPF as an X Client

IPF is built on top of the X Window System and uses the facilities of an X window manager of your choice. (However, the recommended window manager is Motif.) In the figure below, you can see that both the X server and the GUI part of IPF reside on the user’s computer. Another client that is always present on the user’s computer is the user’s window manager. This is not shown in the figure below, however. In most configurations, the “engine” (ipfsrv) part of IPF resides on the user’s computer, but may, as shown below, reside on some other computer across the LAN.

When you start up IPF, the GUI initializes itself, initializes ipfsrv, and then brings up IPF’s window interface.

_images/Powerflow_GUI_Communication.png

PowerFlow/GUI Communication

IPF X Window GUI Architecture

The figure below shows a high-level view of the IPF X Window GUI and its environment. IPF is divided into the GUI code, which is written in C, and the powerflow code, which is written in Fortran. When you run the X Window System and Motif, you are using the Motif and X libraries in addition to Unix operating system calls and IPC (Interprocess Communication) calls. The GUI part of IPF (gui) uses the Motif library and IPC calls. The powerflow part of IPF (ipfsrv) uses IPC calls.

Because the Motif library is used for IPF, the Motif window manager is recommended for running with IPF. You can use another window manager with IPF, but the program will not have a consistent look and feel. The functionality remains the same, but you will notice a visual style within the IPF client that is different from the window manager, which controls the display outside the IPF windows and dialog boxes.

_images/Powerflow_GUI_and_System_Software.png

Powerflow/GUI and System Software

History

Some key developments took place in the late 1970s and 1980s that made possible the X Window System and the X window managers.

  • The idea of the graphical user interface (GUI) was created, implemented, and became popular.

  • Personal computers became powerful enough to handle the data and processing intensive GUI.

  • Efficient, fast, inter-computer communication - the local area network (LAN) — became widespread.

  • A general purpose, non-proprietary operating system - the UNIX operating system — achieved wide acceptance.

All of these developments contributed materially to the possibility and, indeed, the eventual widespread acceptance of the X Window System and X window managers.

In the late 1970s, medium-sized computers began to get powerful enough to handle information organized graphically rather than in a character-based (textual) way. They also began to get cheap enough to be dedicated to one person. It was on one of these computers that the Xerox Corporation installed the very first GUI using a mouse, menus, and windows. This GUI borrowed heavily from the Smalltalk-80 user interface, which was also invented at Xerox. (Smalltalk-80 is an object-oriented programming environment and system.)

GUI - graphical user interface - simply means using the graphics capability of a computer as the primary mode of interacting with users. A few GUIs do not, in fact, use a mouse, menus, and windows. However, GUIs using this combination of elements became common early because of their inherent ease of use.

Meanwhile, truly affordable personal computing was taking off in the late 1970s and early 1980s with the Apple and then IBM PC computers. These computer architectures were essentially graphical in nature, especially the Apple, though their interfaces were still character-based.

In 1984, Apple introduced the first personal computer with a thorough-going GUI. This was the Macintosh. This computer introduced wide numbers of people to a very easy to use graphical interface. It showed many computer manufacturers that they needed to design with GUIs in mind. A few years later, Microsoft Corporation retrofitted a windowing system onto MS DOS IBM PC-compatible computers.

Also in the late 1970s and 1980s, Sun Microsystems, Hewlett-Packard, DEC, and other companies saw the need for powerful computing “workstations” that business, research laboratories, and government could use. These workstations became common where personal computers didn’t have enough power. However, they generally lacked GUIs, which made them harder to use and less versatile than they might have been.

Another element in the computing picture was also developing in the 1970s and 1980s. This was widespread inter-computer communication. The idea of the local area networks (LAN), which was a room-to-room and building-to-building communication network, was created and implemented. A particularly popular LAN was, and is today, the Xerox-created Ethernet. This LAN is simply a cable connecting computers, whereby the computers can request and send just about any kind of data, often organized as files.

Another computing environment element was the development and distribution of a general purpose operating system that was platform independent, the UNIX system developed in the 1970s and 1980s at AT&T’s Bell Labs. This operating system was distributed freely to many college campuses, and the University of California at Berkeley developed many extensions to UNIX, among them sockets which provide efficient communication over LANs. Today, the UNIX operating system is offered commercially by AT&T as UNIX System V.

To complete the computer environment picture of the 1980s and 1990s, engineers at the Massachusetts Institute of Technology created the X Window System, often called just “X.” This GUI and underlying software was designed for powerful workstations with graphics-oriented hardware architecture. These capabilities are now available on high-end PCs as well. It is also designed for computers that make heavy use of a LAN. Though not limited to the UNIX operating system, the X Window System was first developed on UNIX computers.

Working with the GUI

This section describes how to accomplish basic tasks in the GUI version of IPF. After reading through this chapter, you should be able to use the Concepts and Commands section to figure out and work with the rest of IPF’s features.

The material in this section is not written as a complete, start-to-finish tutorial. Rather, the material is organized by individual task. However, the various topics are organized so that they reflect the common order of tasks in a typical session. So, you can either read the topics and do the steps within the topics in the order presented, or you can skip around and try out specific topics as they interest you.

Note

Most of the task procedures in this chapter involve using the mouse and its buttons. When you are asked to use a mouse button, the left-hand button is meant unless you are explicitly directed otherwise.

The main menus and toolbox are the keys to IPF’s main functions. The main menus contain commands that allow you to open files, save files, print network diagrams, solve cases, get help, edit bus and branch data, and so forth. The toolbox contains icon buttons that move you into and out of various display modes. They allow you to create new buses, move buses, bend branches, reduce or enlarge the display, modify bus or branch data, and so forth.

The Display Mode buttons determine whether the map shows the intersection of the currently loaded base case file and the currently loaded coordinate file, or everything in the coordinated file. The current files area tells you which files you currently have loaded. The branch color key indicates the base kV rating of branches shown on the display, or their overload status.

In a prototypical session, you would generally follow this scenario:

  1. Load a solved system and/or a network data file, and a coordinate file via the main menu Files - Open command.

  2. Make changes to the system and/or coordinate file data using the various toolbox icon buttons, which allow direct on-screen manipulation of bus icons and branches, or bring up dialog boxes for adding data to bus and branch records.

  3. Solve the new case with the main menu Process - Solve command.

  4. Save your new case including its solution data with the main menu Files - Save command.

  5. Print out a network diagram with the main menu Files - Print Plot command.

You might also do the following:

  • Run a CFLOW program with the main menu Process - Auto CFLOW command.

  • Get some help along the way with the main menu Help command.

_images/Main_Window.png

Main Window

_images/Toolbox_Icons.png

Toolbox Icons

Starting IPF

IPF is an X Window System application and is started like any other X application. However, your underlying operating system and the window manager you are running offer some ways to simplify how you start up IPF. Essentially, there are three ways you can start up IPF:

  • You type the IPF command name gui in a terminal emulation window.

  • You select IPF on your window manager’s “run applications” menu. Generally, this involves clicking a mouse button on the background to bring up the “run applications” menu.

  • You find that IPF is started automatically when you log in to your account. This means the system administrator has already set up your account to do this. You should see IPF as an icon or open window after the login process is complete.

To start IPF from an X terminal emulator window:

  1. Make sure the X Window System and your window manager are running. Consult with your system administrator if you don’t have X running.

  2. Find a terminal emulator window or open one from a window manager menu.

  3. In the terminal emulator window, enter gui. Within a minute or less, depending on the performance of your computer system, you should see the IPF main window appear.

Exiting IPF

When you are through editing the currently loaded base case or coordinate files, running a solution, etc., and have saved your work, choose the Exit command from the File menu.

  1. Click the File menu and select the Exit command. You will see the Exit dialog box come up. Do not use the window menu button (upper left) to close the IPF window.

  2. Click OK if you are sure you want to exit IPF. Click Cancel if you have changed your mind and want to keep IPF running. If you select OK, IPF closes all its windows and removes them from the screen. You will still be in the X Window System, and you can proceed to any icon or open window to continue working with other X clients. If, after exiting IPF, you decide to run IPF again, see Starting IPF, above.

Opening Files

The Open dialog box shows you the five kinds of files you can open in IPF: the command, change, base case, network data, and coordinate files. See the figure below. For detailed information about these files, see Powerflow Command Language (PCL) and Record Formats.

For most power flow studies, the base case (binary) coordinate files are used. However, network data files must be used to initially create a binary base case file. Change files are used to make changes to a base case file; this case is called a change case, and the results are typically saved as a new base case file. Command files are Powerflow Command Language (PCL).

Unlike the command, change, network data, and coordinate files, which are ASCII text files, the base case file is a binary memory image file. The base case file contains only power system data, which is edited within IPF, whereas the command, change, and network data files may be editedoutside IPF using any ASCII text editor.

The coordinate file is a combination of bus position and branch bending point data in addition to plotting data. The coordinate file bus position and branch bending point locations can be altered by moving them in the GUI display, and a new coordinate file saved if desired. The plotting data can also be edited outside of IPF with an ASCII text editor.

Displaying a Network File

Normally, you will want to load a coordinate file in addition to the network data or base case file you intend to work on. If you do not, you will not be able to display the system graphically in the IPF main window. A system data file needs coordinate position information to display itself in IPF. It must get this information from a coordinate file since it does not have this information within itself. However, if all you want to do is edit a coordinate file, you can load just that file, and it will display properly in the main window.

If you load only a system data file, you can use only the textual editing and report capabilities of IPF to see your data, but you can still solve, make changes, save cases, etc. Also, you can generate a network diagram on the fly from which you can graphically navigate or display results. See Exploring Base Case Connectivity.

To open a network file:

  1. Choose Open from the file menu in the IPF main window. You will see the Open dialog box as shown in Figure 3-3.

  2. Find Network Data File at the left of the dialog box. The button, information box, and file text boxes under the heading allow you to select a network data file. The file text box under the Select button holds a file selection string. The string displayed when you first open the Open dialog box comes from a default that you can set in your XGUI file. See Appendix A, Customizing IPF.

  3. Click the Select button. Notice that the file selection string is transferred to the Filter file text box at the right. Also, the Files list changed to reflect the Filter criteria.

  4. Scroll the Files list to find the file you want to load.

  5. Select the file by clicking it. This action puts the selected file in the Selection file text box below the Files list.

  6. Click the Apply button to put the file name you have selected in the Network Data File file text box at the left side of the Open dialog box.

  7. Click the Load Selections button at the bottom of the left side of the Open box. This final action actually loads the selected file into IPF’s memory.

Since step 7 causes the open files dialog to close, it is best to perform steps 1 to 6 for each of the different kinds of files you want to load, and then click Load Selections at the end to load all files at one time. Note that you cannot open a network and a base file. Only the last one you picked will be loaded.

To open a command, change, base case, or coordinate file:

To open these files, perform the steps above. All of the essentials are similar; only the file type is different.

Saving Files

You can save five kinds of files in the X Window GUI: change files, base case files, network files, coordinate, and stability interface files. Ordinarily, you save files after you are done with a work session, but you can save a file at any time. Change, network, and coordinate files are saved in ASCII text format. Base case files are saved in binary format. Stability interface files can be saved in either binary or ASCII format. In a binary file, a memory image of base case data is written out to a file. See Overview for more information about these files.

To save a file:

  1. Choose Save from the File menu in the main IPF window. You will see the Save dialog box as shown in the figure below.

  2. Change the name of the file you are saving if you do not want to overwrite an existing file.

  3. Click the appropriate Save button to save the desired file.

  4. If the file you are trying to save has the same name as an existing file, you are presented with the Overwrite warning dialog box. You can choose Overwrite to complete the save or Cancel to cancel the save. Note only one base per file is allowed.

_images/Saving_a_File.png

Saving a File

Changing the Displayed Network Size

You can use the X Window scroll bars on the right and bottom edges of the network display window to see a different chunk of the network diagram. The X Window GUI also includes an enlarge (and reduce) displayed network feature. Two buttons in the toolbox control this. X Window GUI has three displayed network size options. When you first load a base case or coordinate file, the middle size is chosen by IPF. If you find you would like to see more detail in a network diagram, you choose the Enlarge button. If, on the other hand, you would like to see the overall picture, you choose the Reduce button. The Enlarge button doubles the displayed network size, and the Reduce button halves the image size.

All other toolbox operations work no matter what the network size is, so you are free to work with the size that best suits the task at hand.

_images/Displayed_Network_Sizes.png

Displayed Network Sizes

To alter the displayed network size:

  1. Make sure you have a coordinate file loaded. See Opening Files to find out how to do this.

  2. Click the Enlarge button in the toolbox in the main window. This magnifies the displayed network by two times. Note that you are now at the top magnification, 2.0.

  3. Click the Reduce button. The displayed network returns to its original size (1.0), which is the size created by an Open operation. Click the Reduce button again. The displayed network size decreases by half. This is the smallest size, 0.5.

Editing Base Case Data

Editing a base case file is one of the primary activities in the X Window GUI. This involves a number of tasks: adding new buses or branches, modifying existing bus or branch values, and deleting existing buses or branches. These tasks are all accomplished in the main window toolbox and display area.

Modifying a Bus

Modifying a bus means to alter any of its associated values as they exist in the currently loaded base case data. This is done through the Input Data Edit Box. Refer to Bus and Branch Editing to find out more about the Input Data Edit Box.

To modify a bus:

  1. Make sure you have system data loaded. See Opening Files to find out how to do this.

  2. Click the Input Data Edit button in the toolbox. You are now in Input Data Edit mode.

  3. Find a bus you want to modify, move the cursor over the bus, and click the left mouse button. The Input Data Edit Box appears with data text boxes filled with the values associated with the bus you clicked.

  4. Change any of the values to new ones or type new values in blank text boxes. See the Record Formats for information on models and values. When you have values correctly typed (there is some data entry checking), click the Apply button at the bottom of the box to modify the bus data in the resident base case data.

Adding a Branch

You can add a branch to a resident base case. Adding a branch means to create a new connection between existing buses, which adds a new branch record within IPF’s data structure. You can add as many as you want up to IPF’s maximum limit. Branches are always associated with their terminating buses, so you access branches through buses.

To add a branch:

  1. Make sure you have system data loaded. See Opening Files to find out how to do this.

  2. Click the New Branch icon in the toolbox in the main window. This puts you in the Add Branch mode.

  3. Move into the display area where you will note that the cursor changes to a right pointing arrow. Click the first bus that you want to connect the branch to. Move to the second bus that you want the branch to connect to and click on it. A line appears on the display connecting the two bus icons. Also, the Input Data Edit Box appears.

  4. Fill in the values for the new branch as appropriate. See Record Formats for more information.

  5. Click the Add button to add the new branch record to the currently resident base case data.

Modifying a Branch

Modifying a branch means to alter any of its associated values as they exist in the currently loaded base case data. This is done through the Input Data Edit Box. Refer to Bus and Branch Editing to find out more about the Input Data Edit Box.

To modify a branch:

  1. Make sure you have system data loaded. See Opening Files to find out how to do this.

  2. Click the Input Data Edit button in the toolbox. You are now in Input Data Edit mode.

  3. Find a bus that is connected to the branch you want to modify, move the cursor over the bus, and click the left mouse button. The Input Data Edit Box appears with data text boxes filled with the values associated with the bus you clicked. But you want a branch.

  4. Find the option menu button (labeled “Bus”) at the upper right of the dialog box. This menu contains records associated with the currently selected bus. You will find continuation, transformer, branch, and other records on this menu.

  5. Press this option button to show the associated items. Drag down to the branch record of your choice and release the mouse button. Note that the Input Data Edit Box now reflects data associated with the branch you chose.

  6. Change any of the text box data to new values. When you have values correctly typed (there is some data entry checking), click the Apply button at the bottom of the box to modify the branch data in the resident base case data.

Adding, Modifying, or Deleting an Area or Intertie

For area or intertie studies, you can add, modify, or delete areas or interties, by using the main window Edit - Area/Interchange command. You can do this at any time. See figures below.

_images/Area_Intertie_Selection_Dialog_Box.png

Area Intertie Selection Dialog Box

To add an area:

  1. Click Area/Interchange on the Edit menu in main window. The Area/Intertie Selection dialog box appears.

  2. Click the Create New button. A small box appears, asking whether you want to create an Area Control (A) record or an Intertie (I) record. Click Area Control.

  3. The Area/Interchange dialog box appears. Fill in the required text boxes.

  4. Click the Add button at the bottom. The Area/Interchange dialog box closes and the new data you typed into the Area/Intertie dialog box now appears in the Area/Intertie Selection dialog box.

_images/Area_Interchange_Dialog_Box.png

Area Interchange Dialog Box

To modify an area intertie:

  1. Click Area/Interchange on the Edit menu in the main window. The Area/Intertie Selection dialog box appears.

  2. Select an item in the list window by clicking it. This action puts the selected item in the Selection text box.

  3. Click the Edit Area/Intertie button. The Area/Interchange dialog box appears.

  4. Change the data in the text boxes.

  5. Click the Modify button. The Area/Interchange dialog box closes and the new data you typed into the Area/Intertie dialog box now appears in the Area/Intertie Selection dialog box.

To delete an area:

  1. Click Area/Interchange on the Edit menu in main window. The Area/Intertie Selection dialog box appears.

  2. Select an item in the list window by clicking it. This action puts the selected item in the Selection text box.

  3. Click the Edit Area/Intertie button. The Area/Interchange dialog box appears.

  4. Click the Delete button.

To create an area continuation record:

  1. Click Area/Interchange on the Edit menu in the main window. The Area/Intertie Selection dialog box appears.

  2. Select an item in the list window by clicking it. This action puts the selected item in the Selection text box.

  3. Click the Edit Area/Intertie button. The Area/Interchange dialog box appears.

  4. Change the data in the text boxes if you need to.

  5. Click the Create Area Continuation Card button. The dialog box appears.

  6. Add zone data to the Zone text boxes.

  7. Click the Add button. The Area/Interchange dialog box closes and the new data you typed into the Area/Intertie dialog box now appears in the Area/Intertie Selection dialog box.

_images/Area_Continuation_Card_Dialog_Box.png

Area Continuation Card Dialog Box

Exploring Base Case Connectivity

Sometimes you may want to explode a portion of a large network to see how buses are locally interconnected. The idea is that you start with one bus on the display and find out what other buses are connected to it. Then, with each of these buses, you find out what buses are connected to these, and so on.

The Explode icon in the toolbox allows you to explore base case connectivity.

To explore a base case:

  1. Load just a base case file to demonstrate this function. See Opening Files to find out how to do this.

  2. Click the New Bus icon in the toolbox to enter Add Bus mode. The Input Data Edit box will come up; just close it without entering any data.

  3. Select Alpha Search on the View menu. In the Alpha Search dialog box, type the first few letters of a bus name. The alphabetical list automatically scrolls to find the bus of interest in the list. See the Alpha Search command entry in Chapter 4 for more information.

  4. Click the bus name of interest. It may already be highlighted, but you must click on it to make it the currently selected bus.

  5. Move to the blank display area. (You should still be in Add Bus mode.) Click once to make the bus icon and name appear.

  6. Move back to the toolbox and click the Explode icon. You previously established a bus that you can now explore bus connectivity with.

  7. Click the bus. You will note that any buses that are connected to your bus of interest are now shown on the display with connecting lines representing branches. You can continue exploring the network by clicking any new buses that show up. You can reveal the entire network in this way if you like (although it will probably look like a mess!)

The buses and branches are positioned by an internal algorithm since you have not loaded any underlying coordinate data. You can click the Move icon and then move the buses around the screen if you want to clean things up.

Sectionalizing a Bus

Sectionalizing a bus separates a bus into two buses and rearranges its branches between the two buses. You can also optionally create a tie line between the two buses. See figure below.

To sectionalize a bus:

  1. Make sure you have system data loaded. See Opening Files to find out how to do this.

  2. Click the Input Data Edit mode button in the toolbox. You are now in Input Data Edit mode.

  1. Select a bus by clicking it. This brings up the Input Data Edit Box. At the center bottom of the dialog box is the Sectionalize button. Click it to cause the Bus Sectionalize dialog box to appear. Note that the bus name of the currently selected bus appears in two places.

  2. Type a new bus name over the existing Bus 2 name to create a new bus.

  3. Click any branch, transformer, etc., record in the left-hand scrolling text box to transfer it to the right-hand scrolling text box. Note that you can go back and forth by clicking the appropriate records till branches, transformers, etc., are all associated with the bus you want.

  4. Click the OK button to send the sectionalized bus data to the resident base case data. If IPF detects any errors or inconsistencies, it puts up the Error dialog box. Examination of the message helps you figure out the problem.

Note

If the name you type is not accepted, IPF has found it to be a duplicate name and rejects it. If, at any point, you would like to start from the beginning, just press Reset at any time. This returns all values to the state they were at the time the dialog box first opened.

  1. Sometimes you may want to connect the old and new buses making up the sectionalized bus. Click on the Bus Tie button to create a line with impedance of 0.0 + j0.00001. You may modify this line later, if you wish

_images/Sectionalize_Operation_Completed.png

Sectionalize Operation Completed

Tapping a Line

Tapping a line means to service a new load by creating a new tap point bus on an existing line. The tapped line is effectively segmented into two lines, separated with a newly created bus. If the load is remote from the tapped point, an additional line and bus will be necessary. The new load and the new bus are connected by a new line. As with many line operations, you access line tapping through a bus that the line is connected to.

To tap a line:

  1. Make sure you have system data loaded. See Opening Files to find out how to do this.

  2. Click the Input Data Edit mode button in the toolbox.

  3. Click a bus icon that is connected to the line you want to tap. This brings up the Input Data Edit Box which is loaded with input data pertaining to the selected bus. Click and hold the option button opposite the bus name at the top of the Input Data Edit Box. The cascading menu lists all branches connected to the current bus. Drag down to the line you are interested in tapping. Be sure that this is a line and not a transformer. Selecting this item brings up the Input Data Edit Box for your line of interest. Near the center bottom of this dialog box is the Tap Line button. Click it to cause the Tap Line dialog box to appear.

  4. Initially the dialog box displays data from a previous invocation. If this is the first time it is displayed, all fields are blank. Enter the name of the bus you want to create in the dialog field Tapped Bus Name and press the Apply button. The selected line is tapped at the point depicting 50% of the total line’s reactance. You can horizontally scroll the line data within the Bus 1 side and the Bus 2 side to verify that the line resistance and reactance is split according to the sliding scale selected. Pressing the Apply button recomputes the line impedance on each side of the tapped bus without affecting any data in the Powerflow base case.

  5. Change the units (Percentage, Miles, Kilometers, or Section) to reflect your tapping criteria. Adjust the horizontal slider as necessary. Move the slider by moving the mouse cursor over it, pressing the left mouse button, and moving left or right till you find the point of the line you want to tap. Release the mouse button.The line tapping slider just above the Reverse Scale button shows the tap point according to the tapping criteria (length of the line in kilometers or miles, or percent of reactance). The line tapping slider also shows any sections the line may be divided into. Again press Apply to update the line’s impedance to reflect the slider’s current value.

  6. If the values are acceptable, click OK to export these changes to Powerflow.

  7. Click Close to cause the dialog box to disappear.

Solving a Network Case

Solving a network case (or base case) causes IPF to calculate bus voltages that satisfy the network constraints as they exist within the currently resident base case data. This is usually done after you have loaded a base case and made some modifications to reflect the conditions of the system you want to study. However, you may solve as soon as you have loaded any system data. You do not need to load a coordinate or change file to solve a case. See figure below for a typical display after a case solution.

_images/Network_Display_After_Solution.png

Network Display After Solution

To solve a base case:

  1. Make sure that you have previously loaded a base case or netdata file. See Opening Files if you have not.

  2. Choose Solve Case from the Process menu in the IPF main window. The Solve dialog box opens and you are presented with a number of options. See the figure below. Note that default values are set for you. If these suit your case, click the Solve button. If the defaults are not appropriate for your case, change them. Then solve the case. See Chapter 4 for a discussion of the options.

The solution may take anywhere from a few seconds to minutes depending on the number of buses in the base case. After the solution is complete, the display shows some of the calculated data.

Bus and Branch Editing

Bus and branch data editing are most often accomplished through the Input Data Edit Box. This dialog box is brought up on the display whenever you click a bus displayed in the main window. The specific data associated with the bus you click fills the text boxes of the Input Data Edit Box. You can change any of the values to new values. You can then store the changed data in the memory-resident bus and branch database, solve the case with the new data values, and optionally save the changes permanently in a file.

Note

See the Network Data Edit menu item entry in this chapter for another way to edit bus and branch data.

Each of the text box fields in a given instance of the Input Data Edit Box corresponds to a record field for a bus, line, or transformer type as documented in the Record Formats section. If you are unsure of the meaning of the fields for a particular bus, line, or transformer type, look it up in that section.

In the Record Formats section, field width, decimal point placement, and sign are specified for each field. Real number fields have a position where a decimal point is implied, i.e. as long as you correctly position your digits, you need not enter a decimal point a a .pfc file or NETWORK_DATA file. However, in the Input Data Edit Box you should always enter a decimal point. Sufficient room has been allowed for this in each field. The GUI will format your data correctly so it fits the field on a standard input record.

When you enter data into the Input Data Edit Box text boxes, the GUI checks to see whether you have entered values correctly. Specifically, it checks for all characters being numeric, having a minus sign (in the proper place), or having a decimal point (period). All other characters are rejected and a warning bell sounds. Other basic checks for valid data are also operating in during data entry. However, it may still be possible to enter invalid data that only shows up when a power flow solution is attempted.

Bus Editing

Bus input data dialogs are accessed directly by clicking on a bus icon in the display, or by selecting a bus name on the Alpha List. Their appearance varies according to the type of the bus. To change the bus type of a bus, click the button labeled Type, near the Owner and Zone fields. This option button pops up a menu showing all the bus types accepted by IPF. If you click on a different type than was originally displayed, the dialog will change into one appropriate to that bus type. If you click the Modify button, the bus will be changed to a different type. You may have to supply more (or different) data in other fields in order for the change to be legal.

Branch and Other Component Editing

You cannot select a branch directly. Branch data is accessed by selecting a bus that is connected to the line or transformer you want to edit. Then, once the Input Data Edit Box shows a bus connected to your line of interest, you pick the line by using the option button labeled Bus, in the upper right corner of the box. Press and drag down to select the one you want. The dialog box changes to reflect the fields and parameters characteristic of lines.

The Bus option menu also contains other bus-related components, or records, such as switched reactance (X) data, bus continuation data, PQ curves, etc. Drag down and release to select any of these you want to edit.

Adding New Components

New buses are added by using the New Bus tool in the main menu toolbox. See Adding a Bus and Related Components for details on this process. New branches can be added only if both terminal buses exist. You can add branches graphically by using the New Branch tool, or by going through the Input Data Edit Box for one of the terminal buses. Other bus-related components can only be added through the dialog box. To add components to a bus, press the option button labeled New Component and drag down to the desired item. Items which are grayed out are not appropriate for this type of bus. For example, switched reactance (X) data can only be added to a BX type bus.

When you release the mouse button, the data dialog for the selected item will appear. You fill in the desired data fields, and click the Add button at the bottom to add it to the currently resident base case data. Notice that the Modify button is grayed out on this dialog.

Input Data Edit Dialog Boxes

The following dialog boxes are all accessed from the Input Data Edit Dialog Box. The dialog boxes are arranged with buses first and branch components last.

Input Data Edit Dialog Boxes

Dialog

Box Description

B-BLANK BUS

Adds bus data for modeling load bus.

BC BUS

Adds bus data for a bus controlled by a BG bus.

BD BUS

Supplies data for a two terminal dc bus.

BE BUS

Adds bus data for a bus that holds its voltage to a specified value.

BF BUS

Supplies data for a special-purpose bus for the NewtonRaphson solution method.

BG BUS

Adds bus data for a bus that controls the voltage of a remote BC bus.

BM BUS

Supplies data for a multi-terminal dc bus.

BQ BUS

Adds bus data for a bus that holds its voltage to a specified value within reactive limits.

BS BUS

Adds bus data for the slack (or swing) bus.

BT BUS

Adds bus data for a bus that maintains its voltage with an LTC transformer.

BV BUS

Adds bus data for a bus that holds its net reactive power within a user-specified voltage range.

BX BUS

Adds bus data for a bus that controls its local voltage by switching capacitors/reactors in and out.

CONTINUATION BUS

Adds additional data to an existing bus record.

SWITCHED REACTANCE

Adds data for voltage controlled shunt device installations.

PQ CURVE

Adds PQ curve data for calculation of Q limits.

SECTIONALIZATION

Provides for the sectionalization of a bus.

LINE TAPPING

(Not yet available) Provides for tapping of lines.

TRANSMISSION LINE

Adds data for a balanced transmission line.

PHASE SHIFTER

Adds data for phase shifting transformers.

TRANSFORMER

Adds data for two-winding transformers.

REGULATING TRANSFORMER

Adds data to give fixed transformers or phase shifters automatic regulating or control status.

EQUIVALENT NETWORK

Adds data for an asymmetrical pi type line.

AC Bus Input Data Boxes

This box will look slightly different, depending on the bus type. All of the AC bus data fields are described below; specific differences are covered under the various bus types. You must click separately in each field that you want to alter. Text entry is always in Insert mode, meaning that you cannot type over a character or number; you must delete it first. Note that when a field is described as a “real number,” you should always enter a decimal point. See below for an example of a typical bus input data dialog box.

_images/Input_Data_Edit_Box_Showing_B-Blank_Bus_Data.png

Input Data Edit Box Showing B-Blank Bus Data.png

Name. An eight character maximum, alphanumeric string designating a bus name. The string must start with an alpha character. The name should be unique. This name is placed in the first text box from the left. The right text box should have a five character maximum numeric string representing the bus’s base kV rating.

Bus. An option button that allows you access to other records that are associated with the currently displayed bus. Press on this button and drag down to select an existing branch or other component. The dialog box transforms into the dialog for the selected component.

Owner. Three character maximum, alphanumeric string designating a bus owner.

Zone. Two character maximum, alphanumeric string designating the zone the bus is in.

Type. An option button that changes the dialog box to reflect different bus types. The types are: B `` (B-blank), ``BC, BE, BF, BG, BQ, BS, BT, BV, and BX. You cannot change an AC bus into a DC bus using this button.

Load P. Five character maximum, real number designating real load in megawatts (MW).

Load Q. Five character maximum, real number designating reactive load in megavoltamperes reactive (MVAR).

Shunt P. Four character maximum, real number designating the shunt admittance load in megawatts (MW) at the base kV of the bus.

Shunt Q. Four character maximum, real number designating shunt admittance in megavoltamperes reactive (MVAR). A positive value is capacitive; a negative value is inductive. The minus sign goes in front of the number.

P Max. Four character maximum, real number designating the maximum real power generation in megawatts (MW).

P Gen. Five character maximum, real number designating scheduled real power generation in megawatts (MW).

Q Sched. Five character maximum, real number designating scheduled reactive power in megavoltamperes reactive (MVAR). May be positive or negative.

Q Max. Five character maximum, real number designating maximum reactive power in megavoltamperes reactive (MVAR). Generally positive.

Q Min. Five character maximum, real number designating minimum reactive power in megavoltamperes reactive (MVAR). Generally negative. The minus sign goes in front of the number.

V Hold. Four character maximum, real number designating a voltage to hold for the bus, in per unit.

V Max. Four character maximum, real number designating a maximum voltage limit in per unit.

V Min. Four character maximum, real number designating a minimum voltage limit in per unit.

Sectionalize. A button that brings up the Sectionalize dialog box. See Sectionalize Dialog Box in this section.

New Component. A tag for the option button that allows you to add a new bus-related component such as a branch, X data, etc. Add. A button that adds a new record to the database.

Modify. A button that modifies the record.

Reset. A button that restores text box displays to their original values (before any changes were made).

Delete. A button that deletes (removes) a record from the database.

Outage. (Not yet implemented.)

Close. A button that causes the dialog box to close and disappear from the display without making any modifications to the record.

B-Blank Bus

The B-blank dialog box supplies data for modeling the typical load bus. See the B-blank record in AC Bus Data (B-blank).

V Max. Four character maximum, real number designating a maximum voltage limit in per unit.

V Min. Four character maximum, real number designating a minimum voltage limit in per unit.

The voltage limit fields take effect only if the voltage of the B-blank bus is being controlled by a remote device.

BC Bus

The BC dialog box supplies data for a bus controlled by one or more BG type buses. See the BC record in AC Bus Data (BC).

V Hold. Four character maximum, real number designating a voltage to hold for the bus, in per unit.

BE Bus

The BE dialog box supplies data for a bus that holds its voltage to a specified value. See the BE record in AC Bus Data (BE).

Q Max. Five character maximum, real number designating maximum reactive power in megavoltamperes reactive (MVAR). Generally positive.

Q Min. Five character maximum, real number designating minimum reactive power in megavoltamperes reactive (MVAR). Generally negative. The minus sign goes in front of the number.

V Hold. Four character maximum, real number designating a voltage to hold for the bus, in per unit.

BF Bus

The BF dialog box supplies data for a special-purpose bus for the Newton-Raphson solution method. It holds the specified voltage until the P-solution has converged, then acts like an ordinary load bus (B-blank). See the BF record in AC Bus Data (BF).

Q Max. Five character maximum, real number designating maximum reactive power in megavoltamperes reactive (Mvar). Generally positive.

Q Min. Five character maximum, real number designating minimum reactive power in megavoltamperes reactive (Mvar). Generally negative. The minus sign goes in front of the number.

V Hold. Four character maximum, real number designating a voltage to hold for the bus, in per unit.

BG Bus

The BG dialog box supplies data for a bus that controls the voltage of a remote BC bus. See the BG record in ac-bus-data-bg.

Q Max. Five character maximum, real number designating maximum reactive power in megavoltamperes reactive (MVAR). Generally positive.

Q Min. Five character maximum, real number designating minimum reactive power in megavoltamperes reactive (MVAR). Generally negative. The minus sign goes in front of the number.

V Max. Four character maximum, real number designating a maximum voltage limit in per unit.

V Min. Four character maximum, real number designating a minimum voltage limit in per unit

Remote Bus. An eight character maximum, alphanumeric string designating the remote bus to be voltage controlled (a BC type bus).

PCS. A three character maximum, numeric string designating the percentage of VARS supplied by this bus to control the remote bus voltage.

BQ Bus

The BQ dialog box supplies data for a bus that holds its voltage to a specified value within reactive limits. See the BQ record in AC Bus Data (BQ).

Q Max. Five character maximum, real number designating maximum reactive power in megavoltamperes reactive (MVAR). Generally positive.

Q Min. Five character maximum, real number designating minimum reactive power in megavoltamperes reactive (MVAR). Generally negative. The minus sign goes in front of the number.

V Hold. Four character maximum, real number designating a voltage to hold for the bus, in per unit.

BS Bus

The BS dialog box supplies data for the system slack (or swing) bus. See the BS record in AC Bus Data (BS).

Q Sched. Five character maximum, real number designating scheduled reactive power in megavoltamperes reactive (MVAR). May be positive or negative.

V Hold. Four character maximum, real number designating a voltage to hold for the bus, in per unit.

Angle. Four character maximum, real number designating a voltage phase angle in degrees. Blank is translated to an angle of zero.

BT Bus

The BT dialog box supplies data for a bus that maintains its voltage with an LTC transformer. See the BT record in AC Bus Data (BT).

Q Sched. Five character maximum, real number designating scheduled reactive power in megavoltamperes reactive (MVAR). May be positive or negative.

V Hold. Four character maximum, real number designating a voltage to hold for the bus, in per unit.

BV Bus

The BV dialog box supplies data for a bus that holds its net reactive power within a user-specified voltage range. See the BV record in AC Bus Data (BV).

Q Sched. Five character maximum, real number designating scheduled reactive power in megavoltamperes reactive (MVAR). May be positive or negative.

V Max. Four character maximum, real number designating a maximum voltage limit in per unit.

V Min. Four character maximum, real number designating a minimum voltage limit in per unit.

BX Bus

The BX dialog box supplies data for a bus that controls its own or a remote bus’s voltage by switching capacitors or reactors in and out. See the BX record in AC Bus Data (BX).

Q Max. Five character maximum, real number designating maximum reactive power in megavoltamperes reactive (MVAR). Generally positive.

Q Min. Five character maximum, real number designating minimum reactive power in megavoltamperes reactive (MVAR). Generally negative. The minus sign goes in front of the number.

V Max. Four character maximum, real number designating a maximum voltage limit in per unit.

V Min. Four character maximum, real number designating a minimum voltage limit in per unit.

Remote Bus. An eight character maximum, alphanumeric string designating the remote bus to be voltage controlled.

BD Bus

The BD dialog box supplies data for a two-terminal DC bus. See the BD record two-terminal–dc-bus-data-bd.

_images/Input_Data_Edit_Box_Showing_BD_Bus.png

Input Data Edit Box Showing BD Bus

Number of Bridges. Two digit integer designating the number of bridges per dc circuit (number of valves serially connected).

Smoothing Reactor. Five character maximum, real number designating smoothing inductance in millihenries.

Min Firing Angle. Five character maximum, real number designating minimum firing angle (\(alpha_min\)) in degrees, for rectifier operation.

Max Firing Angle. Five character maximum, real number designating maximum firing angle (\(alpha_stop\)) in degrees, for inverter operation.

Valve Drop. Five character maximum, real number designating valve voltage drop per bridge, in volts.

Bridge Rating. Five character maximum, real number designating maximum bridge current rating in amps.

Commutating Bus. Eight character maximum, alphanumeric string designating the commutating bus name. This is the bus on the ac system side of the commutating transformer bank.

BM Bus

The BM dialog box supplies data for a multi-terminal dc bus. See the BM record Multi-Terminal DC Bus (BM).

_images/Input_Data_Edit_Box_Showing_BM_Bus.png

Input Data Edit Box Showing BM Bus

Number of Bridges. Two digit integer designating the number of bridges per dc circuit (number of converters serially connected).

Smoothing Reactor. Five character maximum, real number designating smoothing inductance in millihenries.

Min Firing Angle. Five character maximum, real number designating minimum ignition delay angle (\(alpha_min\)) in degrees.

Max Firing Angle. Five character maximum, real number designating maximum ignition delay angle (\(alpha_stop\)) in degrees.

Valve Drop. Five character maximum, real number designating converter valve drop per bridge, in volts.

Bridge Rating. Five character maximum, real number designating bridge current rating (maximum converter current) in amps.

Commutating Bus. Eight character maximum, alphanumeric string designating the commutating bus name.

Converter Type. Single character alpha string designating the converter code. R indicates normal operation as a rectifier; I is normal operation as an inverter. M indicates an inverter with current margin, and blank indicates a passive dc tap.

Ignition Delay Angle. Three character maximum, real number designating the normal ignition delay angle (\(alpha_N\)) for a rectifier, or normal extinction angle (\(gamma_N\)) for an inverter, in degrees.

Min Extinction Angle. Three character maximum, real number designating the minimum ignition angle (\(alpha_min\)) for a rectifier, or minimum extinction angle (\(gamma_0\)) for an inverter, in degrees.

Converter DC Power. Six character maximum, real number designating the scheduled dc bus load (net converter dc output power) in megawatts (MW) at the base kV of the bus.

Converter DC Voltage. Five character maximum, real number designating the scheduled dc bus kV (converter dc voltage).

Continuation Bus

The continuation bus dialog box is used for extending the data for a given bus record. You can specify additional generation, load, and shunt admittance. A typical use is the case where several owners have load at the same bus. Also, shunt specified on this record is considered to be fixed, rather than variable. See the +` (plus) record Continuation Bus Data (+).

_images/Continuation_Bus_Dialog_Box.png

Continuation Bus Dialog Box

Name. An eight character maximum, alphanumeric string, plus a five character maximum real number, designating the name of the bus that this continuation data is associated with. Code Type. An option button that specifies the type of continuation record: +blank, +A, +C, +F +I, +N, +P, or +S. See the IPF Batch User’s Guide for an explanation of these codes.

Owner. Three character maximum, alphanumeric string designating the owner of this particular load, shunt, etc. This will usually be different from the owner of the bus itself.

Code Year. Two character maximum, alphanumeric string. See Continuation Bus Data (+). for details.

Load P. Five character maximum, real number designating real load in megawatts (MW).

Load Q. Five character maximum, real number designating reactive load in megavoltamperes reactive (Mvar).

Shunt P. Four character maximum, real number designating the shunt admittance load in megawatts (MW) at the base kV of the bus.

Shunt Q. Four character maximum, real number designating the shunt reactance load in megavoltamperes reactive (MVar) at the base kV of the bus.

Gen P. Five character maximum, real number designating scheduled real power in megawatts (MW) as a real number.

Gen Qmax. Five character maximum, real number designating maximum reactive power in megawatts (MW).

Gen Qmin. Five character maximum, real number designating minimum reactive power in megawatts (MW).

Switched Reactance

The switched reactance bus dialog box is used for specifying steps in a switched reactance BX bus. See the X record Switched Reactance (X) for detailed information.

_images/Switched_Reactance_Dialog_Box.png

Switched Reactance Dialog Box

Name. An eight character maximum, alphanumeric string, plus a five character maximum real number, designating the name of the BX bus that this data is associated with.

Remote Bus. An eight character maximum, alphanumeric string, plus a five character maximum real number, designating the name of the remote bus to be voltage controlled.

Owner. A three character maximum, alphanumeric string designating the bus owner.

Steps. An integer from 1 to 9, designating the number of increments of shunt of this magnitude.

MVAR. A five character maximum, real number designating a block of switchable reactive shunt in megavoltamperes reactive (Mvar).

PQ Curve

The PQ Curve dialog box allows you to specify points for a generator reactive capability curve for a type BE, BG, BQ, BX, or BS bus. See the QP` record Reactive Capability Curves (QP, QX, QN) for detailed information.

To specify P Gen, Q Max, and Q Min values, type the values in the bottom text entry boxes. Click the Insert button to transfer the values from the text entry boxes to the list boxes above. Rows of values are associated across. Six rows of values are sufficient for most curves. Once you have values typed in and entered, you can replace or delete them, a row at a time.

_images/PQ_Generation_Dialog_Box.png

P-Q Generation Dialog Box

P Gen. Five character maximum, real number designating a particular level of real power generation in megawatts (MW) which is to be associated with certain Q limits. Values may be specified in per unit on Pmax, or in MVA. All values for a curve must be specified the same way.

Q Max. Five character maximum, real number designating maximum reactive power (positive) in megavoltamperes reactive (Mvar) that can be produced by the generator when operating at this level of real power output. Values may be specified in per unit on Pmax, or in MVA. All values for a curve must be specified the same way.

Q Min. Five character maximum, real number designating minimum reactive power (negative) in megavoltamperes reactive (Mvar) that can be absorbed by the generator when operating at this level of real power output. Values may be specified in per unit on Pmax, or in MVA. All values for a curve must be specified the same way.

Insert. A button that inserts the values in the bottom text entry boxes into the text lists above. Replace. A button that replaces the selected row of values in the list above with the current values in the bottom text entry boxes.

Delete. A button that deletes the selected text list row of values.

Active. A radio button that makes the curve defined by the values in the text list rows active, that is, IPF uses the curve to determine what the Q limits will be, based on the current level of Pgen specified in the bus record.

Inactive. A radio button that makes the curve inactive, that is, IPF does not calculate new Q limits whenever Pgen is changed, but uses whatever it currently has stored.

MVA. The values for the PQ curves may be specified in MVA or per unit. Clicking the MVA radio button tells the program to expect values in MVA.

Per Unit. The values for the PQ curves may be specified in MVA or per unit. Clicking the Per Unit radio button tells the program to expect values in per unit on Pmax.

Add. A button that adds a new three-record point set to the current curve data for this bus.

Modify. A button that modifies the curve data. (Not available.)

Reset. A button that restores text box values to their original values (before any changes were made).

Delete. A button that deletes (removes) the curve data from the database.

Outage. (Not applicable.)

Close. A button that causes the dialog box to close and disappear from the display without making any modifications.

Sectionalization

The Sectionalize Bus dialog box allows you to split a bus to create two buses, with existing branches divided between them. You can sectionalize a bus at any time. You get to this dialog box from the Sectionalize button in the Input Data Edit dialog box for the bus you want to split.

When the Sectionalize Bus dialog box first comes up, it assumes the current bus name and information from the Input Data Edit dialog box. Note that the name of the current bus appears in both text boxes found at the top of the dialog box. You change the name in the right-hand box to create a new bus record, which will inherit the bus type and voltage of the old bus.

Once you have changed the bus name to a new one, you can arrange the branch information in the list boxes to define the new connections. The list box under the left-hand text box applies to the bus name on the left side, and the list on the right to the right-hand bus name. If you click on a record in either box, it will be transferred to the other. Use the horizontal and vertical scroll bars to see information that is hidden.

After the two buses and their associated branches are satisfactory, you can optionally press the Bus Tie button to create a “bus tie” record, which is a line with impedance \(0.0 + j0.00001\) between the new bus and the old one. The bus tie record will appear in the text box.

_images/Sectionalize_Bus_Dialog_Box.png

Sectionalize Bus Dialog Box

Sectionalize Bus 1. This text box contains the bus type, name, and base kV of the current bus you are working with in the Input Data Edit Box.

Sectionalize Bus 2. This text box initially contains the name of the current bus. You can change this to be any new bus name. The new bus inherits the base kV, ownership, and bus type of Bus 1.

Bus Tie. Click this button if you want to tie the two buses with a low impedance tie line. This creates a bus tie record. The branch record shows up in the text box. OK. Click this button to cause the new data to be saved in the memory-resident bus and branch database. No changing action occurs until you click OK. The dialog box closes and returns you to the Input Data Edit Box.

Reset. Click this button if you want to return to the initial state of a just opened dialog box. All changes that you have made are erased and returned to initial conditions.

Close. Click this button if you have decided that no save action is necessary, that is, you do not want to make any sectionalization changes to the memory-resident bus and branch database. Clicking this button closes the dialog box and returns you to the Input Data Edit Box.

Line Tapping (may not be available)

Tapping a line means to service a new load by creating a new tap point bus on an existing line. The tapped line is effectively segmented into two lines, separated with a newly created bus. If the load is remote from the tapped point, an additional line and bus will be necessary. The new load and the new bus are connected by a new line. As with many line operations, you access line tapping through a bus that the line is connected to.

_images/Line_Tapping_Dialog_Box.png

Line Tapping Dialog Box

Bus 1 Line Data. This text box displays the lines between bus 1 and the tapped bus. Initially, it contains all the lines between Bus 1 and Bus 2.

Bus 2 Line Data. This text box displays the lines between bus 1 and the tapped bus. Initially, it is empty.

Scale Value Radio Buttons. These ratio buttons identify the line tap point in terms of three different criteria: (1) percent of reactance from bus 1, (2) the distance from bus 1, (3) the section number. Note that transformers and series capacitors (X < 0) have zero (0) length and cannot be tapped.

Scale Slide. A dynamic, moveable slider that shows the proportion of the selected scale on the line between Bus 1 and Bus 2. The slider value changes according to what scale value radio button is currently active.

Base 1 Name. A bus name and base kV bus identifier specifying the terminal 1 bus of the line to be tapped.

Base 2 Name. A bus name and base kV bus identifier specifying the terminal 2 bus of the line to be tapped.

Reverse Scale. A button that flips the scale values from one end to the other.

Tapped Bus Name. The name and base kV of the new bus created at the tap point.

Send. Click this button to cause the line tapping operation data to be saved in the memory-resident bus and branch database. The dialog box closes and returns you to the Input Data Edit Box.

Calculate. Click this button to see the effects of the slider operation. This action does not send any data to Powerflow.

Cancel. A button that closes the dialog box and causes no further action.

Close. Click this button if you have decided that no save action is necessary, that is, you do not want to make any sectionalization changes to the memory-resident bus and branch database. Clicking this button closes the dialog box and returns you to the Input Data Edit Box.

Help. (Not yet implemented)

Transmission Line

The transmission line dialog box specifies the identification and electrical characteristics of a balanced pi line, section of a line, or series capacitor. See the L record Balanced Transmission Line Branch (L).

_images/Transmission_Line_Dialog_Box.png

Transmission Line Dialog Box

Name. Two eight character maximum, alphanumeric strings designating the buses. The strings must start with an alpha character. The first name is placed in the first text box from the left. The next text box should have a four character maximum numeric string representing the bus’s base kV rating. The second bus name and its base kV are to the right of the first.

Metering. An integer (or blank) flag having three possible values: 1 means to meter at the bus 1 end; 2 means to meter at the bus 2 end; and blank means to let the program decide on the following criteria — (1) when bus ownership differs from bus ownership, meter at the point where line ownership differs from bus ownership, or (2) when both buses have the same ownership, meter at bus 1 location.

Owner. A three character alphanumeric code representing ownership of the branch. Circuit ID. A single alphanumeric character representing the circuit identification. Section. An integer (1-9) representing the section number for making an equivalent for series elements. The elements are assembled in ascending numeric order. This may be blank or zero if the line has only one section.

Resistance (R). A six digit real number representing the per unit resistance R.

Reactance (X). A six digit real number representing the per unit reactance X.

Admittance (G/2). A six digit real number representing the per unit admittance G.

Susceptance (B/2). A six digit real number representing the per unit susceptance B.

Number of Parallels. An integer representing the number of parallel circuits represented by this record.

Miles. A real number indicating the line length. Note: if a branch is composed of individual sections, then the total line length is the sum of mileage of each section. Also, note that series capacitors (X < 0) have no mileage.

Current Ratings. Real numbers that are conductor current ratings in amps. Nominal is the normal rating based on the line construction and conductor size. Thermal takes into account the effect of ambient temperature and other environmental factors upon the maximum permissible temperature of the conductor, usually for short time periods. Bottleneck is the minimum rating of the line including other series connected components, such as circuit breakers, fuses, or disconnect switches.

Calculate Impedance. A button that allows you to compute the electrical parameters given the conductor size and type, and tower geometry and length.

Tap Line. A button that allows you to tap a line with a newly added bus.

Add. A button that adds a new record to the database.

Modify. A button that modifies the record.

Reset. A button that restores text box values to their original values (before any changes were made).

Delete. A button that deletes (removes) a record from the database.

Outage. (Not yet implemented.)

Close. A button that causes the dialog box to close and disappear from the display without making any modifications to the record.

Phase Shifter

The Phase Shifter dialog box allows you to add data for phase shifting transformers. See the T Transformer Data (T, TP) and R records Regulating Transformer (R, RV, RQ, RP, RN, RM) for more details.

_images/Phase_Shifter_Dialog_Box.png

Phase Shifter Dialog Box

Name. Two eight character maximum, alphanumeric strings designating the buses. The strings must start with an alpha character. The first name is placed in the first text box from the left. The next text box should have a four character maximum numeric string representing the bus’s base kV rating. The second bus name and its base kV are to the right of the first.

Metering. An integer (or blank) flag having three possible values: 1 means to meter at the bus 1 end; 2 means to meter at the bus 2 end; and blank means to let the program decide on the following criteria — (1) when bus ownership differs from bus ownership, meter at the point where line ownership differs from bus ownership, or (2) when both buses have the same ownership, meter at bus 1 location.

Section. An integer (1-9) representing the section number for making an equivalent for series elements. The elements are assembled in ascending numeric order.

Circuit ID. A single alphanumeric character representing the circuit identification.

Owner. A three character alphanumeric code representing ownership.

Parallels. An integer representing the number of parallel transformers in this record.

Resistance (R). A six digit real number representing per unit equivalent resistance R due to copper loss.

Reactance (X). A six digit real number representing per unit leakage reactance X.

Admittance (G). A six digit real number representing per unit shunt equivalent core loss conductance G (iron losses).

Susceptance (B). A six digit real number representing per unit shunt magnetizing susceptance B. This is always converted to a negative number by the program.

Phase Shift. A five digit real number representing the fixed phase shift in degrees that describes bus 1 relative to bus 2.

Tap 2 kV. A five digit real number representing the fixed bus 2 tap. It is possible for a transformer to have both a phase shift and a tap.

MVA Ratings. All MVA ratings (Nominal, Thermal, Bottleneck, and Emergency) are represented by four digit real numbers. Nominal is the normal rating based on the construction. Thermal takes into account the effect of ambient temperature and other environmental factors upon the maximum permissible temperature of the conductor, usually for short time periods. Bottleneck is the minimum rating of the transformer including other series connected components, such as circuit breakers, fuses, or disconnect switches.

Add. A button that adds a new record to the database.

Modify. A button that modifies the record.

Reset. A button that restores text box values to their original values.

Delete. A button that deletes (removes) a record from the database.

Outage. (Not yet implemented.)

Close. A button that causes the dialog box to close and disappear from the display without making any modifications to the record.

Transformer

The transformer dialog box allows you to add data for fixed tap transformers. See the T record Transformer Data (T, TP).

_images/Transformer_Dialog_Box.png

Transformer Dialog box

Name. Two eight character maximum, alphanumeric strings designating connected buses. The strings must start with an alpha character. The first name is placed in the first text box from the left. The next text box should have a four character maximum numeric string representing the bus’s base kV rating. The second bus name and its base kV are to the right of the first.

Metering. An integer (or blank) flag having three possible values: 1 means to meter at the bus 1 end; 2 means to meter at the bus 2 end; and blank means to let the program decide on the following criteria — (1) when bus ownership differs from bus ownership, meter at the point where line ownership differs from bus ownership, or (2) when both buses have the same ownership, meter at bus 1 location.

Section. An integer (1-9) representing the section number for making an equivalent for series elements. This may be zero or blank if the branch has only one section.

Circuit ID. An alphanumeric character representing the circuit identification.

Owner. A three character alphanumeric code representing ownership.

Parallels. An integer representing the number of parallel transformer banks in this record.

Resistance (R). A six digit real number representing per unit equivalent resistance R due to copper loss.

Reactance (X). A six digit real number representing per unit leakage reactance X.

Admittance (G). A six digit real number representing per unit shunt equivalent core loss conductance G (iron losses).

Susceptance (B). A six digit real number representing per unit shunt magnetizing susceptance B. This is always converted to a negative number by the program.

Tap 1 kV. A five digit real number representing the fixed bus 1 tap.

Tap 2 kV. A five digit real number representing the fixed bus 2 tap.

MVA Ratings. All MVA ratings (Nominal, Thermal, Bottleneck, and Emergency) are represented by four digit real numbers. Nominal is the normal rating based on the construction. Thermal takes into account the effect of ambient temperature and other environmental factors upon the maximum permissible temperature of the conductor, usually for short time periods. Bottleneck is the minimum rating of the transformer including other series connected components, such as circuit breakers, fuses, or disconnect switches.

Add. A button that adds a new record to the database.

Modify. A button that modifies the record.

Reset. A button that restores text box values to their original values (before any changes were made).

Delete. A button that deletes (removes) a record from the database.

Outage. (Not yet implemented.)

Close. A button that causes the dialog box to close and disappear from the display without making any modifications to the record.

Regulating Transformer

The regulating transformer dialog box allows you to add data for regulating transformers. See the R record Regulating Transformer (R, RV, RQ, RP, RN, RM).

_images/Regulating_Transformer_Dialog_Box.png

Regulating Transformer Dialog Box

Name. Two eight character maximum, alphanumeric strings designating connected buses. The strings must start with an alpha character. The first name is placed in the first text box from the left. The next text box should have a four character maximum numeric string representing the bus’s base kV rating. The second bus name and its base kV are to the right of the first.

Owner. A three character alphanumeric code representing ownership.

R (subtypes). An option button allowing you to choose types R-blank, RV, RQ,RP, RN, or RM. See the R record in the IPF Batch User’s Guide for a description of these types.

Low Alpha Fixed. A radio button that identifies the fixed tap side as at the low alpha order bus name terminal. Note that this field is necessary only to resolve ambiguity if Min Tap and Max Tap cannot establish the variable tap side. Low Alpha Fixed is the default.

Bus 1 Variable. A radio button that identifies the variable tap side as at the bus 1 terminal. Note that this field is necessary only to resolve ambiguity if Min Tap and Max Tap cannot establish the variable tap side.

Bus 2 Variable. A radio button that identifies the variable tap side as at the bus 2 terminal. Note that this field is necessary only to resolve ambiguity if Min Tap and Max Tap cannot establish the variable tap side.

Remote Bus. An eight character maximum, alphanumeric string designating the remote bus to be voltage-controlled.

Min Tap. A real number in kV that specifies the minimum tap on the variable tap side.

Max Tap. A real number in kV that specifies the maximum tap on the variable tap side.

Number of Taps. An integer specifying the number of taps on the variable tap side. This must be greater than one for discrete taps; zero (0) indicates continuous taps. Zero is the default.

Add. A button that adds a new record to the database.

Modify. A button that modifies the record.

Reset. A button that restores text box values to their original values (before any changes were made).

Delete. A button that deletes (removes) a record from the database.

Outage. (Not yet implemented.)

Close. A button that causes the dialog box to close and disappear from the display without making any modifications to the record.

Equivalent Network

The equivalent network dialog box allows you to add data for an equivalent, unbalanced pi transmission line branch. See the E record Equivalent Transmission Line Branch (E).

_images/Equivalent_Network_Dialog_Box.png

Equivalent Network Dialog Box

Name. Two eight character maximum, alphanumeric strings designating connecting buses. The strings must start with an alpha character. The first name is placed in the first text box from the left. The next text box should have a four character maximum numeric string representing the bus’s base kV rating. The second bus name and its base kV are to the right of the first.

Metering. An integer (or blank) flag having three possible values: 1 means to meter at the bus 1 end; 2 means to meter at the bus 2 end; and blank means to let the program decide on the following criteria — (1) when bus ownership differs from bus ownership, meter at the point where line ownership differs from bus ownership, or (2) when both buses have the same ownership, meter at bus 1 location.

Owner. A three character alphanumeric code representing ownership.

Circuit ID. An alphanumeric character representing the circuit identification.

Section. An integer (1-9) representing the section number for making an equivalent for series elements. The elements are assembled in ascending numeric order. This may be blank or zero if the line has only one section.

Resistance (R). A six digit real number representing the per unit resistance R through the branch from bus 1 to bus2.

Reactance (X). A six digit real number representing the per unit reactance X through the branch from bus 1 to bus 2.

Admittance (G1). A six digit real number representing the line’s per unit shunt conductance G at the bus 1 terminal.

Susceptance (B1). A six digit real number representing the line’s per unit shunt susceptance B at the bus 1 terminal.

Admittance (G2). A six digit real number representing the line’s per unit shunt conductance G at the bus 2 terminal.

Susceptance (B2). A six digit real number representing the line’s per unit shunt susceptance B at the bus 2 terminal.

Number of Parallels. An integer representing the number of parallel transformer banks in this record.

Current Ratings. Real numbers that are conductor current ratings in amps. Nominal is the normal rating based on the line construction and conductor size. Thermal takes into account the ambient temperature and other environmental factors upon the maximum permissible temperature of the conductor, usually for short time periods. Bottleneck is the minimum rating of the line including other series connected components, such as circuit breakers, fuses, or disconnect switches.

Add. A button that adds a new record to the database.

Modify. A button that modifies the record.

Reset. A button that restores text box values to their original values (before any changes were made).

Delete. A button that deletes (removes) a record from the database.

Outage. (Not yet implemented.)

Close. A button that causes the dialog box to close and disappear from the display without making any modifications to the record.

Customizing the GUI (XGUI)

X resources are X system components managed in common by the X server. Examples of resources are colors, fonts and their characteristics, default size and position of windows, and default file names for dialog boxes. You can change many of these resource values in the IPF gui.

You customize IPF gui, as you do other X clients, by changing the client’s X resources file. This is the XGUI file in your home (logon) directory. It is an ASCII text file, so you can alter it with any text editor. It is recommended that only advanced users edit XGUI to any extent; when making changes to X resource values it is very easy to cause problems that you won’t know how to fix. For example, if you accidentally changed some branch colors to the main window’s background display color, you will not be able see those branches, even though they are still there! Caution is urged when you modify X resource values and specifications.

However, there are a few items that anybody can and will probably want to change. These are covered below.

Note

After you make changes to the XGUI file, you may not see changes in your client (IPF) till you exit the X Window System itself. Exiting and restarting IPF is not sufficient! You must exit IPF and the X Window System and restart both.

XGUI Resources

As you look at the following XGUI file excerpts, note these characteristics:

  • For the most part, each line specifies a resource and value for the resource.

  • Each resource specification consists of a descriptive resource name followed by a colon (:)

followed by a value.
  • Values may be numeric or alpha.

  • Comment lines are preceded by an exclamation point (!).

  • Categories of resources are grouped for reading convenience.

  • The IPF resources you can change — the ones in the XGUI file — are window size and

position, fonts, colors, and file names.

Changing IPF Resources

Most values for resources are easy to figure out. Others, like colors, are more difficult. Here are a few hints to get you started. Be sure to read further in Quercia’s book, or a comparable book, for more information.

Warning

If you make a spelling mistake or the value is not correct for the resource, there are no error messages. The resource is ignored. And, there are no X Window System facilities to help you find your error, so be careful!

Changing Open File Defaults

Although you can always find your way to the file you want to open by using the Files filter system, it is much nicer to have IPF come up with the paths and/or names you most commonly use. Below is the section of the XGUI file which you will want to alter in order to do this. Open XGUI with your text editor and forward search for “DEFAULT MASKS”

! These are the DEFAULT MASKS in the open file menu.

XGUI*open_dia_command_dir_text.value: *.pcl
XGUI*open_dia_change_dir_text.value: *.chg
XGUI*open_dia_base_dir_text.value: *.bse
XGUI*open_dia_network_dir_text.value: *.net
XGUI*open_dia_coord_dir_text.value: *.cor

! These are the default filenames in the open file menu.
! Leave blank where you don't want a default.
! Don't set default filenames for both base and network!!!

XGUI*file_select_dia_command_text.value:
XGUI*file_select_dia_change_text.value:
XGUI*file_select_dia_base_text.value:
XGUI*file_select_dia_network_text.value:
XGUI*file_select_dia_coord_text.value:
###########################################################################

When you first execute IPF and select the Open command from the main window menu, some default file selections fill the file text boxes under the Select buttons. These specify the default filters to be applied.

To change a default filter mask: For example, the default coordinate file mask in the XGUI file for the Open dialog box is:

XGUI*open_dia_coord_dir_text.value: *.cor

This assumes that you are executing gui from the directory where the data files reside, and that you will be selecting the coordinate file you want to load from among files in this directory that end with .cor. (The asterisk (*) is a Unix wildcard character meaning “any arbitrary length string of characters.”

To make the filter default to a different directory, insert (for example) /archive/ipf/dat/:

XGUI*open_dia_coord_dir_text.value: /archive/ipf/dat/*.cor

Now the coordinate files selected are in the /archive/ipf/dat directory. The pathname you specify can be absolute or relative; just be sure that it specifies a valid directory on your system.

To change a default filename mask:

The default base case and coordinate file masks in the XGUI file for the Open dialog box are specified with these two lines:

XGUI*file_select_dia_base_text.value:
XGUI*file_select_dia_coord_text.value:

The filenames are currently blank, meaning that no files are loaded when gui starts up. If during a study you are working continuously from a particular base file, say ../base/97HS4.bse, you might want to edit XGUI to make this file, and its associated coordinate file, load automatically every time you start gui. You then can begin work immediately, without having to go through the Open Files menu.

To add default filenames, insert them after the :

XGUI*file_select_dia_base_text.value: ../base/97HS4.bse
XGUI*file_select_dia_coord_text.value: /archive/ipf/dat/volts.cor

These two files will be automatically loaded for you. If you look at the Open Files menu, you will see their names in the boxes to the right of the filter boxes.

Warning

Do not specify both a base file and a network file name. These are mutually exclusive!

Changing Printer Defaults

You can specify your default printer and also enter a list of others you may want to choose from. These are right at the top of the XGUI file.

XGUI*printer_selection_box*textstring: print

Change “print” to whatever string you will want to use most often.

The section just below this is where you put in the other print strings that you want to appear in the printer list.

Changing Window Position and Size

Windows are positioned on the screen by specifying pixel locations. X is the horizontal dimension. Y is the vertical dimension. The position x,y = (0,0) is the upper left corner of the screen. (XGUI.x, XGUI.y) represents the upper left-hand corner of the main window of IPF.

To change the main window default position:

The default in the XGUI file is::

XGUI.x: 127
XGUI.y: 0

Change the 0 to a 127::

XGUI.x: 127
XGUI.y: 127

Now the upper left-hand corner of the main window appears 127 pixels down and to the right of the 0,0 screen pixel position in the extreme upper left-hand corner of the screen.

To change the main window default size:

The default in the XGUI file is::

XGUI.width: 600
XGUI.height: 550

Change the 550 to a 600::

XGUI.width: 600
XGUI.height: 600

Now the IPF main window will be square. Other windows and dialog boxes in XGUI work similarly.

Changing Fonts

The X Window System for your computer comes with a standard set of fonts. Commonly used fonts such as Courier (a typewriter-like font), Times (a serif, “newspaper” font), and Helvetica (a common, sans serif font) are included. Ask your system administrator about the X fonts available on your computer. Each size, shape, and kind of font has a unique name. Here is the name of one of IPF’s default fonts::

-*-Courier-Bold-R-*--*-100-*-*-*-*-ISO8859-1

This X font name specifies Courier bold with a normal slant (R) of size 10 points. Its International Standards Organization character set registry identification is ISO8851-1. The asterisks denote “don’t care” states for the other font parameters such as, for example, foundry (who made the font) and pixel size.

To change a default font:

For example, the default font in the XGUI file for descriptive IPF text in the windows and dialog boxes is::

XGUI*XmText.fontList:*-Courier-Bold-R-*--*-100-*-*-*-*-ISO8859-1

Change the Courier to Times:

XGUI*XmText.fontList:-Times-Bold-R--100----*-ISO8859-1

Now the descriptive text is a 10 point bold Times of a regular slant.

Changing Colors

X color values can be specified as regular names such as blue, red, yellow, magenta, slate blue, sky blue, navy blue, etc., or as hexadecimal digits. Ask your system administrator for a list of all named standard colors because this is much easier to deal with than figuring out hexadecimal color values. However, here is a quick explanation of the hexadecimal color specification system.

Colors are specified in the RGB (Red-Green-Blue) color system. The RGB hex numbers have 12 digits. The first four stand for the Red component. The middle four stand for the Green component. And the last four stand for the Blue component. (Reading left to right, of course.) ffff hex stands for fully saturated red if it is in the first position. 8000 hex stands for a half way saturated red (called “red4” in X). 0000 hex stands for no red at all, which would be black. The green and blue work analogously. Thus, ffffffffffff hex stands for pure white, and 000000000000 hex stands for pure black. To get the color you want, you need to play with different values of hex numbers in the appropriate Red-Green-Blue positions since the RGB intensities are mixed to render one color.

To change a default color: For example, the default color in the XGUI file for the 500 kV branches as shown in the branch color key of the IPF main window is::

XGUI*kv_500_label.background: #ffffcccc0000

Note the hexadecimal color value specification. This default color is a gold-looking color.

Use a color name specification and change the #ffffcccc0000 to yellow::

XGUI*kv_500_label.background: yellow

Now the 500kV branches and the branch color key shows up as pure yellow.

Changing Default File Names

When you first execute IPF and select the Open command from the main window menu, some default file names fill some of the file text boxes. You can specify your own valid file names or file name masks in the XGUI file.

To change a default file mask:

For example, the default coordinate file mask in the XGUI file for the Open dialog box is::

XGUI*open_dia_coord_dir_text.value: /shr5/all/ipf/dat/*.cor

The *.cor selects just the coordinate files in the given directory (if they all end with .cor, of course). (The asterisk ( * ) is a UNIX wildcard character meaning “any arbitrary length string of characters.””)

Change the /shr5/all to /archive/year1992::

XGUI*open_dia_coord_dir_text.value: /archive/year1992/ipf/dat/*.cor

Now the coordinate files selected are in the /archive/year1992/ipf/dat directory.

You can change any part of the file name, of course, just so long as the file name is a valid file name for your operating system.

CFLOW C API (libcflow)

Overview

CLFOW is a C Application Programming Interface (API) for IPF. The library name is libcflow. With CFLOW, users can access the bus and branch data within the power flow data structures in a highly flexible way. Once data is retrieved from the IPF “data engine”, it can be manipulated within the user-written C program and either output to a file, screen, or plotter, or sent back to the IPF “data engine” for further processing. A CFLOW program is a totally separate process running concurrently with the “powerflow solution and data server” process and communicates with it via an Inter Process Communication (IPC) protocol that uses sockets.

In order to use CFLOW, you must have some knowledge of the C language and have a C compiler. Once a CFLOW program has been written, compiled, linked, and debugged, it is stored as an executable which can be run from the command line or from the IPF GUI using the “PROCESS – CFLOW” menu option.

CFLOW is completely compatible with ANSI C and portable to all environments that have an ANSI C compiler.

History

CFLOW was written to perform analogous functions to the WSCC’s Computationally Oriented Programming Environment (COPE) language. COPE was a standalone language integrated with the WSCC equivalent of BPA’s IPF, the Interactive Powerflow System (IPS). CFLOW is a library of C language functions, that that effectively wrap the ipsrv server component of IPF. This means it operates as a “remote procedure call” library. All the power of the C language is available to CFLOW users, whereas COPE users are limited to the COPE language and environment. Another example of similar functionality is PTI’s IPLAN which is interpreted similar to the way COPE is. CFLOW is more powerful and flexible than COPE.

Audience

This documentation assumes that you are a beginning to mid-level C language programmer. This means you should have successfully written programs in some languages. If you have some experience with Fortran, BASIC, Pascal, or C it will be even easier for you to grasp. You need not have written complex programs, simply programs such as you would be required to complete in an undergraduate college programming course. If you already know C, you are ready to write CFLOW programs. If not, you should probably take a class, invest in a computer tutorial course, and/or spend some time with a good C language book.

The following C programming books are recommended for those users needing introductory or refresher information:

  • Brakakati, Nabajyoti. The Waite Group’s Microsoft C Bible. Howard W. Sams & Company, 1988. This MS-DOS environment reference book clearly describes ANSI C compatibility for each function.

  • Harbison, Samuel P. and Guy L. Steele. C: A Reference Manual. 3rd ed. Prentice-Hall, 1991. This book shows ANSI C facilities contrasted with traditional or alternate facilities. If you are well acquainted with C programming, but want to make sure your program complies with ANSI C, look here.

  • Johnsonbaugh, Richard and Martin Kalin. Applications Programming in ANSI C. MacMillan, 1990. This is a textbook used in beginning undergraduate college courses.

  • Kernighan, Brian W. and Dennis M. Ritchie. The C Programming Language. Second Edition. Prentice-Hall, 1988. This is the standard book for learning the language, updated to a second edition. Experienced programmers will do well with this book. Beginners should use Kochan’s book.

  • Kernighan, Brian W. and Rob Pike. The UNIX Programming Environment. Prentice-Hall, 1984. This book describes how to develop programs in the UNIX operating system.

  • Kochan, Stephen G. Programming in ANSI C. Howard W. Sams & Company, 1988. This book is a comprehensive tutorial for the beginning programmer.

  • Plauger, P. J. The Standard C Library. Prentice-Hall, 1992. This book shows you how to use the standard ANSI and ISO C library functions. It provides code examples for implementing many of the library functions.

Creating a Program

CFLOW is a library of functions that a C program can link to (with an object file linker) to access IPF data and control IPF execution. The program you write is a C program. CFLOW source programs are created using a text editor. The program lines can be entered in “free format,” since there are no column restrictions like Fortran.

Indentation is recommended when designing nested logical constructs to reduce logic errors and enhance readability. For example:

if(condition) {/* beginning of first "if" block */
  if(condition) {/* beginning of second "if" block */
    statement;
    statement;
  }/* end of second "if" block */
  statement;
  statement;
}/* end of first "if" block */
statement;

Include the CFLOW header file, called cflowlib.h, in each file that calls a CFLOW function.

Running a CFLOW Program

From the command line

To run your CFLOW program from the command line, simply run the program as you would any other program from a terminal/command prompt. For example, the following could be used:

my_cflow_program [ arg1 ] [ arg2 ] ...

The library will take care of launching the ipfsrv program and establishing a connection. There are several optional command line arguments that are assumed by every program that uses the libcflow library. These options must precede any of the arguments for the CFLOW program.:

-n noserver, do not launch ipfsrv

-w <wait time> max wait time for socket connect (default of 30)

-c <socket> socket number to use if other than default of

From the GUI

There are two ways to execute a CFLOW program from the GUI: Either in its own terminal window, or in the same terminal window that the GUI is running in (background). CFLOW programs that are run in the same terminal window as the GUI that read/write to stdin or stdout (i.e. use readln or printf) have their I/O intermixed in the same terminal window as the GUI and IPF server. The background mode should usually only be used for programs that generate a report or other output to a file.

To run a CFLOW program from the GUI, you start up the GUI, and set up whatever conditions are required for your program to work, such as loading and solving a case, if the program is designed to report on a currently loaded case. Then select Process - Run CFLOW. You will get a file selection window. Double-click on a directory name, or change the filter field and click the Filter button, to change the file list. When you see the file you want to run (your executable CFLOW program), select it, and it will appear in the Selection field. Select either Window (default) or Background, and, if your program has command line arguments, type these into the CFLOW Program Arguments field. Then click the Launch CFLOW button. The Wait field (default 30 seconds) is provided just in case your program takes longer than 30 seconds to start up. The wait time is the length of time that the GUI/ipfsrv will wait for the CFLOW program to start up and establish a socket (inter-process communication) connection. The value can be set from 15 to 300 seconds. If the CFLOW program has not connected within the wait time, then the CFLOW run is aborted and control is returned to the GUI.

The program is run synchronously. This means that you cannot use the GUI until the CFLOW program is finished running. If the CFLOW program fails, control is returned to the GUI. However, if the CFLOW program hangs (as in an infinite loop), you need to kill the CFLOW process through operating system resources. (For example, on UNIX this can be done with the kill command and on VMS this can be done with the stop process command.) See your computer system documentation or your system administrator for help.

When the program completes, the CFLOW window goes away and control returns to the GUI. You can then load a different file, or make other changes, and select Process - Run CFLOW again to rerun. The scripts run_cflow_win (window) and run_cflow_bg (background) are used to run the CFLOW program. These scripts can be customized for your system.

From ipfbat

For batch, also called background or terminal window interactive processing, the ipfbat program is provided. This program reads a control file rather than connecting to and receiving commands from the GUI process.

A CFLOW program can be run by including the following command in the control file:

/CFLOW, PROGRAM =
[ directory path ] < CFLOW executable file or script file >
[ , WINDOW ]
[ , WAIT = < max wait time for socket connect > ]
[ , ARGS = < command line arguments for the specified program > ]

The brackets ([ ]) denote optional items. The command is free format with the restriction that any “word” (like the [ path ] < file > ) must be all on the same line (not continued on the next line) with no imbedded blanks or any of the following: “,=n”. On a UNIX system, for example, you can use the following:

/CFLOW, PROGRAM = my_cflow_program

This “launches” the program if it is in your directory search path. ARGS = is required only if the CFLOW program requires command line arguments. Without the WINDOW option, any I/O from the CFLOW program goes to standard input or standard output, and will be to and from the same terminal window that the ipfbat program is run from (intermixed with any I/O from the ipfbat program). The scripts run_cflow_win (window) and run_cflow_bg (background) are use to run the CFLOW program. These scripts can be customized for your system.

Debugging

Use the standard system debugger for your computer system to debug CFLOW C programs. Although it is possible to do debugging using the GUI/ipfsrv or the ipfbat programs, it is recommended that you debug by running your CFLOW program from the command line.

If your program expects some setup (i.e. a case already loaded and solved), because your program is used like a subroutine that generates a report or other output based on whatever is currently there, then for debugging purposes, you can create a function that does the setup (e.g. load base, apply changes, solve) and call that function at the beginning of your program. When the program is debugged, you can “comment out” the call to the setup function.

The pf_cflow_init() function uses the C library function system() to launch the ipfsrv program with the output redirected to a file. There is a default wait (time out) of 30 seconds for the ipfsrv program to extablish a socket connection, but this can be increased, if needed, to up to 300 seconds with the -w option. See running From the command line above. In general, when debugging, you want to “step over” (versus “step into”) the pf_cflow_init() function, however, if you decide to step through the function, be aware that part of the code has the time out in effect and will cause a “failed connect” to occur if you proceed too leisurely.

If you experience problems with debugging that you suspect are related to the “system” call that launches the ipfsrv program, you can use the -n (noserver) option as follows to debug from two windows:

In one window run your CFLOW program.:

my_cflow_program -n -w 300 [ arg1 ] [ ... ]

Wait for the log message using socket nnnn (this will happen when the pf_cflow_init() function is executed), then in another window run the ipfsrv program.:

ipfsrv -socket nnnn

where “nnnn” is the same as what the CFLOW program stated. The socket connection should happen within a second.

You can then debug your program in one window while the ipfsrv program runs in the other.

Functions Overview

The CFLOW library is a set of functions, written in the C language, that allows access to IPF data. Behind the scenes, the routines communicate with the IPF program via an interprocess communication channel known as a socket (similar to a pipe or stream). The routines are organized, as much as possible, as data access routines, since the powerflow program is playing the role of data store for the power flow model and solution as well as compute “server.”

There are four major classes of functions:

  • Simple IPF “command” functions.

  • Record-oriented IPF functions.

  • Buffer-oriented IPF “command” functions.

  • Utility functions and local data translation.

The library currently accesses only the Powerflow program. In the future, a similar approach could be used to provide a CFLOW interface for other programs. The various functions are documented in Chapter 4. All of those that access Powerflow start with pf_. All functions return a non-zero integer for an error condition and a zero for successful completion.

Simple Command Functions

Examples of simple functions are pf_area_of_zone, pf_del_zone, pf_rename_area, pf_rename_zone, and pf_rename_bus. These functions perform an operation that requires little or no input data, other than a command, and usually return only a status, or a single piece of data such as pf_area_of_zone does.

Record Oriented Functions

Examples of record-oriented functions are pf_rec_bus and pf_rec_cbus. These functions use C language structures to manipulate a record. Both generic and record-type specific structure definitions are provided, so that field names specific to the record type can be used for a little better “self-documenting” code. For example, the variable containing TAP2 for a transformer contains B2 for an E type line, and the minimum phase shift for a type RM regulating phase shifter. This same variable can be accessed by using the names r.i.branch.tap2, r.i.pf_E.b2, and r.i.pf_RM.min_phase_shift_deg. The table below gives comlete details. The columns represent the input values that are defined for branch records. In the table, “N/A” means that the data item does not apply to that record type; “-” means the variable name is the same as the generic variable name (left most column). See the Record Formats section for descriptions of the various branch records.

Generic branch variable name and type

E

L

T

TP

R,RN,RQ,RV

RM,RP

RZ

LD

LM

char type[3]

E

L

T

TP

R,RN.RQ,RV

RM,RP

RZ

LD

LM

char owner[4]

char bus1_name[9]

float bus1_kv

int meter

var_tap_side

var_tap_side

var_tap_side

char bus2_name[9]

float bus2_kv

char ckt_id

N/A

N/A

I_or_R_control

N/A

int section

N/A

N/A

N/A

N/A

float total_rating

N/A

N/A

I_rate

int num_ckts

num_taps

num_taps

rani_type

N/A

N/A

float r

N/A

N/A

Pc_max

R

R

float x

N/A

N/A

Pc_min

L_mh

L_mh

float g

g1

N/A

N/A

Xij_max

C_uf

C_uf

float b

b1

N/A

N/A

Xij_min

P_sched

N/A

float tap1

g2

miles

tap1

phase_shift_deg

max_tap

max_phase_shift_deg

Bis_max

V_sched

N/A

float tap2

b2

N/A

tap2

tap2

min_tap

min_phase_shift_deg

Bis_min

miles

miles

float alpha_N_deg

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

float gamma_0_deg

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

char descrip[9]

N/A

descrip[9]

N/A

N/A

rmt_bus_name

rmt_bus_name

N/A

N/A

N/A

char date_in[4]

N/A

N/A

char date_out[4]

N/A

N/A

float thermal_rating

rmt_bus_kv

rmt_bus_kv

N/A

float bottleneck_rating

Qmax

Pmax

N/A

float emergency _rating

N/A

N/A

Qmin

Pmin

N/A

N/A

N/A

The functions all use an action code to specify what is to be done with the record, such as D for delete, F2 to retrieve the first branch record associated with two named buses, and O to retrieve solution (output) data for a bus or branch.

Buffer Oriented Operations

The buffer-oriented operations are all accessed through one function: pf_cflow_ipc. This function sends a buffer to Powerflow containing a command, command options, and usually input data. A buffer is returned that contains the results of the request. Any command that is in the IPF Advanced User Manual can be put in the buffer, with records separated by the ’n’ (linefeed) character. Much of the data sent and received in the buffers is WSCC-formatted data.

Utility Functions

Most of the utility functions are provided to form an “abstraction layer” between your program logic and WSCC formatted ascii records. There are functions to translate between the C structures and WSCC ascii records, as well as functions to initialize the C structures.

Notes

Below are a few notes, reminders, and definitions relating to the C language and the CFLOW library functions, for your convenience.

Strings

Many of the function parameters, such as bus names and action codes, are described as strings. In C, the technical definition of a string is as follows: An array of characters, with a null terminator (ASCII character \0) in the element following the last valid character.

The library functions, like most C library functions, expect the strings you supply to conform to this definition. The easiest way is to enclose the value you want in double quotes (e.g. "AMBROSIA"). You can also store a value like this when you initially declare the character array.

Note

When you declare a char array, remember to always size it one larger than you need to store your actual string, so there is room for the null character!

However, you cannot put this value in an array with an assignment statement (name = "AMBROSIA" is illegal). To store a string in a character array, use the standard C strcpy or strncpy function.

A single character can be placed in one element of a character array by enclosing it in single quotes (name[0] = 'A'; is a legal C assignment statement). If you do this, be sure to store a null in the last character (name[8] = '\0';).

Arrays

In C, an array dimension is declared to be the actual number of elements in the array:

char name[9];   /* Sized to hold an 8-character bus name, plus a null.*/

But when you reference the array elements, the indices run from zero to one less than the declared dimension. In the example above, name[0] has the first character of the bus name; name[7] has the last character, and name[8], which is the last element of the array, contains a null.

Function Types

If a function is declared as void, then no return value is expected, and it may be invoked without a place being provided to receive the returned value. Example:

pf_init_bus( &b, “B”, “AMBROSIA”, 230.0 );

Most of the CFLOW functions are int, meaning that they return an integer value, which is usually zero for success and non-zero for any kind of error. These must be called in some way which is compatible with the name of the function being a variable with a value. Example:

int error;
error = pf_rec_bus( &b, “G” );

Main

Your main program must have the standard arguments int and char **:

int main ( int argc, char *argv[] )
{
  ...
}

You cannot merely call it “main”, as you may have done for programs in a C class, or which you will see as examples in the books. Look at the sample CFLOW programs for guidance.

Includes

In most program you write, you at least need the standard C headers stdio.h and string.h, and also the CFLOW library header, cflowlib.h. This is done with a preprocessor statement: #include <stdio.h> for libraries in the standard C include directory. #include "cflowlib.h" for libraries in some other directory.

Linking

Your CFLOW program can be compiled by itself, but in order to execute, it must be linked with the cflow library, libcflow.a. The simplest way to do this (on a Unix system) is to use something like CMake or a Makefile. Look at the examples in this project for how to do this.

Buffers

CFLOW communicates with ipfsrv by using buffers which are passed back and forth (see the next section, Global Buffers, for detailed information). If you want to see what is in the buffers, set the variable cf_debug to one. As long as it has this value, the contents of every buffer passed will be displayed in the terminal window. Since this output will go by so fast you can’t read it, and it can be very voluminous, you will want to limit the number of buffers actually displayed to the ones you are interested in. Set cf_debug back to zero to turn off the display.

Languages

CFLOW routines do not have to be written in C, except for the main program. If you are adept at the intricacies of calling C routines from a Fortran program and vice versa, you can write your main processing and reporting routines in Fortran, or use code you already have. In general, it will be easier to write a C program to perform the function, rather than trying to retrofit.

Simple Report Example

The ANSI C program listed below was derived from a COPE program. This program illustrates how the CFLOW library and ANSI standard C may accomplish many of the same tasks as COPE programs. Detailed discussion follows the program code. The following program outputs a Shunt Reactive Summary report to the screen. A loaded base case in the Powerflow “data engine” provides the data for the report.

/* 
 * The following is an example of a COPE program, re-written
 * in the "C" programming language using the CFLOW library.
 * It does a Shunt Reactive Summary report on the currently
 * loaded case, for a user-entered zone. Output to gui T/W.
 */

#include <stdio.h>
#include <string.h>
/* use this form if "cflowlib.h" is in a "user
library" include area. Your compile procedure
should use the "-I or /I" option that specifies
the path to "cflowlib.h" */
#include "cflowlib.h"

int readln( char *s, int lim ) /* Function to read input from the T/W. */
{
    int i;
    char c;
    for ( i=0; i < lim - 1 && ( c = getchar() ) != EOF && c != '\n'; ++i )
s[i] = c;
s[i] = '\0';
return i;
}
main( int argc, char *argv[] ) /* Main Program */
{
pf_rec r; /* CFLOW structure */
char zn[3];
int error, status ;
float q_avail_react_tot, q_avail_cap_tot,
q_used_react_tot, q_used_cap_tot,
q_unused_react_tot, q_unused_cap_tot,
q_unsched_react_tot, q_unsched_cap_tot;
pf_cflow_init( argc, argv ); /* IPC connection function, required. */
/* Ask user for zone to report */
printf("Enter Zone to report Shunt Reactive Summary > ");
readln( zn, sizeof(zn) );
zn[sizeof(zn)] = '\0';
printf("\n\n Shunt Reactive Summary for Zone %s \n\n",zn);
printf(" Avail_caps Avail_reac Used_caps Used_reac Unus_caps Unus_rx Unsch_caps
Unsch_rx\n\n");
q_avail_react_tot = q_avail_cap_tot =
q_used_react_tot = q_used_cap_tot =
q_unused_react_tot = q_unused_cap_tot =
q_unsched_react_tot = q_unsched_cap_tot = 0.0;
/* Compute zone quantities */
error = pf_rec_bus( &r, "F" ); /* get first bus in case */
status = pf_rec_bus( &r, "O" ); /* get solution data for first bus */
while ( !error && !status ) { /* Loop through all buses in case */
if ( strcmp(r.i.ACbus.zone, zn )==0)
{ /* If bus is in the zone */
q_avail_react_tot += r.s.ACbus.Bshunt_sch_rx;
q_used_react_tot += r.s.ACbus.Bshunt_used_rx;
q_avail_cap_tot += r.s.ACbus.Bshunt_sch_cap;
q_used_cap_tot += r.s.ACbus.Bshunt_used_cap;
if( r.s.ACbus.Qunsch < 0 ) {
q_unsched_react_tot -= r.s.ACbus.Qunsch;
}
else
{
q_unsched_cap_tot += r.s.ACbus.Qunsch;
}
}
error = pf_rec_bus( &r, "N" ); /* get next bus in case */
status = pf_rec_bus( &r, "O" ); /* get solution data for next bus */
}
q_unused_react_tot = q_avail_react_tot - q_used_react_tot;
q_unused_cap_tot = q_avail_cap_tot - q_used_cap_tot;
/* Print zone summary */
printf(" %6.1f %6.1f %6.1f %6.1f %6.1f %6.1f %6.1f %6.1f \n\n",
q_avail_react_tot, q_avail_cap_tot,
q_used_react_tot, q_used_cap_tot,
q_unused_react_tot, q_unused_cap_tot,
q_unsched_react_tot, q_unsched_cap_tot );
pf_cflow_exit(); /* Drop IPC connection */

C programs usually have header files “included” somewhere near the beginning after a comment header. Header files may be standard or programmer-created. One standard header file required is stdio.h if the program does any I/O operations. Various macros and definitions make up these files. string.h is also a standard header file. cflowlib.h is a special header file for the CFLOW library. All CFLOW programs must include this file.

All C programs must include a call to main, which is where program execution starts.

Immediately after main follow a series of declarations of variables local to main. The variable r is a special CFLOW structure of type pf_rec. This is the basic powerflow record structure used to retrieve both input and output data for all types of records.

A three character array representing a two character bus zone code follows. Note that character arrays storing strings should always be declared one byte larger than needed to account for the terminating NULL (\0).) Two integer variables, error and status, are declared next. These will be used to store the return value from calls to pf_rec_bus. The variables to collect the zone total quantities are declared as float (single precision real numbers).

pf_cflow_init is called to establish the IPC socket connection, which the program will use to communicate with either the ipfsrv or ipfbat programs.

We print a question to the terminal window, and use readln to retrieve the user selection of a zone to report on, and make sure the string is null-terminated by storing a null in the last element of the array (remember that C indexes array elements from 0 to n-1). The input zone id is echoed back in the heading of the report, and the floating point variables are initialized.

Now we begin the actual processing. The first bus record is retrieved by calling pf_rec_bus with an action code of “F” (for First). This stores the input record data for the first bus in the currently loaded system in the local structure r. But we want the output (solution) quantities. So we call pf_rec_bus again, with action code “O” (for Output). The necessary id fields have been stored in r by the first call, and these are passed back to ipfsrv so it knows what bus you want output values for.

A while loop now executes. The purpose of the while loop is to sequentially access bus records and gather floating point data related to the shunt reactance. pf_rec_bus initially used action code “F” to go to the first bus record in the base case. After this, pf_rec_bus uses action code “N” to retrieve the next bus record. When the end of all records has been reached, pf_rec_bus returns a -1, which causes the while loop to terminate.

Since only records from the user-specified zone are desired in this program, a test is first performed on each bus record to see if it has the correct zone. The program could be made more efficient by not bothering to retrieve output values except for the right buses; however it has been left this way for simplicity in providing an example. If the bus is in the right zone, then the appropriate floating point values are totaled in assignment statements. This program assumes that the zone has no DC buses; if there are any, then the DC solution variables stored in the same fields as the AC shunt would give you weird results, to say the least! Of course, it would be possible to also test for bus type, along with testing for the zone, in order to avoid this problem.

When the loop terminates, the reactance totals are printed to the screen with printf statements formatted for decimal output. Then we exit, and release the socket connection, by calling pf_cflow_exit.

Standard Line Flow Summary Example

The slfs.c program was translated from a COPE procedure used by WSCC Technical Staff. It reads an input data file of headings and branches to be reported, looks these up in the currently loaded solved system, and sends the report to a file. The report includes the input headings, and group totals where called for, in an attractive format for printing.

This is what the input data file looks like. Heading lines are those with neither ‘LIN’ or ‘TOT’ on them. They are printed as encountered. LIN’ cards identify a branch to be reported; ‘TOT’ cards call for a total to be printed. The “2” in column 5 indicates that the reverse flow is to be reported.:

CANADA AND NORTHWEST
--------------------
  1. Alberta - British Columbia
LIN LANGDON 500 CBK500 500
LIN LNGDN500 500 CRANBROK 500
LIN LNGDN500 500 CBK500 500
LIN 2 POCA TAP 138 EMC138 138
TOTAL
  2. Canada - Northwest
LIN ING500 500 CUSTER W 500
LIN INGLEDOW 500 CUSTER W 500
LIN 2 NLY230 230 BOUNDARY 230
LIN 2 NELWAY 230 BOUNDARY 230
LIN 2 NLYPHS 230 BOUNDARY 230
LIN SELPHS-1 230 MARSHALL 230
LIN SELPHS-2 230 MARSHALL 230
LIN SELPHS-1 230 BEACON N 230
LIN SELPHS-2 230 BEACON S 230
TOTAL
 3. Northwest - California
LIN MALIN 500 ROUND MT500.
LIN DELTA 115 CASCADE 115.
LIN CAPTJACK 500 OLINDA 500.
TOTAL
 4. Celilo - Sylmar
LIN 2 SYLMAR2I106. SYLMARLA230.
LIN 2 SYLMAR1I106. SYLMARLA230.
LIN 2 SYLMAR2R106. SYLMARLA230.
LIN 2 SYLMAR1R106. SYLMARLA230.
TOTAL
NORTHEAST
---------
 1. MPC High Line
LIN 2 CONRAD 115 CUT BANK115.
LIN GT FALLS 161 HAVRE 161.
     .
     .
     .

The program slfs.c prompts the user for the output file name to put the line flow listing in. The input file name is hard-coded in the program.

/* slfs.c
  This CFLOW procedure looks up flows and creates a report
  of flows between buses as listed in an input data file.
  Before the CFLOW procedure is called, a solved power flow case
  must be resident in the powerflow server.
  This CFLOW procedure prompts the user for two file names:
  the output file name to put the line flow listing in,
  the input file name of a file to get line data from.
  The input file has a LIN card for each branch to be monitored.
  If there are multiple lines between the same buses, slfs.c
  picks up all lines. A TOT card flags printing of total flow
 since the last TOT card (or since the beginning). Input lines
 without either LIN or TOT are printed directly to the output file.
 Each data card has LIN in columns 1-3 and the Branch identifiers
 in columns 7 to 31. First Bus name and KV in columns 7-18,
 Second bus name and KV in columns 20-31. Column 5 is a flag to
 tell slfs.c whether to use the "Pin" or "Pout" data quantity for
 the total flow. If the flag is "2", then "Pout" is used; otherwise
 "Pin" is used. The flag corresponds to the metering point.
*/
#include <stdio.h>
#include <stdlib.h>
#include <string.h>
#include "cflowlib.h"
/* cf_debug = 1; /* Put this where you want the buffers displayed,for debugging */
int readln( char *s, int lim ) /* Read a line from the terminal input */
{
    int i;
    char c;
    for ( i=0; i < lim - 1 && ( c = getchar() ) != EOF && c != '\n'; ++i )
        s[i] = c;
    s[i] = '\0';
    return i;
}
int freadln( FILE *fp, char *s, int lim ) /* Read a line from a file */
{
    int i;
    char c;
    for ( i=0; i < lim - 1 && ( c = getc( fp ) ) != EOF && c != '\n'; ++i )
        s[i] = c;
    s[i] = '\0';
    return i;
}
main ( int argc, char *argv[] )
{
    pf_comments comments; /* CFLOW structure */
    pf_rec r; /* CFLOW structure */
    FILE *out, *dat;
    char card[82], cout[31];
    char skv1[5], skv2[5];
    char direc;
    int error, lin, tot;
    float brflow, totalflow = 0.0;
    float kv1, kv2;
    pf_cflow_init( argc, argv );
    /* Open the input file. This could be prompted for, but Don says
     he always uses the same input file, which will NOT be in the
     execution directory,so full pathname is supplied.
     If the file cannot be opened, the program terminates
     */
    dat=fopen( "/home/ipf/cflow_progs/slfs.dat", "r" );
    if ( dat == NULL ) {
        printf("Can't open data file\n");
        exit(0);
    }
    /* Prompt the user for the output file name, and open the file.
    Normally, file will be created in the execution directory,
    so cout is only 30 characters.
    If the file cannot be opened, the program terminates.
    */
    printf("Enter output file name > ");
    readln( cout, sizeof(cout) );
    printf("\n");
    out=fopen( cout, "w" );
    if ( out == NULL ) {
        printf("Can't open output file\n");
        exit(0);
    }
    /* Retrieve caseid and description, and print heading */
    pf_rec_comments( &comments, "G" );
    fprintf(out,"\n%s\n\n", &comments.h[0][33] );
    totalflow = 0.0;
    /* Loop for every line in the data file
    Read a line from the data file, if not "LIN" or "TOT" then
    print the text as is.
    If "LIN" retrieve and print line data.
    If "TOT" print totalflow and reinitialize it.
    */
    /* "C" array indices start at zero; below we use explicit starting index
    of 1 for "card" character array (string), so that column numbers
    will match array indices.
    */
    while ( freadln( dat, &card[1], sizeof( card ) - 1 ) )
    {
        int head;
        
        lin = (!( strncmp( &card[1], "LIN", 3 )) );
        tot = (!( strncmp( &card[1], "TOT", 3 )) );
        head = lin + tot; /* = 0 if not either */
        if (head == 0) /* Heading card - print the text */
        {
            fprintf(out,"%s\n",&card[1]); /* Print from col. 1 - 1st char. is NULL! */
        } /* end if Heading */
        if (lin) /* LIN data card - process line */
        {
            /* Using CFLOW pf_init_branch function; bus kv’s must be real numbers */
            strncpy(skv1, &card[15], sizeof(skv1));
            skv1[4] = '\0';
            strncpy(skv2, &card[28], sizeof(skv2));
            skv2[4] = '\0';
            kv1 = atof(skv1);
            kv2 = atof(skv2);
            
            /* pf_init_branch stores the passed ID fields in r, and zeroes all the other fields */
            pf_init_branch ( &r, "L", &card[7], kv1, &card[20],kv2, "*", 0);

            /* Call CFLOW pf_rec_branch to retrieve output solution data */
            error = pf_rec_branch( &r, "O" );
            /* If branch not found, do not print anything. This happens quite often, since
            the input file is canned, and used on all cases. */
            if ( error ) {
                continue;    /* This sends it back to the ’while’ */
            }
            /* Otherwise, retrieve flows. r is defined in this pgm as a structure of type pf_rec
            i indicates input data, s indicates output data. See cflowlib.h for definitions.
            */
            direc = card[5]; /* Meter flag for Pin or Pout */
            if ( direc == '2' )
            {   /* meter at second bus */
                brflow = r.s.branch.Pout;
                totalflow += brflow;
                fprintf( out,"%s - %s(M) %s kV num ckts %d %7.1f\n",
                         r.i.branch.bus1_name, r.i.branch.bus2_name, skv2,
                         r.s.branch.num_ckt, brflow );
            }
            else /* meter at first bus */
            {
                brflow = r.s.branch.Pin;
                totalflow += brflow;
                fprintf( out,"%s(M) - %s %s kV num ckts %d %7.1f \n",
                         r.i.branch.bus1_name, r.i.branch.bus2_name, skv2,
                         r.s.branch.num_ckt, brflow );
            }
        } /* end if LIN */
        if (tot) /* TOT data card */
        {
            fprintf(out,
                    "\n Total flow is %7.1f \n\n",totalflow);
            totalflow = 0.0 ;
        } /* end else if TOT */
    } /* end while */
    pf_cflow_exit();
} /* end main */

Note that both input values (r.i.branch.) and output values (r.s.branch.) are reported. The “i” stands for “input” and the “s” stands for “solution”.

The variable cf_debug is provided for convenience in debugging a CFLOW program. When it is “true” (set non-zero), all the input and output buffers will be dumped to the terminal window, so you can see exactly what your program is sending and getting back. Since this can be very voluminous, you would only want to turn it on in the area where you are having a problem.

increm Program

The increm program was translated from a COPE procedure used by WSCC Technical Staff. It reads an input data file of branches to be reported, and another file of buses to change generation on. The starting case is hard-coded, and so is the bus that you want to study power transfer from, in this case GADSBY 3 13.8. For each bus in the second file, the generation at GADSBY is increased, that of the other bus decreased, area intertie chedules are adjusted as necessary, the case is solved, and the flow is retrieved for all the branches in the first input file and stored in an array.

The report goes to a file; it consists mostly of a matrix showing the effect of the generation changes on the monitored line flows.

The COPE procedure used the IPS feature INCREM to accomplish this task. IPF has no built-in incrementals function, so the CFLOW program just does what is described in the paragraph above. It is not a general-use incremental program mimicking the IPS function. For simplicity, a lot of names are hard-coded in this program. The user would have to decide whether it would be more efficient to change them in the code for each study, or fix the code to be general and then have to type them in over again for each run.

/******************************************************************************\
UTILITY:    INCREM
TYPE:       Powerflow (IPFSRV v. 209 or later) incremental line flows.
SUMMARY:    Creates an incremental line flow listing of selected lines, sorted 
            by areas.
RELATED:
SEE ALSO:   INCREM COPE procedure for IPS
UPDATED:    February 17, 1995
LANGUAGE:   Standard C.  CFLOW libraries.
DEVELOPER:  Walter L. Powell, TEOS, BPA x3234
REQUESTER:
USERS:
PURPOSE:    Creates an incremental line flow listing of selected lines, sorted 
            by areas. The incremental flows are computed as the change in flows
            from the base case to the incremental case.  Up to 10 incremental 
            cases can be submitted, though this limit is easily extended.
\******************************************************************************/
/* increm.c

   This CFLOW procedure creates an incremental line flow listing of
   selected lines, sorted by areas. The incremental flows are computed
   as the change in flows from the base case to the incremental case.

   Several incremental cases can be submitted. The limit here is 10,
   compared with 64 for the INCREM COPE procedure for IPS. However, this
   limit can be extended with attendent changes in the incremental
   storage arrays and in the output reports.

   Two aspects makes this CFLOW procedure more complicated than the COPE
   equivalent.

   1. IPF uses area intertie "I" records to define the net area export. 
      If these records are present, an interarea transfer is effected
      only by changing the scheduled interarea export. If "I" records exist
      but the particular Area1-Area2 "I" record does not exist, then a
      new "I" record must be added for Area1-Area2 with an export value
      of the desired transfer. If no "I" records exist, then the interarea 
      transfer is effected by the ordinary means, namely, by increasing the 
      area1 export and decreasing the area2 export.

   2. Process INCREM does not exist in IPF.  Consequently, the sorting
      and listing of branches was implemented entirely within this CFLOW
      procedure. 

   The code is intentionally batch. It could be made interactive by 
   prompting for file names and bus names.  All file names and bus names 
   are hard coded.  Changing these requires re-editing, recompiling, and 
   relinking the program.  Fortunately, these steps can be performed in 
   a short time.

   The program's execution sceniero is as follows.

   1. Load in base case history file.
   2. Open branch data file, bus data file, and output report file.
   3. Process the branch data file. For each branch, obtain the base case 
      line flow.
   4. Process the bus data file to identify each transfer pair of buses:
      "busname1" and "busname2".  The "busname1" is a hard-coded global 
      variable.
      a. For each bus pair, perturb busname1's generation +100MW (and its 
         associated areaname1's export +100MW) and busname2's generation 
         -100MW (and its associated areaname2 export -100MW). 
      b. Solve the case.
      c. Loop through the monitored branches, obtaining the line flows
         for the perturbed case.
   5. Print the output report.
      a. Use a branch index array "keysrt" in conjunction with a 
         user-written compare routine (to be used with qsort) to obtain a 
         double-entry list of monitored branches sorted by the following 
         fields: area1, bus1, area2, bus2, id, and section. 
      b. Print out the monitored lines flows using the sort index.
 */

#include <stdio.h>
#include <ctype.h>
#include <stdlib.h>
#include <string.h>

#include "cflowlib.h"
#include "ft.h"

#define NULLC    '\0'
#define MAXFLOWS 1000
#define MAXCASES 10
#define TRUE     1
#define FALSE    0
#define LINES_PER_PAGE 64

/* Declare global variables */

struct FLOWS {
  char   bus1[13];         /* bus1, base1 field                 */
  char   bus2[13];         /* bus2, base2 field                 */
  char   id;               /* id field                          */
  int    section;          /* section field                     */
  char   area1[11];        /* area name corresponding to bus1   */
  char   area2[11];        /* area name corresponding to bus2   */
  float  Pin[MAXCASES+1];  /* Tie line flows in MWs             */
  float  Pout[MAXCASES+1]; /* Tie line flows in MWs             */
  } br_flow[MAXFLOWS];

/* Declare hard-coded files and bus names */

char *progname = "increm";
char *basefile = "98hs3inc.bse";
char *branchfile = "line.dat";
char *busname1 = "GADSBY 313.8";
char *busfile = "name2.dat";
char *outfile = "98hs3inc.out";

/* declare function prototypes */

FILE *efopen (char *, char *);
int compare( const void *, const void * );
/* static int compare( const void *key1, const void *key2 ); */
int increment (char *, char *, float, int);
int get_bus_area (char *, char *);
int mod_bus_gen (char *, float);
int mod_area_export (char *, float);
int mod_itie_export (char *, char *, float);
void title (int *, int *, FILE *, pf_comments *, int, char *);

FILE *efopen (char *file, char *mode) /* fopen file, return message */
				      /* if can't                   */
{
  FILE *fp;

  if ((fp = fopen(file, mode)) != NULL)
    return fp;
  fprintf (stderr, " %s: can't open file %s mode %s\n",
    progname, file, mode);
  return NULL;
}

main(int argc, char *argv[])
{
  pf_comments   c;
  pf_rec        br, itie;

  int i, j, k, status, numcases = 0, keysrt[2*MAXFLOWS], numbr, lineno = 0, 
      pageno = 0, intertie_flag = FALSE, section;
  FILE *fp_busfile, *fp_branchfile, *fp_outfile;
  char id, base[5], busname2[13], oldarea[11], string[133], areaname1[11];

  pf_cflow_init( argc, argv);

  /* Load the history data file */

  status = pf_load_oldbase (basefile);
  if (status) {
    fprintf (stderr, " Unable to open history file %s status %d",
      basefile, status);
    pf_cflow_exit();
    return 1;
  }

  /* Determine if any Area Intertie "I" records exist in the base case */
 
  pf_init_rec (&itie, PF_REC);   /* Initialize structure prior
                                    to calling pf_rec_itie.  
                                    PF_REC is in header file "ft.h"  */
  status = pf_rec_itie (&itie, "F");
  if (status == 0) intertie_flag = TRUE;  /* If success, "I" records exist */

  /* Obtain case comments */

  pf_init_rec (&c, PF_REC);   /* Initialize structure prior
                                 to calling pf_rec_comments.  
                                 PF_REC is in header file "ft.h"  */
  status = pf_rec_comments (&c, "G");

 /* Open the monitored branch data file for read only */

  fp_branchfile = efopen(branchfile, "r");
  if (fp_branchfile == NULL) {
    fprintf (stderr, " Unable to open monitored branch file %s \n",
      branchfile);
    pf_cflow_exit();
    return 1;
  }

  /* Open the bus data file for read only */

  fp_busfile = efopen(busfile, "r");
  if (fp_busfile == NULL) {
    fprintf (stderr, " Unable to open buses list file %s \n",
      busfile);
    pf_cflow_exit();
    return 1;
  }

 /* Open the output report file for write only */

  fp_outfile = efopen(outfile, "w");
  if (fp_outfile == NULL) {
    fprintf (stderr, " Unable to open INCREM output report file %s \n",
      outfile);
    pf_cflow_exit();
    return 1;
  }

  fprintf (fp_outfile, " Base case from history file %s \n", basefile);
  for (i=0; i < 3; i++) {
    if (strnlen (c.h[i], sizeof(c.h[0])) > 0) 
      fprintf (fp_outfile, " %s \n", &c.h[i][1]);
  }  
 /*
  Process each record in the monitored branch file. The procedure invokes
  the following steps.

  1. Parse the ID fields of each branch entity into the branch data 
     structure.

  2. A call to routine "pf_rec_branch" with appropriate arguments will
     obtain the branch output quantitys Pin and Pout.

  3. Parse the ID fields again of each branch entity into arrays used 
     for sorting and printing the output report. The "area1" and "area2"
     arrays are obtained indirectly through the zone. First the zone is
     obtained from the bus data structure of each terminal bus. From each
     zone, the corresponding the area name is obtained via the call 
     "pf_area_of_zone".

  4. An slightly unusual convention is employed here for subscrip "numbr". 
     Normally, a C-arrays begins with subscript "0".  Here, it begins with 
     subscript "1".  The reason is that it is necessary to distinquish 
     normal branches from transposed branches in the "keysrt" array, which 
     will be built after all lines have been read in and all incremental
     cases have been processed. The distinction is done by positive 
     and negative subscripts: +n denotes the normal orientation, -n its 
     transpose.  (C cannot distinquish between +0 and -0.)
  */

  fprintf (stderr, " Reading in monitored line data \n");

  numbr = 0;
  while ( fgets (string, 132, fp_branchfile) != NULL) {
    /*
       Parse the branch data id fields from "string" into structure 
       "br.i.branch" and call "pf_rec_branch" with the "O" option to 
       retrieve the base case flow.

       Copy the parsed branch data id fields into a second structure
       "br_flow[]" for storing the flow results.

       Note that the strncpy command requires that the strings be 
       explicitly null-terminated. 
    */

    pf_init_rec (&br, PF_REC);   /* Initialize structure prior
                                    to calling pf_rec_branch.  
                                    PF_REC is in header file "ft.h"  */
    strcpy (br.i.branch.type, "L ");
    strncpy (br.i.branch.bus1_name, &string[6], 8);
    br.i.branch.bus1_name[8] = NULLC;
    strncpy (base, &string[14], 4);
    base[4] = NULLC;
    br.i.branch.bus1_kv = atof (base);
    strncpy (br.i.branch.bus2_name, &string[19], 8);
    br.i.branch.bus2_name[8] = NULLC;
    strncpy (base, &string[27], 4);
    base[4] = NULLC;
    br.i.branch.bus2_kv = atof (base);
    id = string[31];
    if (id  == '\n' || id == '\t' || id == '\0') id = ' ';
    br.i.branch.ckt_id = id;
    if (strnlen (string) > 32) {
      base[0] = string[32];
      base[1] = NULLC;
      section = atoi (base);
    } else {
      section = 0;
    }
    br.i.branch.section = section;
 /*
    The branch data is now loaded in structure "branch". A call to
    "pf_rec_branch" will retrieve the desired information.
 */
    status = pf_rec_branch (&br, "O");
    if (!status) {
      numbr++;
      strcpy (br_flow[numbr].bus1, &string[6]);
      br_flow[numbr].bus1[12] = NULLC;
      strcpy (br_flow[numbr].bus2, &string[19]);
      br_flow[numbr].bus2[12] = NULLC;
      br_flow[numbr].id = br.i.branch.ckt_id;
      br_flow[numbr].section = br.i.branch.section;
      br_flow[numbr].Pin[0] = br.s.branch.Pin;
      br_flow[numbr].Pout[0] = br.s.branch.Pout;

      /* Get the area name associated with bus1 indirectly through the
	 zone of bus1 */

      status = get_bus_area (br_flow[numbr].bus1, br_flow[numbr].area1);
      if (status) {
        fprintf (stderr, " Unable to retrieve area associated with bus1 of \
monitored branch %s %s \n", br_flow[numbr].bus1, br_flow[numbr].bus2);
	pf_cflow_exit();
	return 1;
      }
      
      /* Get the area name associated with bus2 indirectly through the
	 zone of bus2 */

      status = get_bus_area (br_flow[numbr].bus2, br_flow[numbr].area2);
      if (status) {
        fprintf (stderr, " Unable to retrieve area associated with bus2 of \
monitored branch %s %s \n", br_flow[numbr].bus1, br_flow[numbr].bus2);
	pf_cflow_exit();
	return 1;
      }
    }
  }

  /* Begin the incremental bus loop. This is the list of buses in
     testdc3.bdat, processed one-by-one. */

  while ( fgets (string, 80, fp_busfile) != NULL) {

    strncpy (busname2, string, sizeof(busname2));
    busname2[12] = NULLC;
    status = increment (busname1, busname2, 100.0, intertie_flag);
    if (!status) {

      numcases++;

      /* Solve the modified case */

      status = pf_solution ();

      /* Write change case comments */

      if (status) {

	fprintf (fp_outfile, "\n Incremental case number %d failed \n",
	  numcases);
	fprintf (fp_outfile, "    100 MW scheduled from \"%s\" to \"%s\"\n",
	  busname1, busname2);
	fprintf (stderr, " Incremental case number %d failed \n",
	  numcases);
	for (i = 1; i <= numbr; i++) {
	  br_flow[i].Pin[numcases] = 0.0;
	  br_flow[i].Pout[numcases] = 0.0;
        }
      } else {

	fprintf (fp_outfile, "\n Incremental case number %d \n", numcases);
	fprintf (fp_outfile, "    100 MW scheduled from \"%s\" to \"%s\"\n",
	  busname1, busname2);
	fprintf (stderr, "\n Incremental case number %d \n", numcases);
	fprintf (stderr, "    100 MW scheduled from \"%s\" to \"%s\"\n",
	  busname1, busname2);

	for (i = 1; i <= numbr; i++) {
          pf_init_rec (&br, PF_REC);   /* Initialize structure prior
                                          to calling pf_rec_branch.  
                                          PF_REC is in header file "ft.h"  */
          strcpy (br.i.branch.type, "L ");
	  strncpy (br.i.branch.bus1_name, br_flow[i].bus1, 8);
	  br.i.branch.bus1_name[8] = NULLC;
	  br.i.branch.bus1_kv = atof (&br_flow[i].bus1[8]);
	  strncpy (br.i.branch.bus2_name, br_flow[i].bus2, 8);
	  br.i.branch.bus2_name[8] = NULLC;
	  br.i.branch.bus2_kv = atof (&br_flow[i].bus2[8]);
	  br.i.branch.ckt_id = br_flow[i].id;
          status = pf_rec_branch (&br, "O");
	  br_flow[i].Pin[numcases] = br.s.branch.Pin;
	  br_flow[i].Pout[numcases] = br.s.branch.Pout;
	}
      }
    }
  }

  /* Obtain sorted double entry index "keysrt" for branch flows 
     keysrt[i] > 0 means "br_flow" is processed as is
               < 0 means "br_flow" is processed transposed
   */

  for (i = 0; i < numbr; i++) {
    keysrt[2*i] = i + 1;     
    keysrt[2*i+1] = -keysrt[2*i];
  }
  qsort ( keysrt, 2*numbr, sizeof (keysrt[0]), compare );

  title (&lineno, &pageno, fp_outfile, &c, numcases, "");

  oldarea[0] = NULLC;
  for (i = 0; i < 2*numbr; i++) {
    j = keysrt[i];
    if (j > 0) {
      strcpy (areaname1, br_flow[j].area1);
    } else {
      strcpy (areaname1, br_flow[-j].area2);
    }
    if (strcmp (areaname1, oldarea) != 0) {
      if (lineno+4 > LINES_PER_PAGE) {
        lineno = 0;
        title (&lineno, &pageno, fp_outfile, &c, numcases, areaname1);
      } else {
        fprintf (fp_outfile, "\n From area %s \n\n", areaname1);
        lineno += 3;
      }
      strcpy (oldarea, areaname1);
    }
    if (lineno+1 > LINES_PER_PAGE) {
      lineno = 0;
      title (&lineno, &pageno, fp_outfile, &c, numcases, areaname1);
    }
    if (j > 0) {
      fprintf (fp_outfile, " %s %s %c %s %8.2f  ", br_flow[j].bus1,
	br_flow[j].bus2, br_flow[j].id, br_flow[j].area2,
	br_flow[j].Pin[0]);
      for (k = 1; k <= numcases; k++) {
	fprintf (fp_outfile, " %7.2f", br_flow[j].Pin[k] - br_flow[j].Pin[0]);
      }
    } else {
      fprintf (fp_outfile, " %s %s %c %s %8.2f  ", br_flow[-j].bus2,
	br_flow[-j].bus1, br_flow[-j].id, br_flow[-j].area1,
	-br_flow[-j].Pout[0]);
      for (k = 1; k <= numcases; k++) {
	fprintf (fp_outfile, " %7.2f", 
          -br_flow[-j].Pout[k] + br_flow[-j].Pout[0]);
      }
    }
    fprintf (fp_outfile, "\n");
    lineno++;
  }

  pf_cflow_exit();
  fclose (fp_busfile);
  fclose (fp_branchfile);
  fclose (fp_outfile);
  if (!status) {
    exit (0);
  } else {
    fprintf (stderr, " %s aborted with errors \n", progname);
    exit (1);
  }
}

int get_bus_area (char *name, char *area)

/* This routine returns the area name given the bus name. It is obtained
   indirectly through the bus bus data structure. First, essential information
   is inserted into the bus data structure and the remaining data in the
   structure is obtained after calling "pf_rec_bus". From the zone name in 
   the bus structure, the area name is obtained by calling "pf_area_of_zone".
 */

{
  pf_rec bus;
  char base[5], zone[3];
  int len, status;

  pf_init_rec (&bus, PF_REC);   /* Initialize structure prior
                                   to calling pf_rec_bus.  
                                   PF_REC is in header file "ft.h"  */
  strcpy (bus.i.ACbus.type, "B ");
  strncpy (bus.i.ACbus.name, name, 8);
  bus.i.ACbus.name[8] = NULLC;
  strcpy (base, &name[8]);
  bus.i.ACbus.kv = atof (base);
  status = pf_rec_bus (&bus, "G");
  if (status) {
    fprintf (stderr, " Bus %s is not in history file %s \n", name, basefile);
    return 1;
  }
  strncpy (zone, bus.i.ACbus.zone, 2);
  zone[2] = NULLC;
  status = pf_area_of_zone (area, zone);
  if (status) {
    fprintf (stderr, " No area data in history file %s \n", basefile);
    return 1;
  }
  return 0;
}

int increment (char *busname1, char *busname2, float delta_gen, int flag)

/* This routine applies +/- delta_gen to pairs of buses, areas, and/or 
   intertie records to effect the desired transfer. */

{
  pf_rec      b, a, itie;
  char areaname1[11], areaname2[11];
  int status;

  /* The following are declared "static" such that they can be initialized
     to NULL, are local, and are not volatile, i.e., they retain their value
     after the routine is executed. In FORTRANese, they are similar to local 
     variables, initialized with a DATA statement, and retained with a 
     SAVE statement. 
 */
   static char oldbus1[13] = "", oldarea1[11] = "", oldbus2[13] = "",
              oldarea2[13] = "";
              
  /* Get areaname1 associated with busname1 */

  status = get_bus_area (busname1, areaname1);
  if (status) {
    fprintf (stderr, " Unable to retrieve area associated with bus %s \n", 
     busname1);
    pf_cflow_exit();
    return 1;
  }
              
  /* Get areaname2 associated with busname2 */

  status = get_bus_area (busname2, areaname2);
  if (status) {
    fprintf (stderr, " Unable to retrieve area associated with bus %s \n", 
     busname2);
    pf_cflow_exit();
    return 1;
  }
              
  /* Restore original Pgen on "oldbus1" and modify Pgen on "busname1".
     In this case, restoring the original Pgen on "oldbus1" is not
     necessary because it never changes its name once it is assigned.
     The same is true for area "oldarea1" and for intertie "oldarea1-oldarea2".
     This extra logic (two lines in each instance) is added for generality.
  */

  if (strcmp (busname1, oldbus1) != 0) {
    if (strlen (oldbus1) > 0) 
      status = mod_bus_gen (oldbus1, -delta_gen); 
    status = mod_bus_gen (busname1, delta_gen);
  }
              
  /* Restore original Pgen on oldbus2 and modify Pgen on busname2 */

  if (strcmp (busname2, oldbus2) != 0) {
    if (strlen (oldbus2) > 0) 
      status = mod_bus_gen (oldbus2, delta_gen); 
    status = mod_bus_gen (busname2, -delta_gen);
  }
  if (flag) {
              
    /* Area Intertie "I" records exist and these records define the net
       area interchange export. Restore the original export on intertie 
       "oldarea1-oldarea2" and modify the export on intertie
       "areaname1-areaname2" */

    if (strlen (oldarea1) > 0 && strlen (oldarea2) > 0) 
      status = mod_itie_export (oldarea1, oldarea2, -delta_gen);
    status = mod_itie_export (areaname1, areaname2, delta_gen);
  } else {
              
    /* Area intertie "I" records do not exist. Work directly on the 
       area records. Modify export on each area "areaname1" and 
       "areaname2" */

    if (strlen (oldarea1) > 0) 
      status = mod_area_export (oldarea1, -delta_gen);
    status = mod_area_export (areaname1, delta_gen);
    if (strlen (oldarea2) > 0) 
      status = mod_area_export (oldarea2, delta_gen);
    status = mod_area_export (areaname2, -delta_gen);
  }
  strcpy (oldbus1, busname1);
  strcpy (oldbus2, busname2);
  strcpy (oldarea1, areaname1);
  strcpy (oldarea2, areaname2);
  return status;
}

int mod_bus_gen (char *busname, float delta_gen)

/* This routine changes Pgen on bus "busname" an amount "delta_pgen" */

{
  pf_rec      b;
  int status;
              
  pf_init_rec (&b, PF_REC);   /* Initialize structure prior
                                 to calling pf_rec_bus.  
                                 PF_REC is in header file "ft.h"  */
  strcpy (b.i.ACbus.type, "B ");
  strncpy (b.i.ACbus.name, busname, 8);
  b.i.ACbus.name[8] = NULLC;
  b.i.ACbus.kv = atof (&busname[8]);

  status = pf_rec_bus (&b, "G");
  if (status) {
    fprintf (stderr, " Bus %s is not in history file %s \n",
      busname, basefile);
    pf_cflow_exit();
    return 1;
  }

  /* Add "delta_gen" to bus generation */

  b.i.ACbus.Pgen = b.i.ACbus.Pgen + delta_gen;
  status = pf_rec_bus (&b, "M");
  return status;
}

int mod_area_export (char *areaname1, float delta_export)

/* This routine changes Export on Area "areaname1" an amount "delta_export" */

{
  pf_rec      a;
  int status;
              
  pf_init_rec (&a, PF_REC);   /* Initialize structure prior
                                 to calling pf_rec_bus.  
                                 PF_REC is in header file "ft.h"  */
  strcpy (a.i.area.type, "A ");
  strcpy (a.i.area.name, areaname1);
  status = pf_rec_area (&a, "G");
  if (status) {
    fprintf (stderr, " Area %s is not in history file %s \n",
      a.i.area.name, basefile);
    pf_cflow_exit();
    return 1;
  }

  /* Add "delta_export" to area export */

  a.i.area.sched_export = a.i.area.sched_export + delta_export;
  status = pf_rec_area (&a, "M");
  return status;
}

int mod_itie_export (char *areaname1, char *areaname2, float delta_export)

/* This routine changes Export on area intertie "areaname1-areaname2" and
   amount "delta_export" */

{
  pf_rec      itie;
  int status;
              
  pf_init_rec (&itie, PF_REC);   /* Initialize structure prior
                                    to calling pf_rec_itie.  
                                    PF_REC is in header file "ft.h"  */
  if (strcmp (areaname1, areaname2) == 0) {
    return 0;
  } else {
    strcpy (itie.i.itie.type, "I ");
    strcpy (itie.i.itie.area1_name, areaname1);
    strcpy (itie.i.itie.area2_name, areaname2);
    status = pf_rec_itie (&itie, "G");
    if (status) {
      itie.i.itie.sched_export = delta_export;
      status = pf_rec_itie (&itie, "A");  /* Add a new "I" record       */
    } else {
      itie.i.itie.sched_export = itie.i.itie.sched_export + delta_export;
      status = pf_rec_itie (&itie, "M");  /* Modify existing "I" record */
    }
    return status;
  }
}

int compare( const void *key1, const void *key2 )
/* static int compare( const void *key1, const void *key2 ) */

/* This comparing function obtains the relative sort order of *key1 and
   *key2 upon the following fields:

   1. area1.
   2. bus1.
   3. area2.
   4. bus2.
   5. id.

 */

{
  int i = *((int *) key1), j = *((int *) key2), comp;
  char *area11, *area12, *area21, *area22, *bus11, *bus12, *bus21, *bus22,
       id1, id2;
  int sect1, sect2;

  if (i == j) {
    return 0;
  } else {
    if (i > 0) {
      area11 = br_flow[i].area1;
      area12 = br_flow[i].area2;
      bus11 = br_flow[i].bus1;
      bus12 = br_flow[i].bus2;
      id1 = br_flow[i].id;
      sect1 = br_flow[i].section;
    } else {
      area11 = br_flow[-i].area2;
      area12 = br_flow[-i].area1;
      bus11 = br_flow[-i].bus2;
      bus12 = br_flow[-i].bus1;
      id1 = br_flow[-i].id;
      sect1 = br_flow[-i].section;
    }
    if (j > 0) {
      area21 = br_flow[j].area1;
      area22 = br_flow[j].area2;
      bus21 = br_flow[j].bus1;
      bus22 = br_flow[j].bus2;
      id2 = br_flow[j].id;
      sect2 = br_flow[j].section;
    } else {
      area21 = br_flow[-j].area2;
      area22 = br_flow[-j].area1;
      bus21 = br_flow[-j].bus2;
      bus22 = br_flow[-j].bus1;
      id2 = br_flow[-j].id;
      sect2 = br_flow[-j].section;
    }
    comp = strcmp (area11, area21);
    if (comp == 0) comp = strcmp (bus11, bus21);
    if (comp == 0) comp = strcmp (area12, area22);
    if (comp == 0) comp = strcmp (bus12, bus22);
    if (comp == 0) comp = (unsigned int)id1 - (unsigned int)id2;
    if (comp == 0) comp = sect1 - sect2;

    return comp;
  }
}

void title ( int *lineno, int *pageno, FILE *fp_outfile, pf_comments *c, 
             int numcases, char *areaname)
{
  /* Write base case comments */

  int i;

  fprintf (fp_outfile, "\f\n\n");
  (*pageno)++;
  for (i=0; i < 3; i++) {
    if (strlen (c->h[i]) > 0) 
      fprintf (fp_outfile, " %s \n", &c->h[i][1]);
      (*lineno)++;
  }
  fprintf (fp_outfile, "\n INCREMENTAL report (DELTA) line flows in MW \
page No. %d \n\n", *pageno);
  fprintf (fp_outfile, " From bus     To bus     cir To area   Base Flow   ");
  for (i = 1; i <= numcases; i++) {
    fprintf (fp_outfile, "Incr %2d ", i);
  }
  (*lineno) += 6;
  if (strlen (areaname) > 0) {
    fprintf (fp_outfile, "\n From area %s \n\n", areaname);
    (*lineno) += 3;
  }
}

libcflow API Reference

The header file (cflowlib.h) used both by all CFLOW programs to define structures, constants, etc. in the libcflow library.

union input_data
#include <cflowlib.h>

Input data union.

Public Members

pf_AC_bus ACbus

Use for accessing AC bus input data.

pf_DC_bus DCbus

Use for accessing DC bus input data.

pf_branch branch

Use for accessing branch input data.

pf_LD LD

Use for accessing Two Terminal DC Line input data.

pf_LM LM

Use for accessing Multiterminal DC Line input data.

pf_E E

Use for accessing Equivalent Transmission Line Branch input data.

pf_L L

Use for accessing Balanced Transmission Line input data.

pf_T T

Use for accessing Transformer input data.

pf_TP TP

Use for accessing Phase Shifting Transformer input data.

pf_R R

Use for accessing Regulating Transformer (LTC voltage control) input data.

pf_RN RN

Use for accessing Regulating Transformer (Contraints on VAR flow via change to RQ type of limits are violated) input data.

pf_RQ RQ

Use for accessing Regulating Transformer (LTC VAR control) input data.

pf_RV RV

Use for accessing Regulating Transformer (Contraints on VAR flow via change to RP type of limits are violated) input data.

pf_RP RP

Use for accessing Regulating Transformer (LTC phase shifter) input data.

pf_RM RM

Use for accessing Regulating Transformer input data.

pf_RZ RZ

Use for accessing Series Compensated Rani Model input data.

pf_area area

Use for accessing area input data.

pf_itie itie

Use for accessing intertie input data.

pf_cbus cbus

Use for accessing continuation bus input data.

pf_qcurve qcurve

Use for accessing reactive power capability curve input data.

pf_xdata xdata

Use for accessing switched reactance input data.

char cmnt[120]

Use for accessing comment.

struct pf_AC_bus
#include <cflowlib.h>

This structure holds power flow input data for an AC bus. The fields type, owner, name, kV, and zone are the same for both AC and DC buses.

Public Members

char type[3]

Two character bus record type, for example, B, BS, BQ, etc.

char owner[4]

Three character bus owner.

char name[9]

Eight character bus name.

float kv

Base kV of the bus.

char zone[3]

Two character zone name.

int dummy1

Ignore. This is a dummy field used for alignment purposes.

float Pload

Real load in MW.

float Qload

Reactive load in MVAR.

float Pshunt

Real shunt in MW.

float Qshunt

Reactive shunt in MVAR.

float Pmax

Maximum real load in MW.

float Pgen

Scheduled real power in MW.

float Qsch_Qmax

Scheduled reactive load in MVAR (Qsch) or a real number designating maximum reactive power in MVAR (Qmax).

float Qmin

Minimum reactive power in MVAR.

float Vhold_Vmax

Voltage to hold in per unit (Vhold) or a real number designating a maximum voltage limit in per unit (Vmax), depending on the bus type.

float Vmin_Vdeg

Minimum voltage limit in per unit, or voltage angle for the BS bus

char rmt_name[9]

Eight character remote bus name.

float rmt_kv

Base kV of a remote bus.

char dummy2

Ignore. This is a dummy field used for alignment purposes.

float pct_vars

Percent vars supplied for control of remote bus.

struct pf_area
#include <cflowlib.h>

This structure holds power flow input data for control areas which can be made up of multiple zones.

Public Members

char type[3]

Record type; here “A” for area record.

char name[11]

Ten character area name.

char sbus_name[9]

Eight character area slack bus name.

float sbus_kv

Base kV of the area slack bus.

float sched_export

Scheduled export power from an area.

char zone0[3]

Two character zone defined to be in an area.

char zone1[3]

Two character zone defined to be in an area.

char zone2[3]

Two character zone defined to be in an area.

char zone3[3]

Two character zone defined to be in an area.

char zone4[3]

Two character zone defined to be in an area.

char zone5[3]

Two character zone defined to be in an area.

char zone6[3]

Two character zone defined to be in an area.

char zone7[3]

Two character zone defined to be in an area.

char zone8[3]

Two character zone defined to be in an area.

char zone9[3]

Two character zone defined to be in an area.

float max_Vpu

Maximum per unit voltage.

float min_Vpu

Minimum per unit voltage.

struct pf_area_soln
#include <cflowlib.h>

This structure holds power flow solution (output) data for control areas which can be made up of multiple zones.

Public Members

char type[3]

Two character record type.

float Pgen

Total area generation.

float Pload

Total area load.

float Ploss

Total area losses.

float Pexport

Total actual export.

struct pf_branch
#include <cflowlib.h>

This structure holds power flow input data for a branch record.

Public Members

char type[3]

Two character branch record type.

char owner[4]

Three character branch owner.

char bus1_name[9]

Bus 1 name.

float bus1_kv

Base kV for bus 1.

int meter

The line metering point for area tie lines.

1 = bus 1 end.

2 = bus 2 end.

If blank, metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus name 1 will be the metering point.

char bus2_name[9]

Bus 2 name.

float bus2_kv

Base kV for bus 2.

char ckt_id

Circuit identification if more than one parallel branch exists.

int section

Section number for making an equivalent for series elements (numeric). Program assembles series elements in numerical order of section numbers (need not be consecutive).

float total_rating

Total ampere rating for all lines.

int num_ckts

Number of parallel circuits represented by this record, for information purposes only. The equivalent impedance is entered in r, x, g, b for lines with equal legs.

float r

Per unit resistance at base kV and base MVA.

float x

Per unit reactance at base kV and base MVA.

float g

Per unit conductance G_pi/2 at base kV and MVA. This format is for balanced lines when Y_pi sending equals Y_pi receiving and only Y_pi needs to be input.

float b

Per unit susceptance B_pi/2 at base kV and MVA.

float tap1

Tap at bus1 of transformer, in kV for normal tap, in degrees for phase shifter.

float tap2

Tap at bus2 of transformer, in kV.

float alpha_N_deg

Initial firing angle in degrees at rectifier (DC lines).

float gamma_0_deg

Minimum margin angle in degrees at inverter (DC lines).

char descrip[9]

Unknown.

char date_in[4]

Energization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

char date_out[4]

De-nergization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

float thermal_rating

Thermal rating in Amps.

float bottleneck_rating

Bottleneck rating in Amps.

float emergency_rating

Emergency rating in MVA.

struct pf_branch_soln
#include <cflowlib.h>

This structure holds power flow solution data for branch records.

Public Members

char type[3]

Two character record type.

int num_ckts

If ckt id was “*””, contains number of parallels

float Pin

Real power flow at bus1, in MW. Positive indicates flow from bus1 toward bus2.

float Qin

Reactive power flow at bus1, in MVAR. Positive indicates flow from bus1 toward bus2.

float Pout

Real power flow at bus2, in MW. Negative indicates flow from bus1 to bus2 (i.e., without losses, Pout = -Pin).

float Qout

Reactive power flow at bus2, in MVAR. Negative indicates flow from bus1 to bus2.

float Ploss

Real losses, in MW (Pin + Pout).

float Qloss

Reactive losses, in Mvar (Qin + Qout).

float crit_line_load_amps

Largest current in any section of a line (amps).

float crit_line_rat_amps

Actual value of rating used (amps).

char crit_line_rat_code

Type of rating used – N, B, T, or E.

int crit_line_load_term

Largest flow in a transformer terminal (MVA).

float crit_xfmr_load_mva

Largest flow in a transformer (MVA).

float crit_xfmr_rat_mva

Actual value of rating used (MVA).

char crit_xfmr_rat_code

Type of rating used – N, B, T, or E.

int crit_xfmr_load_term

Largest flow in a transformer terminal (MVA).

float tot_line_load_pct

Percent line compensation (total negative reactance divided by total positive reactance).

float tot_line_load_amps

Line compensation in amps.

float tot_xfmr_load_pct

Percent loading on the transformer, using the indicated rating

float tot_xfmr_load_mva

Transformer load in apparent power (MVA).

float tap1

Final tap at bus1 of transformer, in kV for normal tap, in degrees for phase shifter.

float tap2

Final tap at bus2 of transformer, in kV.

struct pf_bus_AC_soln
#include <cflowlib.h>

This struct stores power flow solution values for an AC bus.

Public Members

char type[3]

Two character bus record type, for example, B, BS, BQ, etc.

float Pgen

Solved real power generation in MW.

float Qgen

Solved reactive power in MVAR.

float Vmag

Solved voltage magnitude in per unit.

float Vdeg

Solved voltage angle in degrees.

float Pload

Solved real load in MW.

float Qload

Solved reactive load in MVAR.

float Bshunt_used

Total shunt used, net of capacitors (+) and reactors (-).

float Bshunt_sch

Total shunt available, net of capacitors and reactors.

float Bshunt_used_cap

Capacitive shunt used, MVAR.

float Bshunt_sch_cap

Capacitive shunt available, MVAR.

float Bshunt_used_rx

Reactive shunt used, MVAR.

float Bshunt_sch_rx

Reactive shunt available, MVAR.

float Qunsch

MVARs produced, on a type BS or BE bus.

struct pf_bus_DC_soln
#include <cflowlib.h>

This struct stores power flow solution values for a DC bus.

Public Members

char type[3]

Two character bus record type.

float P_DC

AC real power into the DC bus, positive at the rectifier and negative at the inverter.

float Q_DC

AC reactive power into the DC bus, returned as a positive number.

float V_DC

DC terminal voltage (final voltage at commutating bus, in kV).

float converter_deg

Converter angle, alpha for rectifier, gamma for inverter, in degrees

float P_valve_losses

Difference between AC power and DC power.

float Q_valve_losses

Difference between AC power and DC power (same as Q_DC).

float dummy1

Ignore. This is a dummy field used for alignment purposes.

float dummy2

Ignore. This is a dummy field used for alignment purposes.

float dummy3

Ignore. This is a dummy field used for alignment purposes.

float dummy4

Ignore. This is a dummy field used for alignment purposes.

float dummy5

Ignore. This is a dummy field used for alignment purposes.

float dummy6

Ignore. This is a dummy field used for alignment purposes.

float dummy7

Ignore. This is a dummy field used for alignment purposes.

struct pf_case_stats
#include <cflowlib.h>

Miscellaneous case data.

Public Members

char PF_version[11]

Ten character string containing Powerflow version information.

float base_mva

Base MVA of the base case (normally 100.0).

int num_DC_systems

An integer count of the number of DC systems in the case.

int num_areas

An integer count of the number of areas in the case.

int num_ities

An integer count of the number of interties in the case.

int num_zones

An integer count of the number of zones in the case.

int num_owners

An integer count of the number of owners in the case.

int num_buses

An integer count of the number of buses in the case (both AC and DC)

int num_area_slack_buses

An integer count of the number of area slack buses in the case.

int num_DC_buses

An integer count of the number of dc buses in the case.

int num_AGC_buses

An integer count of the number of buses with AGC control in the case.

int num_BX_buses

An integer count of the number of BX (constant V using switched Q) buses in the case.

int num_adjustable_buses

An integer count of the number of adjustable buses in the case.

int num_pct_var_ctrl_buses

An integer count of the number of buses with percent VAR control in the case.

int num_branches

An integer count of the number of branches in the case.

int num_circuits

An integer count of the number of circuits in the case. All parallel lines count as one circuit.

int num_DC_lines

An integer count of the number of DC linse in the case.

int num_LTC_xfmrs

An integer count of the number of LTC transformers in the case.

int num_phase_shifters

An integer count of the number of phase shifters in the case.

int case_soln_status

An integer containing the solution status. Corresponds to enumerated variables as follows:

1 = NO_CASE (no case data loaded)

2 = UNSOLVED (netdata loaded)

5 = SOLVED (successful solution, or solved case loaded)

6 = SAVED (solved case has been saved)

7 = DIVERGED (unsuccessful solution - diverged)

int num_diff_kv

An integer count of the number of unique kVs in the case.

int num_rec_types

An integer count of the number of unique record types in the case.

struct pf_cbus
#include <cflowlib.h>

This structure holds power flow input data for continuation bus (+) records.

Public Members

char type[3]

Two character bus record type, for example, “+””, “+A”, etc.

char owner[4]

Three character bus owner.

char name[9]

Eight character bus name.

float kv

Base kV of the bus.

char code_year[3]

Two character extension of type.

float Pload

Real load in MW belonging to this owner.

float Qload

Reactive load in MVAR belonging to this owner.

float Gshunt

Fixed real shunt in MW.

float Bshunt

Fixed reactive shunt in MVAR.

float Pgen

Scheduled real power in MW for this owner.

float Qgen_Qmax

Scheduled reactive power in MVAR (Qgen) or maximum reactive power in MVAR (Qmax).

float Qmin

Minimum reactive power in MVAR.

struct pf_cbus_soln
#include <cflowlib.h>

This structure holds power flow solution (output) data for continuation bus (+) records.

Public Members

char type[3]

Two character bus record type, for example, “+””, “+A”, etc.

float Pgen

Solved real power generation in MW.

float Qgen

Solved reactive power generation in MVAR.

float Pload

Solved real load (same as input).

float Qload

Solved reactive load (same as input).

float Gshunt

Solved real shunt.

float Bshunt

Solved reactive shunt.

struct pf_comments
#include <cflowlib.h>

Comment card data.

Public Members

char case_name[11]

Ten character string containing caseid.

char case_desc[21]

Twenty character string containing case description.

char h[3][133]

A character array containing case headers. The first one, h[0], is generated by IPF, and contains the program version, the caseid and description, and the date of the run. The other two are user-specified.

char c[20][121]

A character array containing case comments.

struct pf_DC_bus
#include <cflowlib.h>

This structure holds power flow input data for a DC bus. The fields type, owner, name, kV, and zone are the same for both AC and DC buses.

Public Members

char type[3]

Two character bus record type.

char owner[4]

Three character bus owner.

char name[9]

Eight character bus name.

float kv

Base kV of the bus.

char zone[3]

Two character zone name.

int bridges_per_ckt

Number of dc bridges per circuit.

float smooth_rx_mh

Smoothing reactance in millihenries (mH).

float alpha_min_deg

Alpha_min in degrees.

float alpha_stop_deg

Alpha_stop in degrees.

float valve_drop_per_bridge_volts

Voltage drop per valve.

float bridge_current_rating_amps

DC current rating.

float alpha_gamma_N_deg

Alpha_N or gamma_N in degrees.

float gamma_0_deg

Gamma_0 in degrees.

float P_sched

Scheduled power MW.

float V_sched

Scheduled voltage kV.

float dummy1

Ignore. This is a dummy field used for alignment purposes.

char commutating_bus_name[9]

Eight character commutating bus name.

float commutating_bus_kv

Commutating bus kV.

char converter_code

One character converter code.

float dummy2

Ignore. This is a dummy field used for alignment purposes.

struct pf_E
#include <cflowlib.h>

This structure holds power flow input data for a equivalent transmission line record (asymmetric pi representation).

Public Members

char type[3]

Two character record type “E”.

char owner[4]

Three character owner.

char bus1_name[9]

Bus 1 name.

float bus1_kv

Base kV for bus 1.

int meter

The line metering point for area tie lines.

1 = bus 1 end.

2 = bus 2 end.

If blank, metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus name 1 will be the metering point.

char bus2_name[9]

Bus 2 name.

float bus2_kv

Base kV for bus 2.

char ckt_id

Circuit identification if more than one parallel line exists.

int section

Section number for making an equivalent for series elements (numeric). Program assembles series elements in numerical order of section numbers (need not be consecutive).

float total_rating

Total ampere rating for all lines.

int num_ckts

Number of parallel circuits represented by this record, for information purposes only. The impedance is entered in r, x, g1, b1, g2, b2.

float r

Per unit resistance at base kV and base MVA.

float x

Per unit reactance at base kV and base MVA.

float g1

Per unit conductance at base kV and MVA for bus 1 end of line.

float b1

Per unit susceptance at base kV and MVA for bus 1 end of line.

float g2

Per unit conductance at base kV and MVA for bus 2 end of line.

float b2

Per unit susceptance at base kV and MVA for bus 2 end of line..

float dummy1

Ignore. This is a dummy field used for alignment purposes.

float dummy2

Ignore. This is a dummy field used for alignment purposes.

char dummy3[9]

Ignore. This is a dummy field used for alignment purposes.

char date_in[4]

Energization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

char date_out[4]

De-nergization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

float thermal_rating

Thermal rating in Amps.

float bottleneck_rating

Bottleneck rating in Amps.

float dummy4

Ignore. This is a dummy field used for alignment purposes.

struct pf_itie
#include <cflowlib.h>

This structure holds power flow input data for intertie records. It indicates the two areas between which interchange must be scheduled.

Public Members

char type[3]

Two character record type, here “I” for intertie record.

char area1_name[11]

Ten character area1 name.

char area2_name[11]

Ten character area2 name.

float sched_export

Scheduled export power.

struct pf_itie_soln
#include <cflowlib.h>

This structure holds power flow solution (output) data for interties which can be.

Public Members

char type[3]

Two character record type.

float Pexport

Solution export power.

float Pcirc

Solution circulating current.

int input_exists

An integer indicating whether intertie values are internally or externally generated.

0= no input record (internally generated itie)

1= input data is from input record.

struct pf_L
#include <cflowlib.h>

This structure holds power flow input data for an AC line record (symmetric pi representation).

Public Members

char type[3]

Two character record type “L”.

char owner[4]

Three character owner.

char bus1_name[9]

Bus 1 name.

float bus1_kv

Base kV for bus 1.

int meter

The line metering point for area tie lines.

1 = bus 1 end.

2 = bus 2 end.

If blank, metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus name 1 will be the metering point.

char bus2_name[9]

Bus 2 name.

float bus2_kv

Base kV for bus 2.

char ckt_id

Circuit identification if more than one parallel branch exists.

int section

Section number for making an equivalent for series elements (numeric). Program assembles series elements in numerical order of section numbers (need not be consecutive).

float total_rating

Total ampere rating for all lines.

int num_ckts

Number of parallel circuits represented by this record, for information purposes only.

float r

Per unit resistance at base kV and base MVA.

float x

Per unit reactance at base kV and base MVA.

float g

Per unit conductance at base kV and MVA.

float b

Per unit susceptance at base kV and MVA.

float miles

Length of the line in miles - information only.

float dummy1

Ignore. This is a dummy field used for alignment purposes.

float dummy2

Ignore. This is a dummy field used for alignment purposes.

float dummy3

Ignore. This is a dummy field used for alignment purposes.

char descrip[9]

Information only.

char date_in[4]

Energization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

char date_out[4]

De-nergization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

float thermal_rating

Thermal rating in Amps.

float bottleneck_rating

Bottleneck rating in Amps.

float dummy4

Ignore. This is a dummy field used for alignment purposes.

struct pf_LD
#include <cflowlib.h>

This structure holds power flow input data for a two terminal DC line record.

Public Members

char type[3]

Two character record type “LD”.

char owner[4]

Three character owner.

char bus1_name[9]

Converter bus 1 name.

float bus1_kv

Base kV for bus 1.

int meter

The line metering point for area tie lines.

1 = bus 1 end.

2 = bus 2 end.

If blank, metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus name 1 will be the metering point.

char bus2_name[9]

Converter bus 2 name.

float bus2_kv

Base kV for bus 2.

char I_or_R_control

Inverter or rectifier control - Enter ‘R’ for rectifiier control or ‘I’ for inverter control (point of DC line in which scheduled power is measured).

int dummy1

Ignore. This is a dummy field used for alignment purposes.

float total_rating

Total ampere rating for all lines.

int dummy2

Ignore. This is a dummy field used for alignment purposes.

float R

DC Line resistance, ohms.

float L_mh

DC line inductance, millihenries.

float C_uf

DC line capacitance, microfarads.

float P_sched

Schedule DC power (MW) - Scheduled DC power in megawatts from converter 1 to 2 metered at the end indicated by I or R in I_or_R_control.

float V_sched

Schedule DC line volts (kV) - at rectifier end of DC line.

float miles

How many miles long the line is.

float alpha_N_deg

Initial firing angle in degrees at rectifier.

float gamma_0_deg

Minimum margin angle in degrees at inverter.

char dummy3[9]

Ignore. This is a dummy field used for alignment purposes.

char dummy4[4]

Ignore. This is a dummy field used for alignment purposes.

char dummy5[4]

Ignore. This is a dummy field used for alignment purposes.

float thermal_rating

Thermal rating in Amps.

float bottleneck_rating

Bottleneck rating in Amps.

float dummy6

Ignore. This is a dummy field used for alignment purposes.

struct pf_LM
#include <cflowlib.h>

This structure holds power flow input data for a multiterminal DC line record.

Public Members

char type[3]

Two character record type “LM”.

char owner[4]

Three character owner.

char bus1_name[9]

Converter bus 1 name.

float bus1_kv

Base kV for bus 1.

int meter

The line metering point for area tie lines.

1 = bus 1 end.

2 = bus 2 end.

If blank, metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus name 1 will be the metering point.

char bus2_name[9]

Converter bus 2 name.

float bus2_kv

Base kV for bus 2.

char dummy1

Ignore. This is a dummy field used for alignment purposes.

int dummy2

Ignore. This is a dummy field used for alignment purposes.

float total_rating

Total Current (I) Rating in Amps - Maximum DC line current in ampere.

int dummy3

Ignore. This is a dummy field used for alignment purposes.

float R

DC Line resistance, ohms.

float L_mh

DC line inductance, millihenries.

float C_uf

DC line capacitance, microfarads.

float dummy4

Ignore. This is a dummy field used for alignment purposes.

float dummy5

Ignore. This is a dummy field used for alignment purposes.

float miles

Length of the line in miles - information only.

float dummy6

Ignore. This is a dummy field used for alignment purposes.

float dummy7

Ignore. This is a dummy field used for alignment purposes.

char dummy8[9]

Ignore. This is a dummy field used for alignment purposes.

char date_in[4]

Energization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

char date_out[4]

De-nergization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

float thermal_rating

Thermal rating in Amps.

float bottleneck_rating

Bottleneck rating in Amps.

float dummy9

Ignore. This is a dummy field used for alignment purposes.

struct pf_qcurve
#include <cflowlib.h>

This structure holds power flow input data for reactive power capability.

Public Members

char type[3]

Two character record type - here “QP”, “QM”, or “QN”.

char PU_code[3]

Two character code – PU for per unit or blank for kV values.

char active

One character code – “A” for active or “*”” for inactive.

char bus_name[9]

Eight character bus name.

float bus_kv

Base kV of the bus.

float Pgen0

Real power levels in MW, for the reactive capability curve. Value is Qmin0 for QN records, Qmax0 for QM cards, and Pgen0 for QP cards, but is always named Pgen0, etc.

float Pgen1

Real power levels in MW, for the reactive capability curve.

float Pgen2

Real power levels in MW, for the reactive capability curve.

float Pgen3

Real power levels in MW, for the reactive capability curve.

float Pgen4

Real power levels in MW, for the reactive capability curve.

float Pgen5

Real power levels in MW, for the reactive capability curve.

float Pgen6

Real power levels in MW, for the reactive capability curve.

float Pgen7

Real power levels in MW, for the reactive capability curve.

float Pgen8

Real power levels in MW, for the reactive capability curve.

float Pgen9

Real power levels in MW, for the reactive capability curve.

struct pf_qcurve_soln
#include <cflowlib.h>

This structure holds power flow solution (output) data for reactive power cability curves.

Public Members

char type[3]

Two character record type – here “QP”, “QM”, or “QN”.

float Pgen

Real power output level in MW.

float Qgen

Reactive power output level in MVAR.

struct pf_R
#include <cflowlib.h>

This structure holds power flow input data for regulating transformer record. Struct for R, RN, RQ, RV type records.

Public Members

char type[3]

Two character record type “R”.

char owner[4]

Three character owner.

char bus1_name[9]

Bus 1 name.

float bus1_kv

Base kV for bus 1.

int var_tap_side

Variable tap side if T_max and T_min cannot orient T_x.

0 - Low alpha is fixed

1 - Bus 1 is variable

2 - Bus 2 is variable

char bus2_name[9]

Bus 2 name.

float bus2_kv

Base kV for bus 2.

char dummy1

Ignore. This is a dummy field used for alignment purposes.

int dummy2

Ignore. This is a dummy field used for alignment purposes.

float dummy3

Ignore. This is a dummy field used for alignment purposes.

int num_taps

Total number of LTC taps. If blank, assumes continuous action.

float dummy4

Ignore. This is a dummy field used for alignment purposes.

float dummy5

Ignore. This is a dummy field used for alignment purposes.

float dummy6

Ignore. This is a dummy field used for alignment purposes.

float dummy7

Ignore. This is a dummy field used for alignment purposes.

float max_tap

Maximum kV tap.

float min_tap

Minimum kV taps.

float dummy8

Ignore. This is a dummy field used for alignment purposes.

float dummy9

Ignore. This is a dummy field used for alignment purposes.

char rmt_bus_name[9]

Controlled bus name.

char date_in[4]

Energization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

char date_out[4]

De-nergization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

float rmt_bus_kv

Controlled bus kV.

float Qmax

Maximum reactive (MVAR) flow through the transformer.

float Qmin

Minimum reactive (MVAR) flow through the transformer.

struct pf_rec
#include <cflowlib.h>

Record data.

Public Members

input_data i

Used to access power flow input data.

solution_data s

Used to access power flow solution (output) data.

struct pf_RM
#include <cflowlib.h>

This structure holds power flow input data for regulating transformer RM, RP record types.

Public Members

char type[3]

Two character record type “RM”.

char owner[4]

Three character owner.

char bus1_name[9]

Bus 1 name.

float bus1_kv

Base kV for bus 1.

int var_tap_side

Variable tap side if T_max and T_min cannot orient T_x.

0 - Low alpha is fixed

1 - Bus 1 is variable

2 - Bus 2 is variable

char bus2_name[9]

Bus 2 name.

float bus2_kv

Base kV for bus 2.

char dummy1

Ignore. This is a dummy field used for alignment purposes.

int dummy2

Ignore. This is a dummy field used for alignment purposes.

float dummy3

Ignore. This is a dummy field used for alignment purposes.

int num_taps

Total number of LTC taps.

float dummy4

Ignore. This is a dummy field used for alignment purposes.

float dummy5

Ignore. This is a dummy field used for alignment purposes.

float dummy6

Ignore. This is a dummy field used for alignment purposes.

float dummy7

Ignore. This is a dummy field used for alignment purposes.

float max_phase_shift_deg

Maximum angle in degrees.

float min_phase_shift_deg

Minimum angle in degrees.

float dummy8

Ignore. This is a dummy field used for alignment purposes.

float dummy9

Ignore. This is a dummy field used for alignment purposes.

char rmt_bus_name[9]

Controlled bus name.

char date_in[4]

Energization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

char date_out[4]

De-nergization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

float rmt_bus_kv

Controlled bus kV.

float Pmax

Maximum real power (MW) flow through the transformer.

float Pmin

Maximum real power (MW) flow through the transformer.

struct pf_RZ
#include <cflowlib.h>

This structure holds power flow input data for Rapid Adjustment of Network Impedance (RANI) device. It represents a series connected thyristor which changes its series impedance to control power or voltage.

Public Members

char type[3]

Two character record type “RZ”.

char owner[4]

Three character owner.

char bus1_name[9]

Bus 1 name.

float bus1_kv

Base kV for bus 1.

int var_tap_side

Variable tap side if T_max and T_min cannot orient T_x.

0 - Low alpha is fixed

1 - Bus 1 is variable

2 - Bus 2 is variable

char bus2_name[9]

Bus 2 name.

float bus2_kv

Base kV for bus 2.

char ckt_id

Circuit identification if more than one parallel transformer exists.

int section

Section number for making an equivalent for series elements (numeric). Program assembles series elements in numerical order of section numbers (need not be consecutive).

float I_rate

Rated current.

int rani_type

TYPE 1, 2, or 3

TYPE 1 - Control Pc using Xij TYPE 2 - Control V using Xij TYPE 3 - Control V using Bis

float Pc_max

Pc_max in MW

float Pc_min

Pc_min in MW

float Xij_max

Per unit maximum reactance.

float Xij_min

Per unit minimum reactance.

float Bis_max

Per unit minimum reactance.

float Bis_min

Per unit minimum reactance.

float dummy1

Ignore. This is a dummy field used for alignment purposes.

float dummy2

Ignore. This is a dummy field used for alignment purposes.

char dummy3[9]

Ignore. This is a dummy field used for alignment purposes.

char dummy4[4]

Ignore. This is a dummy field used for alignment purposes.

char dummy5[4]

Ignore. This is a dummy field used for alignment purposes.

float dummy6

Ignore. This is a dummy field used for alignment purposes.

float dummy7

Ignore. This is a dummy field used for alignment purposes.

float dummy8

Ignore. This is a dummy field used for alignment purposes.

struct pf_T
#include <cflowlib.h>

This structure holds power flow input data for transformer record.

Public Members

char type[3]

Two character record type “T”.

char owner[4]

Three character owner.

char bus1_name[9]

Bus 1 name.

float bus1_kv

Base kV for bus 1.

int meter

Metering point.

1 = bus 1 end.

2 = bus 2 end.

If blank, metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus name 1 will be the metering point.

char bus2_name[9]

Bus 2 name.

float bus2_kv

Base kV for bus 2.

char ckt_id

Circuit identification if more than one parallel transformer exists.

int section

Section number for making an equivalent for series elements (numeric). Program assembles series elements in numerical order of section numbers (need not be consecutive).

float total_rating

Total ampere rating.

int num_ckts

Number of parallel circuits represented by this record, for information purposes only.

float r

Per unit resistance at base kV and base MVA.

float x

Per unit reactance at base kV and base MVA.

float g

Per unit conductance at base kV and MVA.

float b

Per unit susceptance at base kV and MVA.

float tap1

Fixed bus 1 TAP which describe bus 1 relative to bus 2.

float tap2

Fixed bus 2 TAP.

float dummy1

Ignore. This is a dummy field used for alignment purposes.

float dummy2

Ignore. This is a dummy field used for alignment purposes.

char dummy3[9]

Ignore. This is a dummy field used for alignment purposes.

char date_in[4]

Energization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

char date_out[4]

De-nergization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

float thermal_rating

Thermal rating in Amps.

float bottleneck_rating

Bottleneck rating in Amps.

float emergency_rating

Emergency rating in MVA.

struct pf_TP
#include <cflowlib.h>

This structure holds power flow input data for phase shifting transformer record.

Public Members

char type[3]

Two character record type “TP”.

char owner[4]

Three character owner.

char bus1_name[9]

Bus 1 name.

float bus1_kv

Base kV for bus 1.

int meter

The line metering point for area tie lines.

1 = bus 1 end.

2 = bus 2 end.

If blank, metering point will be identified (1) by location where line ownership differs from bus ownership or (2) when buses at end of tie line have same ownership, then the bus name 1 will be the metering point.

char bus2_name[9]

Bus 2 name.

float bus2_kv

Base kV for bus 2.

char ckt_id

Circuit identification if more than one parallel transformer exists.

int section

Section number for making an equivalent for series elements (numeric). Program assembles series elements in numerical order of section numbers (need not be consecutive).

float total_rating

Total ampere rating.

int num_ckts

Number of parallel circuits represented by this record, for information purposes only.

float r

Per unit resistance at base kV and base MVA.

float x

Per unit reactance at base kV and base MVA.

float g

Per unit conductance at base kV and MVA.

float b

Per unit susceptance at base kV and MVA.

float phase_shift_deg

Fixed bus 1 TAP or fixed phase shift in degrees which describe bus 1 relative to bus 2.

float tap2

Fixed bus 2 TAP or blank for fixed phase shifter.

float dummy1

Ignore. This is a dummy field used for alignment purposes.

float dummy2

Ignore. This is a dummy field used for alignment purposes.

char dummy3[9]

Ignore. This is a dummy field used for alignment purposes.

char date_in[4]

Energization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

char date_out[4]

De-nergization Date in format “MYY”. Where M = {1,2,3,4,5,6,7,8,9,O,N,D} and YY = last two digits of year.

float thermal_rating

Thermal rating in Amps.

float bottleneck_rating

Bottleneck rating in Amps.

float emergency_rating

Emergency rating in MVA.

struct pf_xdata
#include <cflowlib.h>

This structure holds power flow input data for switched reactance devices (capacitor and reactor banks).

Public Members

char type[3]

Two character array designating the record type — here “X” for switched reactance record.

char owner[4]

Three character array designating an owner.

char bus_name[9]

Eght character bus name.

float bus_kv

Base kV of the BX bus.

char rmt_name[9]

Eight character remote bus name.

float rmt_kv

Remote bus base kV.

int seg1_num_steps

Number of each reactance value available (integer).

float seg1_delta_mva

Magnitude of reactance values available.

int seg2_num_steps

Number of each reactance value available (integer).

float seg2_delta_mva

Magnitude of reactance values available.

int seg3_num_steps

Number of each reactance value available (integer).

float seg3_delta_mva

Magnitude of reactance values available.

int seg4_num_steps

Number of each reactance value available (integer).

float seg4_delta_mva

Magnitude of reactance values available.

int seg5_num_steps

Number of each reactance value available (integer).

float seg5_delta_mva

Magnitude of reactance values available.

int seg6_num_steps

Number of each reactance value available (integer).

float seg6_delta_mva

Magnitude of reactance values available.

int seg7_num_steps

Number of each reactance value available (integer).

float seg7_delta_mva

Magnitude of reactance values available.

int seg8_num_steps

Number of each reactance value available (integer).

float seg8_delta_mva

Magnitude of reactance values available.

struct pf_xdata_soln
#include <cflowlib.h>

This structure holds power flow solution (output) data for switched reactance (capacitor and reactor banks) devices.

Public Members

char type[3]

Two character array designating the record type — here “X” for switched reactance record.

int seg1_sch_units

Scheduled number of steps.

int seg1_used_units

Actual number of steps used.

float seg1_mvar_per_unit

Actual reactance amounts used per step.

int seg2_sch_units

Scheduled number of steps.

int seg2_used_units

Actual number of steps used.

float seg2_mvar_per_unit

Actual reactance amounts used per step.

int seg3_sch_units

Scheduled number of steps.

int seg3_used_units

Actual number of steps used.

float seg3_mvar_per_unit

Actual reactance amounts used per step.

int seg4_sch_units

Scheduled number of steps.

int seg4_used_units

Actual number of steps used.

float seg4_mvar_per_unit

Actual reactance amounts used per step.

int seg5_sch_units

Scheduled number of steps.

int seg5_used_units

Actual number of steps used.

float seg5_mvar_per_unit

Actual reactance amounts used per step.

int seg6_sch_units

Scheduled number of steps.

int seg6_used_units

Actual number of steps used.

float seg6_mvar_per_unit

Actual reactance amounts used per step.

int seg7_sch_units

Scheduled number of steps.

int seg7_used_units

Actual number of steps used.

float seg7_mvar_per_unit

Actual reactance amounts used per step.

int seg8_sch_units

Scheduled number of steps.

int seg8_used_units

Actual number of steps used.

float seg8_mvar_per_unit

Actual reactance amounts used per step.

union solution_data
#include <cflowlib.h>

Solution (output) data union.

Public Members

pf_bus_AC_soln ACbus

Use for accessing AC bus solution (output) data.

pf_bus_DC_soln DCbus

Use for accessing DC bus solution (output) data.

pf_branch_soln branch

Use for accessing branch solution (output) data.

pf_area_soln area

Use for accessing area solution (output) data.

pf_itie_soln itie

Use for accessing intertie solution (output) data.

pf_cbus_soln cbus

Use for accessing continuatino bus solution (output) data.

pf_qcurve_soln qcurve

Use for accessing reactive capability curve solution (output) data.

pf_xdata_soln xdata

Use for accessing switched reactance solution (output) data.

file cflowlib.h

Defines

CFLOW_IPC_BUFF_SIZE

This is the byte size of the in and out buffers used by CLFOW.

Typedefs

typedef pf_R pf_RN
typedef pf_R pf_RQ
typedef pf_R pf_RV
typedef pf_RM pf_RP

Enums

enum pf_list_type

This is an enumeration of options that you can use in calls to pf_get_list().

Values:

enumerator AREA_LIST

A list of the different area names in the case. String length 11. Max size 50.

enumerator BUS_LIST

A list of the different bus names in the case.

enumerator KV_LIST

A list of the different bus kV’s in the case. String length 4. Max size 150.

enumerator OWNER_LIST

A list of the different owners in the case. String length 4. Max size 450.

enumerator REC_TYPE_LIST

A list of the different record types in the case. String length 3. Max size 50.

enumerator ZONE_LIST

A list of the different zones in the case.. String length 3. Max size 150.

Functions

void pf_cflow_exit(void)

Close the data link to the powerflow engine (ipfsrv).

Call this in to “disconnect” properly from ipfsrv.

Returns

Has no return; it calls the exit function.

void pf_cflow_init(int argc, char *argv[])

Initialize the data link to the powerflow engine (ipfsrv).

Establishes a socket connection with the Powerflow process (ipfsrv). Other command line arguments that have been collected by the argv mechanism may be used by the CFLOW program. The command line arguments are “shifted left” such that *argv[1] contains the first command line argument intended for the CFLOW program and argc is updated to reflect the count of those arguments only.

Returns

Returns 0 if it is successful; otherwise, it calls the exit function.

int pf_cflow_ipc(void)

Buffer interface to powerflow.

A low-level interface to the interprocess communication that uses two global buffers pf_cflow_inbuf and pf_cflow_outbuf. This routine is used by most of the other pf functions; however, you can also use it directly. You put valid PCL commands and associated WSCC-formatted data records into pf_cflow_outbuf, call pf_cflow_ipc, then look for the results in pf_cflow_inbuf.

A list and description of the valid PCL commands is in the documentation.

Returns

Returns 0 if it is successful; otherwise, it calls the exit function.

int pf_del_area(char *area)

Delete area by name.

Delete an area along will all buses and all associated branches in the area.

error = pf_del_area("ARIZONA"); 

See also

pf_del_zone

Parameters

area[in] A string representing an area name.

Returns

Returns 0 (zero) if it is successful; otherwise, it returns 1.

int pf_del_zone(char *zone)

Delete zone by name.

Delete a zone along will all buses and all associated branches in the zone.

error = pf_del_zone("NA"); 

See also

pf_del_area

Parameters

zone[in] A string representing a zone name.

Returns

Returns 0 (zero) if it is successful; otherwise, it returns 1.

int pf_rename_area(char *oldname, char *newname)

Rename an area.

Utilizes the powerflow change records of type Z.

See also

pf_rename_zone pf_rename_bus

Parameters
  • oldname[in] A string representing an area name to be changed.

  • newname[in] A string representing an area name that will become the new name.

Returns

Returns 0 (zero) if it is successful; otherwise, it returns 1.

int pf_rename_bus(char *oldname, float oldkv, char *newname, float newkv)

Rename a bus and re-map all associated data to the new name.

Utilizes the powerflow change records of type Z.

See also

pf_rename_zone pf_rename_area

Parameters
  • oldname[in] A string representing a bus name to be changed.

  • oldkv[in] A floating point number representing the base kV of the bus.

  • newname[in] A string representing an area name that will become the new name.

  • newkv[in] A floating point number representing the new base kV.

Returns

Returns 0 (zero) if it is successful; otherwise, it returns 1.

int pf_rename_zone(char *oldname, char *newname)

Rename a zone.

All zone fields for all records in a zone are updated. If the new zone name already exists, a combined zone results if adjacency permits; otherwise, it is an error.

Utilizes the powerflow change records of type Z.

Parameters
  • oldname[in] A string representing a zone name to be replaced.

  • newname[in] A string representing the new zone name.

Returns

Returns 0 (zero) if it is successful; otherwise, it returns 1.

int pf_load_changes(char *filename)

Load changes into case.

Passes an ASCII change file name to ipfsrv so that it can read and interpret the file or filename contains an “*\n” followed by change records which are to be processed by ipfsrv. The records must be separated by “\n”.

Parameters

filename[in] A string representing a file name, or “*\n”, followed by valid change records.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_load_netdata(char *filename)

Load network data.

Passes a network data file name to the ipfsrv process so that it can read and interpret the network data file. Or contains an “*\n” followed by bus and branch records which are to be processed by ipfsrv. The records must be separated by “\n”. If a case is currently loaded, it is overwritten and the data is lost. The case loaded is not usable by GUI after CFLOW has completed.

Parameters

filename[in] A string representing a file name or an “*\n” followed by bus and branch records.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_load_oldbase(char *filename)

Load a base case.

Passes a base case filename to the ipfsrv process so that it can read and interpret the file as an “oldbase”. If a case is currently loaded, it is overwritten and the data is lost.

Parameters

filename[in] A string representing a file name followed by an optional, “rebuild = ON|OFF”.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_put_inrec(char *record)

Send WSCC change record to powerflow.

Changes, adds, or deletes an input data record for Powerflow. See Record Format section for a description of input record types and rules for adding, changing, and deleting. This function provides a means of inputting records for which there is not a specific function such as factor change (P), although it can be used for inputting any WSCC input record

Parameters

record – A string containing WSCC formatted data for a Powerflow input data record.

Returns

Returns 0 (zero) if it is successful; otherwise, it returns 1.

int pf_rec_area(pf_rec *r, char *action)

Retrieves, modifies, adds, or deletes area data.

Parameters
  • r[inout] A pointer to a structure of type pf_rec supplied by the calling routine.

  • action[in]

    A string designating the action to be performed on an area record. See below for the codes and their meanings. Either upper or lower case is acceptable.

    ”F” Retrieves the first area record.

    ”N” Retrieves the next area record. (Area name must be valid.)

    ”G” Retrieves the rest of the area record. (Area name must be valid.)

    ”D” Deletes an area record. (Area name must be valid.)

    ”A” Adds an area record. (All required data fields must be valid. See the IPF Batch User’s Guide .)

    ”M” Modifies an area record. (All required data fields must be valid. See the IPF Batch User’s Guide .)

    ”E” Eliminates all area records. (area_rec is ignored and can be set to zero. This code does not delete any zones, buses, etc. It places all zones in area “blank.”)

    “O” Retrieves the solution output data. (The case must be solved and the area name must be valid.)

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_rec_branch(pf_rec *r, char *action)

Retrieves, modifies, adds, or deletes branch records.

To access individual fields of the records use the union member name, for example, using a declaration of pf_rec br; then br.i.branch.tap1 would reference the input tap1 field for a transformer. If you were looking at an E-type line instead, the variable br.i.branch.tap1 would contain the g2 value, but to make it more obvious what you were actually doing, you would probably want to use the union member name br.i.E.g2, instead. All of the structures and unions are declared in cflowlib.h.

Parameters
  • r[inout] A pointer to a structure of type pf_rec, supplied by the calling routine.

  • action[in]

    A string designating the action to be performed on a branch record. See below for the codes and their meanings. Either upper or lower case is acceptable.

    ”F3” Retrieves the first branch record associated with bus1, bus2, and circuit ID. bus1_name, bus1_kV, bus2_name, bus2_kV, and ckt_id must be valid.

    ”N3” Retrieves the next branch record associated with bus1, bus2, and circuit ID. See notes below.

    ”F2” Retrieves the first branch record associated with bus1 and bus2. bus1_name, bus1_kV, bus2_name, bus2_kV must be valid.

    ”N2” Retrieves the next branch record associated with bus1 and bus2. See notes below.

    ”F1” Retrieves the first branch record associated with bus1. bus1_name and bus1_kV must be valid.

    ”N1” Retrieves the next branch record associated with bus1. See notes below.

    ”F” Retrieves the first branch record disregarding bus association. All id fields may be null or zero.

    ”N” Retrieves the next branch record disregarding bus association. See notes below.

    ”G” Retrieves the rest of the branch record. All id fields must be valid to get a specific record.

    ”D” Deletes a branch record. All id fields must be valid.

    ”A” Adds a branch record. All fields appropriate for the branch type must be valid

    ”M” Modifies a branch record. All fields appropriate for the branch type must be valid.

    ”O” Retrieves the solution output data.

    Notes:

    1) with a “wildcard” circuit ID of ” ” or “*” and a section code of zero (or blank) -“G” and “F3” are the same as “F2”.

    2) with a valid (non-“wildcard”) circuit ID and a section code of zero (or blank) -“G” is the same as “F3”.

    3) codes “F”, “N”, “N1”, “N2”, and “N3” do not need any data specified in the

    pf_rec , however the first use of “N”, “N1”, “N2”, and “N3” relies on initialization with a “F”, “F1”, “F2”, “F3”, or “G” code on a previous call.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_rec_bus(pf_rec *r, char *action)

Retrieves, modifies, adds, or deletes bus records.

pf_rec is a union of both input data (i) and solution data (s). To access individual fields of the records use the union member name, for example, using a declaration of pf_rec b; then b.i.ACbus.Pload would contain the MW load for an AC bus, and the smoothing reactance for a DC bus, but to make it more obvious what you were actually doing, you would probably want to use the union member name b.i.DCbus.smooth_rx_mh instead, when dealing with a DC bus. If you are retrieving all buses, you can use the ACbus designation for the type, owner, name, kv, and zone fields; the contents of these fields is the same regardless of the bus type.

Parameters
  • r[inout] A pointer to a structure of type pf_rec supplied by the calling routine.

  • action[in]

    A string designating the action to be performed on an intertie record. See below for the codes and their meanings. Either upper or lower case is acceptable.

    ”F” Retrieves the first bus record.

    ”N” Retrieves the next bus record. (Name and kV must be valid.)

    ”G” Retrieves the rest of the bus record. (Name and kV must be valid.)

    ”D” Deletes a bus record. (Name and kV must be valid.)

    ”A” Adds a bus record. (All data fields must be valid. See the Record Formats section.)

    ”M” Modifies a bus record. (All data fields must be valid. See the Record Formats section.)

    ”O” Retrieves the solution output data. (The case must be solved and name and kV must be valid.)

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_rec_cbus(pf_rec *r, char *action)

Retrieves, modifies, adds, or deletes continuation bus (+) data. Note that cbus data is always associated with particular buses.

Parameters
  • r[inout] A pointer to a structure of type pf_rec, supplied by the calling routine.

  • action[in]

    A string designating the action to be performed on a continuation bus record. See the table below for the codes and their meanings. Either upper or lower case is acceptable.

    ”F1” Retrieves the first continuation bus record associated with a given bus (name, kV).

    ”N1” Retrieves the next cbus record associated with a given bus. (All ID fields must be valid. See the Record Formats section.)

    ”G” Retrieves the rest of the cbus record. (All ID fields must be valid. See the Record Formats section.)

    ”D” Deletes a cbus record. (All ID fields must be valid. See the Record Formats section.)

    ”A” Adds a cbus record. (All data fields must be valid. See the Record Formats section.)

    ”M” Modifies a cbus record. (All data fields must be valid. See the Record Formats section.)

    ”O” Retrieves the output data. (The case must be solved; all ID fields must be valid. See the Record Formats section.)

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_rec_comments(pf_comments *r, char *action)

Retrieves or modifies the case name, project title, and case comments.

Parameters
  • r[in] A pointer to a structure of type pf_comments.

  • action[in]

    A string designating the action to be performed. See below for the codes and their meanings. Either upper or lower case is acceptable.

    ”G” Retrieves the case comments.

    “M” Modifies the case comments. All data is updated with the contents of the record.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_rec_itie(pf_rec *r, char *action)

Retrieves, adds, modifies, and deletes intertie data.

Parameters
  • r[inout] A pointer to a structure of type pf_rec, supplied by the calling routine.

  • action[in]

    A string designating the action to be performed on an intertie record. See below for the codes and their meanings. Either upper or lower case is acceptable.

    ”F” Retrieves the first intertie record.

    ”N” Retrieves the next intertie record. (Name1 and Name2 must be valid.)

    ”G” Retrieves the rest of the intertie record. (Name1 and Name2 must be valid.)

    ”D” Deletes an intertie record. (Name1 and Name2 must be valid.)

    ”A” Adds an intertie record. (All data fields must be valid. See the Record Formats section.)

    ”M” Modifies an intertie record. (All data fields must be valid. See the Record Formats section.)

    ”O” Retrieves the solution output. (The case must be solved and name1 and name2 must be valid.)

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_rec_qcurve(pf_rec *r, char *action)

Retrieves, modifies, adds, or deletes reactive power capability curve data.

Parameters
  • r[inout] A pointer to a calling routine-supplied structure of type pf_rec.

  • action[in]

    A string designating the action to be performed on qcurve record. See below for the codes and their meanings. Either upper or lower case is acceptable.

    ”G” Retrieves the rest of the Q curve records associated with a given bus. (Name and kV must be valid. See the Record Formats section.)

    ”D” Deletes a Q curve record. (Name and kV must be valid. See the Record Formats section.)

    ”M” Modifies a Q curve record. (Valid only for activation or inactivation. See the Record Formats section.)

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_rec_xdata(pf_rec *r, char *action)

Retrieves, modifies, and adds switched reactance (X) data.

The delete function is handled by changing the BX bus to another bus type or deleting the BX bus.

Parameters
  • r[inout] A pointer to a structure of type pf_rec, supplied by the calling routine.

  • action[in]

    A string designating the action to be performed on a switched reactance record. See below for the codes and their meanings. Either upper or lower case is acceptable.

    ”F” Retrieves the first xdata record in a case.

    ”N” Retrieves the next xdata record in a case. (Name and kV must be valid. See the Record Formats section.)

    ”G” Retrieves the xdata record associated with bus_name and bus_kV.

    ”A” Adds an xdata record. (All required data must be valid. See the Record Formats section.)

    ”M” Modifies an xdata record. (All required data must be valid. See the Record Formats section.)

    “O” Retrieves the output data. (The case must be solved; all id fields must be valid. See the Record Formats section.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_rec_a2b(char *net_data, pf_rec *r, char *action)

Converts an ASCII record in WSCC format to a pf_rec.

Parameters
  • net_data[in] A pointer to a source string of network or output data.

  • r[in] A pointer to a structure of type pf_rec.

  • action[in] A pointer to a string designating the action to be performed. “I” Converts network data string to binary input data. “O” Converts output data string to binary solution data.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_rec_b2a(char *net_data, pf_rec *r, char *action)

Converts a pf_rec to an ASCII record in WSCC format.

All data fields in pf_rec must be valid.

Author

William D. Rogers

Date

1-23-1995

Parameters
  • net_data[out] A pointer to a destination string for network data.

  • r[in] A pointer to a structure of type pf_rec.

  • action[in]

    A pointer to a string designating the action to be performed on a bus record. See below

    ”I” Writes network data record.

    ”D” Writes change record to delete.

    ”A” Writes change record to add.

    ”M” Writes change record to modify.

    ”O” Writes solution record. (The case must be solved.)

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_save_changes(char *filename)

Save a CHANGES file.

Saves to a change file the input data changes you have made to the currently resident base case data.

Parameters

filename[in] A string representing a file name.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_save_netdata(char *filename, char *dialect, char *ratings, int size)

Save network data.

Save network data from a powerflow base case in ASCII format.

Parameters
  • filename[in] A string representing a file name.

  • dialect[in] A string having the following possible values: “BPA”, “WSCC”, “WSCC1”, or “PTI”. These refer to different forms that the output file can take. See ?? for the differences in dialects.

  • ratings[in] A string having the following possible values: “EXTENDED”, “NOMINAL”, or “MIN_EXTENDED”. See ?? for a description of these options for ratings.

  • size[in] An integer representing the size of output records - either 80 or 120. The choice of 120 is valid only with the BPA dialect.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_save_newbase(char *filename)

Save new base case.

Saves the currently resident base case in its current state to the specified filename.

Parameters

filename[in] A string representing a file name

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_save_wscc_stab_data(char *filename, char *type)

Save WSCC Stability Data.

Saves the power flow data required for input to the WSCC Stability program in either ASCII or binary form depending on the type argument value.

Parameters
  • filename[in] A string representing a file name.

  • type[in] A string representing the type of file format of the saved file. The type values are either “ASCII” or “BINARY”

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_solution(void)

Solve the current case.

Causes the powerflow process (ipfsrv) to initiate a solution on the currently resident base case data.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_init(void)

Start up and initialize the powerflow engine.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_get_list(char *list, int listlen, enum pf_list_type type, char *data)

Retrieve list of owners, areas, bus kV’s, record types, or zones.

The list argument should be a two dimensional character array with the first dimension being the number of areas, and the second dimension being 11 to store area names of up to 10 characters in length. For example, for AREA_LIST, the array might be declared as

char area_names[20][11] 
if you know that there are not more than 20 area names in the case. pf_case_info gives information on the number of areas, zones, owners, etc. The listlen argument prevents the routine from exceeding the bounds of your array.

Parameters
  • list[out] A pointer to a two dimensional character array of size [area size][11].

  • listlen[in] An integer specifying the maximum number of list elements.

  • type[in] The type of list.

  • data[in] Any additional data needed for Program Control Language query. Use “” if none.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_area_of_zone(char *area, char *zone)

Finds the name of the area that a zone is in.

Parameters
  • area[out] A pointer to an array of 11 characters in which the area name is returned.

  • zone[in] A string holding a zone name.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_case_info(pf_case_stats *r)

Retrieve case info.

Retrieves data from a Powerflow base case and puts it in the info structure.

Parameters

r[out] A pointer to a structure of type pf_case_stats.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

void pf_init_rec(void *r, int rtype)

Initialize pf_rec data.

Initializes a data buffer of type pf_rec to blanks and zeros, in order to clear out old data before calling one of the pf_rec routines to store new data in it. Its use is not necessary, but is recommended.

Parameters
  • r – A pointer to a structure of type pf_rec, supplied by the calling routine.

  • rtype – An enumerated variable defined in ft.h

void pf_init_qcurve(pf_rec *r, char *type, char *name, float kv)

Initialize all P-Q curve data fields.

Initializes all P-Q curve data fields to 0 except ID fields that are initialized to the values passed as parameters. This function is used to store ID fields for a specific bus before calling pf_rec_qcurve() to retrieve the generator capability curve values for that bus.

Parameters
  • r[out] A pointer to a structure of type pf_rec supplied by the calling routine.

  • type[in] A string that specifies the record type (must be “QP”).

  • name[in] A string that contains the bus name.

  • kv[in] A floating point value representing the base kV.

void pf_init_itie(pf_rec *r, char *type, char *area1, char *area2)

Initialize all intertie data fields.

Initializes all intertie data fields to 0 except ID fields that are initialized to the values passed as parameters. This function is used to store ID fields for a specific tie line before calling pf_rec_itie() to retrieve the values for that line.

Parameters
  • r – A pointer to a structure of type pf_rec, supplied by the calling routine.

  • type – A string that specifies the record type (must be “I”).

  • area1 – A string which contains the area 1 name.

  • area2 – A string which contains the area 2 name.

void pf_init_cbus(pf_rec *r, char *type, char *owner, char *name, float kv, char *year)

Initialize all continuation bus fields.

Initializes all continuation bus data fields to 0 except ID fields which are initialized to the values passed as parameters. This function is used to store ID fields for a specific bus before calling pf_rec_cbus() to retrieve the continuation record values for that bus.

Parameters
  • r[out] A pointer to a structure of type pf_rec, supplied by the calling routine.

  • type[in] A string that specifies the record type (must be “+”).

  • owner[in] A string that contains the owner name.

  • name[in] A string that contains the bus name.

  • kv[in] A floating point value representing the base kV.

  • year[in] A two character string that contains the code year.

void pf_init_bus(pf_rec *r, char *type, char *name, float kv)

Initialize all bus data fields.

Initializes all bus data fields to 0 except ID fields which are initialized to the values passed as parameters. This function is used to store ID fields for a specific bus before calling pf_rec_bus to retrieve the values for that bus.

Parameters
  • r[out] A pointer to a structure of type pf_rec, supplied by the calling routine.

  • type[in] A string that specifies the record type (either B or any bus type is legal).

  • name[in] A string that contains the bus name.

  • kv[in] A floating point value representing the base kV.

void pf_init_branch(pf_rec *r, char *type, char *name1, float kv1, char *name2, float kv2, char cid, int sid)

Initialize all branch data fields.

Initializes all branch data fields to 0 except ID fields which are initialized to the values passed as parameters. This function is used to store ID fields for a specific branch before calling pf_rec_branch to retrieve the values for that branch.

Parameters
  • r[out] A pointer to a structure of type pf_rec, supplied by the calling routine.

  • type[in] A string which specifies the record type (L, T, E, or specific R-type).

  • name1[in] A string that contains the bus 1 name.

  • kv1[in] A floating point value representing the base kV for bus 1.

  • name2[in] A string that contains the bus 2 name.

  • kv2[in] A floating point value representing the base kV for bus 2.

  • cid[in] A string that contains the circuit ID. For solution data, ‘*’ will retrieve the sum of all parallel circuits.

  • sid[in] A integer value representing the section ID. For solution data, a value of 0 will retrieve the total equivalent line.

void pf_init_area(pf_rec *r, char *type, char *name)

Initialize all area data fields.

Initializes all area data fields to 0 except ID fields which are initialized to the values passed as parameters. This function is used to store ID fields for a specific area before calling pf_rec_area to retrieve the values for that area.

Parameters
  • r[in] A pointer to a structure of type pf_rec, supplied by the calling routine.

  • type[in] A string that specifies the record type (must be A).

  • name[in] A string that contains the area name.

int pf_bus_exists(char *name, float kv)

Seee if a bus exists.

Author

William D. Rogers

Date

8-17-1994

Parameters
  • name[in] A pointer to a string containing the bus name.

  • kv[in] A real value representing the bus base kV.

Returns

Returns 0 if the bus exists; otherwise, it returns 1.

int pf_user_init_def(void)

Initialize User Analysis definitions.

Initializes the user analysis arrays in powerflow (IPF). It should be called prior to other user analysis functions. It sends the command /INITDEF to ipfsrv.

Author

William D. Rogers

Date

1-6-1995

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_user_load_def(char *definitions)

Load User Analysis definitions into IPF.

Loads the user analysis arrays in powerflow (IPF) with the specified symbol definitions. It sends the command

/LOADDEF 
, followed by a newline (
'\n' 
) separated list of definitions, to powerflow.

Author

William D. Rogers

Date

1-6-1995

Parameters

definitions[in] A pointer to a string containing User Analysis Define statements.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_user_sub_def(char *base)

Substitute User Analysis definitions.

Performs character string substitutions using computed base case quantities upon the tokens defined with the >DEFINE statements within comment records sent to powerflow either through the pf_user_load_def function or a User Analysis file. The return message is available in the global buffer reply_pf. It sends the command

/SUBDEF, SOURCE=<name> 
, where name is either “BASE” or “ALTERNATE_BASE” (“ALT”).

Author

William D. Rogers

Date

1-6-1995

Parameters

base[in] A pointer to a string designating the source base case as “BASE” or “ALTERNATE_BASE” (may be abreviated to “ALT”).

Returns

Returns 0 if it is successfull; otherwise, it returns -1.

int pf_user_report(char *filename, char *output, char action)

Load a User Analysis file for customized analysis listings.

Loads a user analysis file for generating customized analysis listings. The requested report is appended to the output file, which is created if it doesn’t already exist.

Author

William D. Rogers

Date

1-6-1995

Parameters
  • filename[in] A character string representing a user analysis file name.

  • output[in] A character string representing an output report file name.

  • action[in] A string designating the action to be performed.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_user_define(char *symbol, char *id, char *type)

Define User Analysis Symbol.

Builds a symbol definition and loads it into the user-analysis arrays in powerflow (IPF). It sends a command constructed as follows:

/LOADDEF 
> DEFINE_TYPE <symbol_type> 
LET <symbol_name> = <id_of_computed_quantity>
If blanks are part of the quantity id, substitute them with pound signs (#). All data is case insensitive. Symbol names are limited to six characters. Use blanks or commas to separate identity items.

Author

William D. Rogers

Date

1-30-1995

Parameters
  • symbol – A pointer to a string containing a symbol name.

  • id – A pointer to a string containing quantity identity.

  • type – A pointer to a string containing symbol type.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_user_comment(char *symbol, char *suffix, char *format)

Define User Analysis comment record.

Builds a comment record and loads it into the user-analysis arrays in powerflow (IPF). It sends a command constructed as follows:

/LOADDEF 
C <symbol_name><symbol_suffix> = $<symbol_name><symbol_suffix><format>
All data is case insensitive, however, the case is preserved. Symbol names are limited to six characters. The suffix is optional and is used for BUS_INDEX and ZONE_INDEX data types. Use a null string (“”) if the suffix is not applicable. The format obeys the Fortran convention and can be either floating point (i. e. /F8.3) or text (i. e. /A7). The default is /F6.0. The format string must include the slash (/).

Comment cards constructed by pf_user_comment are designed to be processed by either pf_user_quantity to retrieve floating point values or pf_user_string to retrieve textual information.

Author

William D. Rogers

Date

1-30-1995

Parameters
  • symbol[in] A pointer to a string containing a symbol name.

  • suffix[in] A pointer to a string containing an index suffix.

  • format[in] A pointer to a string containing format code.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_user_quantity(char *symbol, char *suffix, float *quantity)

Retrieve a User Analysis quantity.

Searches the reply_pf buffer after a pf_user_sub_def function is called for “<symbol_name><index_suffix> = “, where the suffix is optional, and scans in the floating point value that immediately follows. Comment cards can be built with pf_user_comment or any other applicable method. The case of the symbol and suffix must match. The suffix is optional and is used for BUS_INDEX and ZONE_INDEX data types. Use a null string (“”) for the suffux, if the data type does not use a suffix. The suffix must include the period (i.e. “.VK”).

Author

William D. Rogers

Date

1-30-1995

Parameters
  • symbol[in] A pointer to a string containing a symbol name.

  • suffix[in] A pointer to a string containing an index suffix.

  • quantity[in] A pointer to a float to hold the retrieved quantity.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_user_string(char *symbol, int length, char *info)

Retrieve for User Analysis string.

Searches the reply_pf buffer after a pf_user_sub_def function is called for “<symbol_name> = ” and scans into info the number of immediately following characters specified by length. Comment cards can be built with pf_user_comment or any other applicable method. The case of the symbol name must match. Where applicable include the suffix in the symbol name string.

Author

William D. Rogers

Date

1-31-1995

Parameters
  • symbol[in] A pointer to a string containing a symbol name.

  • length[in] An integer specifying the number of characters to scan.

  • info[in] A pointer to a destination string for the scanned data.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_user_branch(char *symbol, pf_rec *r, char *type)

Define User Analysis Branch Index.

Builds a symbol definition and corresponding comment card based on the data in a pf_rec structure and the supplied symbol and type and loads them into the user-analysis arrays in powerflow (IPF). It sends a command constructed as follows:

/LOADDEF 
> DEFINE_TYPE <symbol_type> 
LET <symbol_name> = <bus1_name> <bus1_kv>[*] <bus2_name> <bus2_kv>[*] 
C <symbol_name> = $<symbol_name>/F15.7
Bus names and voltages are derived from the pf_rec branch structure. Blanks in the bus names are replaced by pound signs (#). An asterisk (*) determines at which terminal the line flow is computed. If the metering point in the branch data is 0 or 1, the first bus is selected, if 2 then the second. Symbol names are limited to six characters and are case insensitive, but retain case for the comment card.

Author

William D. Rogers

Date

1-31-1995

Parameters
  • symbol[in] A pointer to a string containing a symbol name.

  • r[in] A pointer to a structure of type pf_rec.

  • type[in] A pointer to a string indicating the quantity type.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_user_itie(char *symbol, pf_rec *r, char *type)

Define User Analysis intertie symbol.

Builds a symbol definition and corresponding comment card based on the data in a pf_rec structure and the supplied symbol and type and loads them into the user-analysis arrays in powerflow (IPF). It sends a command constructed as follows:

/LOADDEF 
> DEFINE_TYPE <symbol_type> 
LET <symbol_name> = <area1_name> <area2_name> 
C <symbol_name> = $<symbol_name>/F15.7
Area names are derived from the pf_rec intertie structure. Blanks in the area names are replaced by pound signs (#). Symbol names are limited to six characters and are case insensitive, but retain case for the comment card.

Author

William D. Rogers

Date

1-31-1995

Parameters
  • symbol[in] A pointer to a string containing a symbol name.

  • r[in] A pointer to a structure of type pf_rec.

  • type[in]

    A pointer to a string indicating the quantity type.

    ’P’ = INTERTIE_P

    ’Q’ = INTERTIE_Q

    ’S’ = INTERTIE_P_SCHEDULED

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_user_bus(char *symbol, pf_rec *r, char *suffix)

Define User Analysis Bus Index.

Builds a symbol definition and corresponding comment card based on the data in a pf_rec structure and the supplied symbol and suffix and loads them into the user-analysis arrays in powerflow (IPF). It sends a command constructed as follows :

/LOADDEF 
> DEFINE_TYPE  BUS_INDEX 
LET <symbol_name> = <bus_name> <bus_kv> 
C <symbol_name><index_suffix> = $<symbol_name><index_suffix>/F15.7
Bus name and voltage is derived from the pf_rec bus structure. Blanks in the bus names are replaced by pound signs (#). Symbol names are limited to six characters and are case insensitive, but retain case for the comment card. The suffix must contain the period (i. e. “.VK”).

Author

William D. Rogers

Date

1-31-1995

Parameters
  • symbol[in] A pointer to a string containing a symbol name.

  • r[in] A pointer to a structure of type pf_rec.

  • suffix[in] A pointer to a string containing the BUS_INDEX suffix.

Returns

Returns 0 if it is successful; otherwise, it returns -1.

int pf_plot(char *cor_filename, char *ps_filename, char *options)

Create a plot.

Causes powerflow (IPF) to generate a plot. Difference plots may be made by first loading an reference (alternate) base case with pf_load_refbase() and providing a difference plot coordinate file. pf_plot sends a command constructed as follows:

/plot
<cor_filename> 
<ps_filename>
<options>

Author

William D. Rogers

Date

7-6-1995

Parameters
  • cor_filename[in] A string representing the name of a coordinate file.

  • ps_filename[in] A string representing the name of the postscript file to be created.

  • options[in] An optional string (may be NULL), representing a list of comments and options, separated by newline (“\n”). Each option must begin with an “@”” character.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_load_refbase(char *filename)

Load a reference base case.

Passes a base case filename to the ipfsrv process so that it can read and interpret the file as a “reference base” (also referred to as an “alternate

base”). This is done prior to requesting difference plots or comparison (difference) reports. If a reference case is currently loaded, it is overwritten and the data is lost.

Author

William D. Rogers

Date

7-7-1995

Parameters

filename[in] A string representing a file name.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_select_base(char base)

Select primary base base or reference base base records.

Allows the pf_rec functions to access the input and solution data in either the primary base case (OLDBASE) loaded with pf_load_oldbase or the reference (alternate) base case loaded with pf_load_refbase. The accessed base case initially defaults to the OLDBASE data.

Author

William D. Rogers

Date

7-21-1995

Parameters

base[in] A character indicating which set of data other commands act upon: ‘O’ OLDBASE data or ‘R’ REFBASE data.

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_solve_area(char base)

Get the area interchange for an area.

Run the solution to obtain the area interchange amount. Can run for either the old base case or the reference base case.

Author

William D. Rogers

Date

3-6-1996

Parameters

base[in]

A character indicating the base case for which to calculate area interchange.

’O’ = Old base case ‘R’ = Reference base case

Returns

Returns 0 if it is successful; otherwise, it returns 1.

int pf_command(char *command)

Run PCL commands.

Passes an ASCII control file name to ipfsrv so that it can read and interpret the file.

Author

William D. Rogers

Date

5-6-1996

Parameters

command[in] A string representing PCL commands [and data].

Returns

Returns 0 if it is successful; otherwise, it returns -1.

Variables

char pf_cflow_inbuf[]
char pf_cflow_outbuf[]
char err_buf[]
char reply_pf[]
int pf_cflow_socket
int cf_debug
group input_data

The following structures are used for input to powerflow. This is the set of CFLOW structures used by the “pf_rec_…” functions

group pf_rec

Read, write, and modify powerflow records.

The pf_rec_ functions allow powerflow input (network data) and output (solution) data to be retrieved, as well as allowing input data (network data) to be added, modified, or deleted.

group pf_user

The pf_user_ functions provide a means of using the User Analysis features of the powerflow.

dir /home/docs/checkouts/readthedocs.org/user_builds/bpa-ipf/checkouts/doc-updates/include
example pf_area_of_zone.c

int cnt;
char zones[32][3]; /* array for zone list */

pf_get_list((char *)zones, 10, ZONE_LIST, "");

for (cnt = 0; cnt < 10; ++cnt)
{
    char area_name[11];
    int error;
    error = pf_area_of_zone(area_name, zones[cnt]);
    printf("zone %-5s is in area %-10s\n", zones[cnt], area_name);
}

example pf_bus_exists.c


 int found;
 
 found = pf_bus_exists(new_name, kv);
 
 if (found == 0)
    printf(" - This node already exists! %s\n", b.i.ACbus.name);

example pf_case_info.c

int error;

pf_case_stats ci;

error = pf_case_info (&ci);

if (!error) 
{
    fprintf (out, "Number of areas = %d\n", ci.num_areas, 
                  "Number of zones = %d\n", ci.num_zones, 
                  "Number of buses = %d\n", ci.num_buses,
                  "Number of connections = %d\n", ci.num_circuits, /* Not including parallels*/
                  "Number of lines = %d\n", ci.num_branches);

    if (ci.case_soln_status == SOLVED)
        fprintf(out, "This was a solved case.\n\n");
}

example pf_get_list.c

int cnt;
char owners[64][4]];

pf_get_list((char *)owners, 64, OWNER_LIST);

printf("owners=\n");

for (cnt=0; cnt < 64; ++cnt) 
{
    printf("%-5s",owners[cnt]);
}

example pf_init_functions.c

pf_rec r;

printf("Initialize area record == \n"); 
pf_init_area(&r, "A", "NORTHWEST");
printf("Type = %s  Area Name = %s  Scheduled export = %7.1f\n\n", r.i.area.type, r.i.area.name, r.i.area.sched_export);


printf("Initialize branch record == \n");

pf_init_branch(&r, "L", "WESTMESA", 345.0, "FOURCORN", 345.0, "1", 0);

printf("Bus1 Name = %s%5.1f Bus2 Name = %s%5.1f R = %7.1f X = %7.1f\n\n", 
   r.i.branch.bus1_name, r.i.branch.bus1_kv, r.i.branch.bus2_name, r.i.branch.bus2_kv, r.i.branch.r, r.i.branch.x);


int error;
pf_rec *b; 

/* This function is normally used to find data for a specific bus. 
pf_init_bus stores the ID fields in the structure. */
pf_init_bus (&b, "B", "SJUAN G1", 22.0); 

/* Then pf_rec_bus retrieves the data. */
error = pf_rec_bus (&b, “G”);

/* Gets rest of bus data (input). */
if (!error)
    error = pf_rec_bus (&b, "O"); /* Gets output bus data. */

fprintf (out, "Initialize cbus record == \n");
pf_init_cbus (&r,"+","PNM", "SAN JUAN", 345.0, " ");
fprintf (out, "Bus Name = %s%5.1f Owner = %s  Load = %7.1f\n\n", r.i.cbus.name, r.i.cbus.kv, r.i.cbus.owner, r.i.cbus.Pload);

fprintf (out, "Initialize itie record == \n");
pf_init_itie (&r, "I", "NORTHWEST", "BC=HYDRO");
fprintf (out, "Area 1 = %s  Area 2 = %s  Scheduled flow = %7.1f\n\n", 
  r.i.itie.area1_name, r.i.itie.area2_name, r.i.itie.sched_export);

fprintf (out, "Initialize Q=curve record == \n");
pf_init_bus (&r, "QP", "SJUAN G1", 22.0);
fprintf (out, "Bus Name = %s%5.1f Status code = %s\n\n",
           r.i.qcurve.bus_name, r.i.qcurve.bus_kv, r.i.qcurve.active);

pf_init_rec(r, AREA);
pf_init_rec(r, L_LINE);
pf_init_rec(r, AC_BUS);
pf_init_rec(r, CBUS);
pf_init_rec(r, ITIE);
pf_init_rec(r, QCURVE);

example pf_load_functions.c

int error;
pf_rec br;

error = pf_load_oldbase ("43bus.bse");
printf("Loaded old base 43bus.bse, status = %d\n\n", error);

if (!error) {
    error = pf_load_changes("43bus.chg");
    printf("Loaded change file 43bus.chg, status = %d\n\n", error);
}

error = pf_load_oldbase ("j98cy94.bse, rebuild = ON");

pf_load_refbase("J98CY94.BSE"); 
pf_select_base('R'); 
pf_rec_branch(&br, "F")

example pf_main.c

#include "cflowlib.h"

int main(int argc, char *argv[])
{
    pf_cflow_init(argc, argv);
    printf("pf_load_netdata=%d\n", pf_load_netdata("bench.net"));
    printf("pf_solution=%d\n", pf_solution());
    pf_cflow_exit();
}

example pf_plot.c

pf_load_oldbase("A98CY94.BSE");
pf_load_refbase("J98CY94.BSE");
pf_plot("500BUS_DIF.COR", "A98CY94.PS", "");

system("print/queue=EOHQMS_PS A98CY94.PS");

example pf_put_inrec.c

The following program uses pf_put_inrec to change an input data record in Powerflow and then outputs a success or failure message to the screen.

int error;
char record [130];

/* record needs to contain valid change, add, or delete input data */
error = pf_put_inrec ( record );
if (!error)
    printf ("Successfully changed, added, or deleted input record.\n");
else
    printf ("Invalid record.\n"); }

example pf_rec.c

pf_rec c, a, bus, branch; 
int error, status;
char net_data[80]; 
FILE *out;

printf("Enter branch identifying data: "); 
gets(net_data); 
pf_rec_a2b(net_data, &b, "I");

pf_rec_bus(&bus, "F");
pf_rec_b2a(net_data, &bus, "I");
printf("%s\n", net_data);

pf_cflow_init( argc, argv );
out = fopen ("ipf_report.txt", "w");

/* Obtain case comments */ 
error = pf_rec_comments (&c, "G");
fprintf (out, "Current case is: %s Description: %s\n\n", c.case_name, c.case_descrip);

fprintf (out, "%s\n", c.h[0]); 
fprintf (out, "%s\n", c.h[1]);
fprintf (out, "%s\n\n", c.h[2]);
fprintf (out, "%s\n", c.c[0]);
fprintf (out, "%s\n", c.c[1]);
fprintf (out, "%s\n\n", c.c[2]);

pf_rec_branch(&branch, "O");

/* Area data */
fprintf (out, "\n******** AREA DATA ********\n\n");
cf_debug = 1;
error = pf_rec_area( &a, “F” ); /* get first area */
cf_debug = 0;

status = pf_rec_area( &a, “O” ); /* get first area output*/

while ( !error && !status )
{
    fprintf (out, "Type Area Name  Slack Bus    NZn  Export    Pgen Pload   Ploss Pexport  Vmax  Vmin\n");
    fprintf (out, " %s  %s %s%5.1f %d %7.2f %7.1f %7.1f %7.1f %7.1f %6.4f %6.4f\n", 
      a.i.area.type, a.i.area.name, a.i.area.sbus_name, a.i.area.sbus_kv, a.i.area.num_zones, a.i.area.sched_export, a.s.area.Pgen, a.s.area.Pload, a.s.area.Ploss, a.s.area.Pexport, a.i.area.max_Vpu,a.i.area.min_Vpu);
    
    fprintf (out, "Zones in Area:  %s  %s  %s  \n\n", a.i.area.zones[0], a.i.area.zones[1], a.i.area.zones[2]);
    
    error = pf_rec_area( &a, “N” ); /* get next area */
    status = pf_rec_area( &a, “O” ); /* get next area output*/
}

pf_init_itie("I ", areaname1, areaname2);
status = pf_rec_itie (&itie, "G");

for (error = pf_rec_branch(&branch,"f1"); error == 0; error = pf_rec_branch(&branch,"n1"))
{
    printf("      %s, kv= %6.1f,name2= %s, kv2= %6.1f\n", 
         branch.i.branch.bus1_name, branch.i.branch.bus1_kv, branch.i.branch.bus2_name, branch.i.branch.bus2_kv);
}

for (error = pf_rec_bus(&bus, "f"); error == 0; error = pf_rec_bus(&bus, "n"))
{
    pf_rec_bus(&r,"o");
    printf("name= %s, kv= %6.1f, vmag=%6.1f, vdeg=%6.1f\n", 
        bus.i.ACbus.name, bus.i.ACbus.kv, bus.s.ACbus.Vmag, bus.s.ACbus.Vdeg);
}

/* CBUS DATA */
fprintf (out,”\n******** CBUS DATA ********\n\n”);      error = pf_rec_bus( &r, “F” );           /* get first bus in case */     status = pf_rec_cbus( &r, “F1” );  /* is there a cbus record?  */
while (!error) {
    do {
        error = pf_rec_bus( &r, “N” ); /* get next bus in case */
        status = pf_rec_cbus( &r, “F1” ); /* is there a cbus record? */
    } while (status);

    while ( !status )  /* loop on bus with cbus record(s) */ {
        status = pf_rec_cbus( &r, “O” );
        fprintf (out, "Type Own  Bus Name         Pload  Qload  Gshunt Bshunt    Pgen  Qgn-mx    Qmin  \n");
        fprintf (out, " %s %s  %s%5.1f %7.1f %7.1f %7.1f %7.1f %7.1f %7.1f %7.1f\n\n", 
          r.i.cbus.type, r.i.cbus.owner,r.i.cbus.name,r.i.cbus.kv, r.s.cbus.Pload,r.s.cbus.Qload,r.s.cbus.Gshunt,r.s.cbus.Bshunt, r.i.cbus.Pgen ,r.i.cbus.Qgen_Qmax,r.i.cbus.Qmin);
        status = pf_rec_cbus( &r, “N1” );
    }
}


close(out);

example pf_rename.c

int error;
error = pf_rename_area ("NORTHWEST", "NW AREA");
error = pf_rename_bus ("BELL", 69, "BELL1", 60.6);
error = pf_rename_zone ("7", "N7");

example pf_save.c

error = pf_save_changes ("mychanges.chg");
error = pf_save_netdata ("mychanges.net","WSCC", "NOMINAL", 80);
error = pf_save_newbase ("mychanges.bse");
error = pf_save_wscc_stab_data ("mychanges.asif", "ASCII");

Network Diagrams

Overview

IPF has two different network diagram presentations. One is the display you see in the GUI graphics, and the other is the hard copy map. The display is for convenience in accessing system data graphically - it does not represent what the plotted map will look like, nor does it need to be ‘pretty’. The hard copy diagram is designed for reports, documentation, and analysis. It can be generated as a report from the graphic display or produced in a batch environment. This section addresses the hard copy diagram which is designed for reports, documentation, and analysis.

Both presentations use the same coordinate file format. The most important coordinate data, like bus icon and name locations, and line bending points, can be edited graphically from the GUI by moving things around and saving the altered coordinate file. However, you will have to plot out the map in order to see how your changes have affected the hard copy appearance.

The basic diagram shows power system components modeled in a power flow study. The diagram is less detailed than a Powerflow listing, but may have more (or different) information than the graphic display. It shows essential bus and branch solution data. The diagram also shows identification data. For example, it shows date, case identification, program version, and the options used to generate the diagram. The diagram can be enhanced by adding to the coordinate file such items as:

  • A legend.

  • A border.

  • A control block for case identification, signatures, etc.

  • A case title heading.

  • Selected tie line flows and loss summary.

  • An inset showing detail in a selected area.

  • Any PostScript language objects.

These items will show up on the map plotted from the GUI, even though many of them cannot be added or edited from the GUI. For details on all the hard copy diagram options and capabilities, and the usage of the ipfplot and ipfbat programs, see ipfplot and ipfnet.

Input Requirements, Output, and Operation

The Plot function is a set of FORTRAN subroutines within ipfmain, which build a dynamic PostScript objects file of references to a static PostScript objects file (pfmaster.post). The same routines are called by the Print Plot command issued from the GUI, a command file entered via ipfbat or the GUI, and by the batch program ipfplot. The dynamic file, which is built by “anding” a coordinate file with powerflow data, defines which data will appear on a diagram. The static ASCII PostScript file describes how data will appear on a diagram.

When you load a coordinate file, for example name.cor, into the GUI, the program copies the contents of the file into name.tmp. Any changes you make during your interactive session are reflected in the latter file. They will disappear when you exit IPF unless you Save the coordinate file before exiting.

When you select the Print Plot item on the File menu, IPF uses the intersection of the name.tmp file and the currently loaded system data to define which data will appear on the diagram. It then combines this with the file pfmaster.post, which describes how data will appear on the diagram. The result is a name.ps file, which is sent to a PostScript-capable printer using the Printer Destination string you have selected.

Input Requirements

The input requirements are:

  • A coordinate file, built via the GUI and/or an ASCII text editor.

  • A solved system network, either from a base case file or currently loaded in IPF.

  • The static PostScript file (pfmaster.post) defining how data will be shown on the

diagram.

Output

A dynamic PostScript file, which is built by the Plot program, is appended to the static PostScript file and sent to a PostScript interpreter (printer or computer display) to produce a diagram.

Plot Program Operation

GUI: Select Print Plot from the File pull-down menu. You can also change the options for the particular plot, by selecting Diagram Options and/or Page Options. These override the options which may be specified in the coordinate file.

ipfbat: See ipfnet.

ipfplot: Enter ipfplot coordinate_file base_file_1 [base_file_2]. This is a strictly batch process which does not require the GUI. A coordinate file name and one solved base file must be provided. The second base file is required only for difference maps.

However it is invoked, the Plot program determines which information should appear on the diagram by examining the coordinate file. It then searches the Powerflow data for bus, branch, area, and intertie data that are identified in the coordinate file. When a match is found, the Powerflow and coordinate data are combined and formatted into a dynamic PostScript file to activate procedures on the static PostScript file. In addition to bus, branch, transformer, area, and intertie records, all other coordinate file records — options, draw, >define, comment, and PostScript — are processed by the Plot program and formatted to invoke procedures on the static PostScript file.

Coordinate File

The coordinate file used by the diagram program is the same file that is generated and used by the GUI display. Since the coordinate file is an ASCII file, it can be generated by any ASCII text editor. The records in that file are described in this section.

The Coordinate file consists of primary coordinate data records and supportive coordinate data records. All coordinates are first quadrant positive Cartesian coordinate values in centimeters. The lower left corner of the diagram is coordinate (0,0). The primary coordinate data records those which specify the bus and branch (bend) locations. These records are:

  • Bus Record B

  • Line Record L

  • Transformer Record T

  • Area Record A

  • Intertie Record I

The Coordinate file may also include supportive record types to produce a diagram suitable for long term documentation. These records are:

  • File Identification Record [ID COORD

  • Options Record O

  • Define Record >DEFINE_TYPE

  • Comment Record C

  • Draw Record D

  • PostScript Record P

  • Trailer Record 9 or (*EOR)

For complete details on all of the coordinate file records, see ??.

File Indentification Record - [ID COORD

The file identification record signifies the beginning of a set of coordinate records. See the table below. Options are set to their default condition when this record is encountered. One such record is required at the beginning of the coordinate file, but it may optionally contain several [ID COORD records and their associated coordinate record sets. Multiple [ID COORD records may be used to insert a control block, legend, or an inset of a detailed section of the diagram.

File Identification Record Format

Column

Format

Description

1-9

A9

[ID COORD

9-90

Not used by Plot program, available for user notes.

Options Record - O

Options affect the general appearance of a diagram and determine which Powerflow data will be displayed for each bus and branch on a diagram.

The default option values can be overridden by options specified in the coordinate file. If a coordinate file is currently loaded in the GUI, and the options are changed via the Page Options or Diagram Options menus, these will override (replace) those originally specified in the file. If the file is saved, the new options will be saved in it.

The = and , and blank field delimiters may be used interchangeably. Option names may be upper or lower case. Upper case characters shown in the tables indicate the minimum mandatory characters for identifying the option.

Option Record Format

Column

Format

Description

1-2

A 2

OP - identifies an option record.

3-90

A 88

Free field description of option, see tables below for details.

Here is an example of how to specify options in the coordinate file::

OPtions OR=L
Options SCale_factor=0.9,0.9
OP BUs_detail=Bus_name,Powerflow_name

Page Options These are general appearance options. Several of them are interdependent. They are applied in the following order:

  • Orientation

  • Scale

  • Offset

  • Border with transparency flag

  • Box for identification

  • Case location

  • Comment location

  • Coordinate file name location

  • Size

  • Legend location

The option values can be set on the Diagram Options menu.

General Appearance (Page) Options

Option

Description

SIze=XX.XX,YY.YY

DEFAULT = 21.59 by 27.94 cm (8.5 by 11 inches).

ORientation=Landscape ORientation=Portrait

DEFAULT=Portrait.

OFfset=XX.XX,YY.YY

Lower left of diagram relative to lower left of page. DEFAULT = 0.0, 0.0.

TRansparency=Transparent TRansparency=Opaque

DEFAULT for insets is Opaque. Main diagram is always opaque.

SCale_factor=X.XX,Y.YY

DEFAULT = 1.0, 1.0.

BOrder=XX.XX,YY.YY

Locates upper right corner of border. DEFAULT = no border.

BX=XX.UL,YY.UL,XX.LR,YY .LR

Locates an identification box. XX.UL and YY.UL locate the upper left corner of the box. If XX.LR and YY.LR are zero (0), the box is positioned in the lower right corner of the diagram. Default coordinates are established for CR (coordinate file), CAse_name, and COmments. These locations can be overridden. A standard border is drawn as near the edge of the paper as most PostScript printers will allow. DEFAULT = no identification box.

CAse_name=XX.XX,YY.YY

Locates case name from Powerflow program. DEFAULT = no case name.

COmments=XX.XX,YY.YY

Locates comments from user entry and Powerflow program. DEFAULT = no Powerflow comments.

CR=XX.XX,YY.YY

Locates coordinate file name DEFAULT = relative to BX.

LG=XX.XX,YY.YY

Locates upper left corner of legend box. DEFAULT = no legend.

_images/Page_Options_Dialog_Box.png

Page Options Dialog Box

Diagram Options

The options described in the table below determine which powerflow values will be displayed on a diagram.

Those selections that are ON by DEFAULT may be turned off in one of two ways. Some, such as the bus name selection, may be toggled to the abbreviations on the bus coordinate records, full bus name, or full bus name and base kv. Others, such as generation, may be turned off by preceding the value of interest with NO_. For example, to not show generation::

Option BUs_detail=NO_Generation
or
O BU=NO_G

You can also specify on the bus coordinate record whether or not the generation and shunt reactance at this bus should be displayed. See bus coordinate records in Table ?? and Figure ?? for details. The no display indicator on the coordinate records can be overridden with a draw more or alwaws draw option for generators or shunt reactors. For example,:

Op BUs_detail=AL_Generators
Op BUs_detail=MO_Generators
Option BUs_detail=AL_Shunt
_images/GUI_Diagram_Options.png

GUI Diagram Options

Some of the diagram options are independent; others are mutually exclusive. Look at the GUI menu above to quickly determine which is which. Those with diamond buttons are exclusive; those with square buttons can be turned on or off in any combination. This applies no matter whether the options are specified from the menu or in the coordinate file.

Powerflow Values Options

Option

Description

DIagram_type=Pq_flow DIagram_type=Mva/I DIagram_type=Loss DIagram_type=Interchange DIagram_type=Coordinates Diagram_type=Loading %

See flow detail; DEFAULT Maximum values P and/or Q set via P_S, Q_S

No flow data % current or % MVA rating

VAlues=Normal VAlues=Difference

DEFAULT case1 - case2

FLow_detail=P_Sending_end FLow_detail=Q_Sending_end FLow_detail=P_Receiving FLow_detail=Q_Receiving

DEFAULT DEFAULT

BUs_detail=Bus_name,Abbreviation BUs_detail=Bus_name,Powerflow_name (and kV) BUs_detail=Voltage,kV BUs_detail=Voltage,Per Unit BUs_detail=Angle BUs_detail=Generation BUs_detail=Shunt BUs_detail=Load BUs_detail=Total_flow of undrawn branches BUs_detail=Outages

DEFAULT

DEFAULT

DEFAULT DEFAULT DEFAULT

Not yet implemented.

BRanch_detail=Trans_taps BRanch_detail=Compensation BRanch_detail=Parallels,Combined BRanch_detail=Parallels,Separate BRanch_detail=Outages

DEFAULT

Not yet implemented.

File Management This option is used to ‘include’ a separate file of coordinate data into the current file that you are plotting. CFLOW reports can be incorporated into the diagram by this mechanism. Multiple files may be included, if desired. This option is not presently available from the GUI. That is, if in the GUI you load a coordinate file which includes “Option File” records, these will be ignored. However, there is a means of including a single auxiliary coordinate file in a GUI plot. Under the File pull down menu, select Plot Options, then User Comments. Include a comment which is the name of the file, preceded by an ampersand (&). See section :ref:`` for more information.

The ABERDEEN INSET in Figure 5.8 was created with an & record.

The included file should not be a complete, independent coordinate file. For example, if it has a [ID COORD record, none of the file will be included. If it contains any options which have already been defined, these will produce warning messages and will have no effect. Options which are not defined in the main file can be defined in the included file; they will be applied to the entire diagram.

The included file must be terminated with a (*EOR) record, or its last line will be lost.

File Management Option

Option

Description

File=filename

Coordinate data from the specified file will be inserted into the current file. (This feature has not yet been implemented in the GUI.)

PostScript Records

PostScript, >Define, Comment, and Draw records are processed in the order specified by the user. For example, a PostScript record can be used to change the font for comment records. A comment record may or may not define coordinates. If coordinates are not defined, the comment is printed below the previous comment record. A series of Draw records or a series of PostScript records is often required to accomplish a specific task.

PostScript commands, columns 3 - 82 of the PostScript records, are sent directly to the PostScript file. They have the complete versatility of the PostScript language (PSL). A typical use is to change fonts within a series of comment records or to add simple graphics to a diagram. These records could also be generated, inserted, or edited by a CFLOW program (see also Comment Records, below).

PostScript Record Format

Column

Format

Description

1

A 1

P - identifies a PostScript record.

3-82

A 80

Any valid PostScript command including commands defined in pfmaster.post

>Define Records

The define records associate solution values to variables that can be manipulated and printed within comment records. Section user-analysis provides an in-depth discussion of this feature. See the table below for the format of >DEFINE records.

Define Record Format

Column

Format

Description

1-7

A 7

>DEFINE — identifies a define record.

1-90

A 90

See user-analysis, /USER- ANALYSIS section, Symbol Definitions.

Comment Records

Comment records may display simple text or may be used in conjunction with >DEFINE records to display Powerflow values.

They may also be used in conjunction with CFLOW, to create mini-reports on the printed map. Your CFLOW program can edit a coordinate file directly, or create/edit an auxiliary file containing comment records, which is included in the main file(s) with an OPtion = FIle record (see also PostScript records, above).

Comment Record Format

Column

Format

Description

1

A 1

C - identifies a comment record.

3-14

2F 6.2

X, Y coordinates of comment. DEFAULT - after previous comment.

15-90

A 76

Comments.

Draw Records

Draw records are used to draw straight lines such as borders and boxes on a diagram.

Draw Record Format

Column

Format

Description

1

A 1

D - identifies a draw record.

3-14

2F 6.2

X, Y coordinates.

15

I 1

1 = draw or 2 = move to specified coordinates.

16-27

2F 6.2

X, Y coordinates.

28

I 1

1 = draw or 2 = move to specified coordinates.

29-40

2F 6.2

X, Y coordinates.

41

I 1

1 = draw or 2 = move to specified coordinates.

42-53

2F 6.2

X, Y coordinates.

54

I 1

1 = draw or 2 = move to specified coordinates.

55-66

2F 6.2

X, Y coordinates.

67

I 1

1 = draw or 2 = move to specified coordinates.

68-79

2F 6.2

X, Y coordinates.

80

I 1

1 = draw or 2 = move to specified coordinates.

Bus Coordinate Data

The bus coordinate data describes where and how the Powerflow bus values will be displayed on the diagram. See the table and card below for the format of the bus coordinate data record.

Bus Coordinate Data Format

Column

Format

Description

1

A 1

B — Identifies the Bus coordinate record. This record type is created when you place a bus graphically.

2

I 1

Display flag: 0,Blank - Display the bus symbol. 1 - Do not display the bus symbol, but print the name. This is accessed by the Hide Bus and Show Bus buttons in the Bus Coord Edit menu.

3-10

A 8

Bus name to match Powerflow data. Used for identification.

11-14

F 4.0

Bus kv to match Powerflow data. Used for identification.

15-22

A 8

Name abbreviation to print on diagram. This can be edited from the Bus Coord Edit menu.

23

I 1

Print bus voltage relative to bus name: 1 - over name 2 - right of name 3 - below name - this is the GUI-generated default 4 - left of name 5 - do not print the voltage 6 - print the voltage, but no name

24-35

2F 6.2

X, Y of center of bus symbol. This changes whenever you move a bus in the GUI display.

36-47

2F 6.2

X, Y of the lower left corner of the bus name (if other than default). This changes whenever you move a bus name.

48-50

F 3.0

Angle (in degrees) of generator symbol (0 degrees assigns X > 0, Y = 0 position Angle > 0 moves counter clockwise). An angle of 0 is a flag to not display the generator. GUI-generated default is 150 degrees.

51-53

F 3.0

Angle of reactance symbol. An angle of 0 is a flag to not display the reactor. GUI-generated default is 120 degrees.

54-55

A 2

Bus symbol shape identifier: Blank - round symbol - this is the default from GUI. HB - horizontal bar, length = radius x 2 VB - Vertical bar User may add other symbols corresponding to symbols added in master PostScript file.

56-59

F 4.2

Bus symbol radius in centimeters.

_images/Bus_Coordinate_Data_Record.png

Bus Coordinate Data Record

Branch Coordinate Data

The branch coordinate data describes the bending points in a branch and identifies which segment will show the flow and transformer symbol or compensation symbol. See the table and card record below for the format of the branch coordinate data record.

Column 27 requires additional explanation. Several alternative routes may be established for printing parallel circuits separately. The most preferred path is 1, next 2, etc. When the option to display parallel circuits separately is on and there are as many or more routings as circuits, the circuits are shown separately.

Branch Coordinate Data Format

Column

Format

Description

1

A 1

L or T identifies a Line or Transformer. This record type is generated when you place a bending point in a line or transformer.

2

Not used.

3-10

A 8

Bus1 name.

11-14

F 4.0

Bus1 kV.

15-22

A 8

Bus2 name.

23-26

F 4.0

Bus2 kV.

27

I 1

Circuit number for routing parallel circuits separately. Not available from GUI.

28

Not used.

29-30

I 2

Segment for annotation with flow. A negative number means do not show arrow and flow. Not available from GUI.

31-42

2F 6.2

X, Y coordinates for 1st bending point.

43-54

2F 6.2

X, Y coordinates for 2nd bending point.

55-66

2F 6.2

X, Y coordinates for 3rd bending point.

67-78

2F 6.2

X, Y coordinates for 4th bending point.

79-90

2F 6.2

X, Y coordinates for 5th bending point

_images/Branch_Coordinate_Data_Record.png

Branch Coordinate Data Record

Area Coordinate Data

The area record is used to define the location of an area interchange bubble. See the table and figure below for the format of the area coordinate data record.

0, blank — Display the area symbol. 1 — Do not display the area symbol, but print the name. 3-12 A 10 Area name — Name of area as shown in IPF. 13 Not used. 14-23 A 10 Abbreviation — A name appearing on the diagram. If blank, no name is printed. 24-35 2F 6.2 X,Y of center of area symbol. 36-37 A 2 Area symbol shape identifier. (The default — blank — is a cartouche. The user may add other symbols corresponding to symbols added in the master PostScript file.) 38-41 F 4.2 Radius — Radius of circular segments of cartouche. 42-45 F 4.2 Width — Width of linear segment of cartouche. 46-90 Not used.

_images/Area_Coordinate_Data_Record.png

Area Coordinate Data Record

Intertie Coordinate Data

The intertie record is used to locate the bending points of an intertie connecting two areas. This record becomes necessary when crowding of interties occurs. See table and figure below for the format of the intertie coordinate data record.

2 Not used. 3-12 A 10 Area 1 — Name of first area. 13 Not used. 14-23 A10 Area 2 — Name of second area. 24-28 Not used. 29-30 I 2 Segment for annotation with flow. A negative number means do not show arrow and flow. 31-42 2F 6.2 X, Y coordinates for 1st bending point. 43-54 2F 6.2 X, Y coordinates for 2nd bending point. 55-66 2F 6.2 X, Y coordinates for 3rd bending point. 67-78 2F 6.2 X, Y coordinates for 4th bending point. 79-90 2F 6.2 X, Y coordinates for 5th bending point.

_images/Intertie_Coordinate_Data_Record.png

Intertie Coordinate Data Record

Annotation Record

The annotation record can be used to document a data file. The record is ignored by the diagram program. You can also temporarily remove a coordinate record from service by inserting a “!”” or “#”” before it.

an annotation record. 2-90 A Any ASCII printing characters.

Trailer Record

The trailer record signifies the end of the usable data. Any records beyond the trailer record are ignored by the program. See table for the format of the trailer record.

PostScript Procedures

This section is for the advanced user who wants to customize the appearance of the diagram by modifying PostScript procedures.

The PostScript procedures are stored in ASCII form on the pfmaster.post file. The procedures that are most likely to be changed by the user are described below.

Coordinate Data Within the Postscript Procedures File

The PostScript procedures file is used as a data repository for selected coordinate data. A % (percent sign) as the first character of a record instructs the PostScript interpreter to process the record as a comment. The FORTRAN program reads columns 2-79 of these comment records as coordinate data records. These records must be within the first 100 records of the pfmaster.post file and contain the following delimiters::

%[xx Beginning of a block 'xx' of coordinate format data
%(end) End of block
%[End End of all coordinate data in pfmaster.post repository

Diagram Identification Data

Diagram identification data is retrieved when the user requests the label box (BX) option. Typically, the identification includes:

  • Powerflow case name.

  • Date of Powerflow run.

  • Version of Powerflow program used to create case.

  • Description of Powerflow case.

  • Time of Powerflow run.

The identification data in the pfmaster.post file is of the form shown below. Refer to the pfmaster.post file for the identification data in your installation.:

%%Begin data read by psplot
%[BX WSCC will change the first 7 characters to: %[BPABX
%>DEFINE_TYPE OLDBASE LET cAse=CASE
%>DEFINE_TYPE OLDBASE LET dAte=DATE
%>DEFINE_TYPE OLDBASE LET pFvr=PFVER
%>DEFINE_TYPE OLDBASE LET dEsc=DESC
%P /Helvetica-Bold findfont 10 scalefont setfont
.
.
.
%Option SSpecific Comments=20
%(end)
%[End BPA data block read by psplot --DO NOT REMOVE THIS RECORD
%[WSCCBX WSCC will change the first 4 characters of this record to: %[BX
%! ****** emulated stuff *************
%>DEFINE_TYPE OLDBASE LET tIme=TIME
%P /Helvetica findfont 07 scalefont setfont
.
.
.
%Option SSpecific Comments=03
%(end)
%[End WSCC data block read by psplot --DO NOT REMOVE THIS RECORD

Legend

The legend is in PostScript form and is used when the legend option (LG) is selected. The legend identifies line patterns with kV ranges. The user may examine the procedure acLine for a description of the operands passed to that operator.

The legend data in the pfmaster.post file is of the form shown below.:

/legndId
{
 gsave
 x-legnd y-legnd translate
 0 -4.50 cmtr translate
 newpath
 0 0 moveto 0 4.50 cmtr lineto 2.2 cmtr 4.50 cmtr lineto 2.2 cmtr 0 cmtr linet
o
 closepath stroke
 /Helvetica-Bold findfont 10 scalefont setfont
 0.4 cmtr 4.00 cmtr moveto
 (LEGEND) show
 /Helvetica-Bold findfont 08 scalefont setfont
 [ 0.10 cmtr 3.25 cmtr 2.10 cmtr 3.25 cmtr ]
 () () () 1 0 ( 0 - <100 kv) () () 0 099 acLine
 [ 0.10 cmtr 2.50 cmtr 2.10 cmtr 2.50 cmtr ]
 () () () 1 0 (100 - <200 kv) () () 0 199 acLine
 [ 0.10 cmtr 1.75 cmtr 2.10 cmtr 1.75 cmtr ]
 () () () 1 0 (200 - <231 kv) () () 0 230 acLine
 [ 0.10 cmtr 1.00 cmtr 2.10 cmtr 1.00 cmtr ]
 () () () 1 0 (231 - <500 kv) () () 0 499 acLine
 [ 0.10 cmtr 0.25 cmtr 2.10 cmtr 0.25 cmtr ]
 () () () 1 0 (500 kv and up) () () 0 500 acLine
 grestore
} def

Line Pattern Data

Line pattern data is stored in the array LinePattern. The length must be defined in LinePatternArray. The put operator stores data in the array element indicated by the indexes 0, 1, 2, 3, etc.

The first two values in the array are the voltage range for the line pattern. Next is an array with a nested array. The nested array is line pattern, and the other value in the offset as required by the operator `setdash. The last value in LinePattern is the line width.

To be within a voltage range, a voltage must be greater than or equal to the minimum voltage specified and less than the maximum voltage specified.

The line patterns for outages and interchange lines are similar but without the voltage range specification.

The line pattern data in the pfmaster.post file is::

%***** LINE PATTERN DATA****************
/LinePatternArray 5 def
/LinePattern LinePatternArray array def
/LinePatternCount LinePatternArray 1 sub def
 LinePattern 0 [200 231 [ [3 6] 0 ] 1.00 ] put
 LinePattern 1 [500 2000 [ [1 1000] 0 ] 1.00 ] put
 LinePattern 2 [100 200 [ [5 1] 0 ] 1.00 ] put
 LinePattern 3 [231 500 [ [1 5] 0 ] 1.00 ] put
 LinePattern 4 [0 99999 [ [1000 1] 0 ] 1.00 ] put

%***** Line Pattern for Outage Line ******************

/LinePatternOut [ [ [1 4] 0 ] 1.00 ] def
/curve-offset 8 def

%***** Line Pattern for Interchange Line ******************

/LinePatternInt [ [ [1 10000] 0 ] 1.00 ] def

Bus Overvoltage/Undervoltage Range Values

Acceptable bus voltage range data is stored in the array VoltLim. The length must be defined in VoltLimArray. The put operator stores data in the array element indicated by the indexes 0, 1, 2, 3, etc.

The first two values in each element of the array are a voltage range. The second two values are the minimum and maximum acceptable per unit voltages for buses in that voltage range.

To be within a voltage range, a voltage must be greater than or equal to the minimum voltage specified and less than the maximum voltage specified.

%***** BUS OVER-VOLTAGE/UNDER-VOLTAGE DATA *********

/VoltLimArray 5 def /VoltLim VoltLimArray array def /VoltLimCount VoltLimArray 1 sub def VoltLim 0 [230 500 0.95 1.052] put VoltLim 1 [500 2000 1.00 1.100] put VoltLim 2 [115 230 0.95 1.052] put VoltLim 3 [ 0 115 0.95 1.052] put VoltLim 4 [ 0 9999 1.00 1.000] put

Bus Symbols

The user may add new bus shapes or change the existing ones. The default bus shape is a circle. A vertical bar (VB) and horizontal bar (HB) are also available. See ?? and ?? below. Bus symbols added in the pfmaster.post file can then be associated with bus records through the bus shape and scale factor fields on the bus coordinate record.

A typical bus symbol definition in the pfmaster.post file is the vertical bar bus symbol::

shapeIndex (VB) eq % begin drawing vertical bar
 {
 [] 0 setdash
 obj-line-width setlinewidth
 newpath % clear current point so it doesn’t show
 -.075 cmtr -1 cmtr bsScale mul moveto
 -.075 cmtr 1 cmtr bsScale mul lineto
 .075 cmtr 1 cmtr bsScale mul lineto
 .075 cmtr -1 cmtr bsScale mul lineto
 closepath
 gsave
 buscolor aload pop setrgbcolor % set backgroung color
 fill
 grestore
 fgcolor aload pop setrgbcolor % set foreground color
 exit
} if % done drawing vertical bar

Area Symbols and Bubble Plots

The user may add new area shapes or change the existing one. The default area shape is a cartouche (round-cornered box). See ?? and ??. Area symbols added in the pfmaster.post file can then be associated with area records through the area shape and scale factor fields on the area coordinate record.

The default area symbol definition in the pfmaster.post file is the cartouche or bubble::

%------- The enclosed code may be customized at the user's pleasure -----

bubFlg 0 ne                            % do not draw cartouche
{ exit } if

shapeIndex ( ) eq                      % begin drawing cartouche
{
bbSz1 0 eq {/bbSz1 0.80 cmtr def} if   % setup default size for bubble
bbSz2 0 eq {/bbSz2 1.50 cmtr def} if   % setup default size for bubble
 [] 0 setdash
 bub-wall-width setlinewidth
newpath                                % clear current point so it doesn't show
 /bbSz3 bbSz2 2 div def
 bbSz3 neg 0 bbSz1 90 270 arc
 bbSz3 bbSz1 neg lineto
 bbSz3 0 bbSz1 270 90 arc
 closepath
 gsave
 bgcolor aload pop setrgbcolor         % set background color
 fill
 grestore
 fgcolor aload pop setrgbcolor         % set foreground color

 /xTxt xTxt bbSz3 sub                  % calculate new x text coordinates
   bbSz1 3 div sub def
 /yTxt yTxt 0.5 cmtr add def           % calculate new y text coordinates

 exit
 } if                                  % done drawing cartouche

%-------- The enclosed code may be customized at the user's pleasure -----

Diagram Components

Example diagrams are shown in ?? and ??.

The hard copy diagram allows buses, branches, area, and interchange symbols to be intermixed on a diagram. Typically, however, bus/branch and area interchange diagram are drawn separately.

The diagram consists of two types of components:

  • Supportive components such as borders, diagram identification, legend, and comments.

  • Primary diagram components such as buses, branches, areas, and interchange flows.

Supportive Diagram Components

The example diagrams illustrate the two different types of default options, one with an identification box in the lower left corner (BPA standard) and the other with case id and headers at the top of the page (WSCC standard).

A border is drawn as close to the edge of the paper as printers allow.

The information below the border identifies the type of diagram, the date and time the diagram was created, the Powerflow program version that created the diagram, the time that the Powerflow case was created, and the name of the coordinate file.

In example 1, the case name, the date the case was created, and the Powerflow program version that created the case are shown on the first line within the box. A 20-character description of the case is on the second line. Comments entered by the user at the time the diagram was created follow. Note that the last user-entered comment on the bus/branch diagram begins with an ampersand (&). This comment instructs the program to read additional coordinate data from the file aberdeeninset.cor.

Blocks of text such as LOSSES on the bus/branch diagram and INTERTIE SCHEDULED ACTUAL on the area interchange diagram are the product of >DEFINE and C records in the coordinate file.

The LG (LeGend) option selects and locates the legend shown on the bus/branch diagram.

In example 2, an IPS-like three line title appears above the map. The first line is composed of the case name, description, date, and program version. The other two lines were entered as headers in the PF ID/Description menu (corresponds to command /HEADER in Power Flow Control (PFC)).

Primary Diagram Components: Bus/Branch Diagrams

The majority of the options previously discussed in the Options Record - O section refer to bus/branch diagrams. These options, along with the coordinate file, customize the diagram to the user’s specifications. In general, the diagram consists of bus and branch symbol groups and Powerflow solution values. Area and intertie information may appear on the same diagram, but there will be no connection between the two graphs, as is shown below.

_images/Diagram_Example.png

Diagram Example

The bus symbol group and values consists of the following:

  • Bus symbol — Circle, bar, etc. In the figure above, the bus symbol is fully-shaded (black) — see CHEHALIS 115 — for undervoltage buses and half-shaded (gray) — see OLYMPIA 500 — for overvoltage buses.

  • Identification — Powerflow name and kV or abbreviation. The figure below shows buses with the abbreviated form of identification. The CHEHALIS 230 bus is abbreviated CHEHALIS.

  • Voltage and angle — Printed above, below, or to the left or right of identification. In the figure above, the CHEHALIS 230 bus voltage is 238 kV and angle -27 degrees.

  • Bus load - Printed above, below, or to the left or right of voltage and angle. In the figure above, the load at CHEHALIS 230 is 13 MW and 4 Mvar.

  • Total flow on branches to buses not shown on diagram — printed above, below, or to the left or right of load. In the figure above, the net flow at the CHEHALIS 230 bus on branches that are not shown on the diagram is 39 MW into the bus and 17 Mvar out of the bus.

  • Generator symbol — Circle connected to bus with a short line segment. Power generation in MW is printed above the line and reactive generation is printed below the line. The figure above shows the generation at PAUL 500 is 1340 MW and -47 Mvar. A close inspection of the data would show the actual generation is on a low voltage bus at the same location as PAUL 500.

  • Shunt Reactive — Capacitor or inductor symbol connected to a bus with a short line segment. Maximum reactance available at the bus is printed above the line, and actual reactance used is printed below the line. The figure above shows that 116 Mvar of capacitive reactance is available and 109 Mvar is used at OLYMPIA 230.

The branch symbol group and values consist of the following:

  • Line segment symbol - Voltage-coded line segment representing a line or transformer connection between buses. Note the relationship to the legend.

  • Arrow symbol - Indicates direction of real power flow through the branch. In the figure above, a solid-shaded arrow (black) indicates the branch is loaded at 100% or more of a rated capacity.

  • Overload indicator - Flags circuits that are approaching an overload condition. Branches that are approaching a nominal, thermal, bottleneck, or emergency loading are flagged with an N, T, B, or E under the arrow. The actual current or Mva flow in the line or transformer is before the numeric flag and the rating follows the flag. The figure above shows the PAUL 500 to OLYMPIA 500 line carrying 287 amps and is over 90% of the line’s thermal rating of 270 amps. The solid arrow indicates the line is over 100% of the rating. (This is contrived data, of course.)

  • Branch flow - Real and reactive power (MW and Mvar) Branch flow is shown above the arrow. Real and reactive sending and receiving end flows are differentiated as follows. MW values are simply shown as numbers. Mvar values are shown within parentheses. Receiving end values are shown within square brackets. Negative values indicate a flow opposite the arrow direction. In the figure above, branch flow is shown above the arrow. Real and reactive sending and receiving end flows are differentiated as follows. MW values are simply shown as numbers. Mvar values are shown within parentheses. Receiving end values are shown within square brackets. Negative values indicate a flow opposite the arrow direction. The power flowing from PAUL 500 to OLYMPIA 500 is 252 MW and -92 Mvar as measured at the sending end.

  • Branch flow — MVA and current. An alternative to showing MW and Mvar is to show MVA for transformers and current for lines. The value shown is the maximum for any section of the circuit. If the maximum is at a point other than the sending end, an R is appended to the flow. If a circuit is composed of both line sections and transformer sections, the maximum current for the line section and maximum MVA for the transformer section will be shown. The receiving or sending/receiving end flag is eliminated.

    Example: .. image:: ../img/Example_500_amp_650_mva_Branch_Flow.png

    This example indicates 500 amps in a line section and 650 MVA in a transformer.

    Example: .. image:: ../img/Example_1000_amp_Branch_Flow.png

  • Branch flow - Real and reactive power loss. Real and reactive losses in MW and Mvar are shown above the arrow.

    Example: .. image:: ../img/Example_Real_Reactive_Branch_Loss.png This example indicates a loss of 1.23 MW and 0.05 Mvar in the branch.

  • Parallel circuits - Show number of parallel circuits represented by branch (default). The number of parallel circuits carrying the flow on the diagram is shown in brackets below the line. The figure above shows two parallel circuits between PAUL and SATSOP carrying a total of 260 MW and -92 Mvar.

  • Parallel circuits - Show flow on each circuit represented (option). The flow on each of the parallel circuits can be shown separately. The figure above shows two parallel circuits between CHEHALIS 230 and CHEHALIS 115. Each circuit is carrying 14 MW and -2 Mvar.

  • Transformer symbol (shown at tip of arrow).

  • Transformer taps (shown below transformer). The fiture above shows the CHEHALIS 115/230 transformers with taps of 115.50 and 234.75.

  • Series compensation symbol (shown at tip of arrow).

  • Series compensation value - Percent of line compensation shown below capacitor symbol. The figure shows the CHEHALIS 230 to OLYMPIA 230 line with 45% compensation.

Primary Diagram Components: Interchange Diagram

The area interchange diagrams are quite simple, showing the area data within the area symbol (bubble), and flow data above the lines connecting areas.

The area symbol and data consists of the following:

  • Area symbol — Cartouche (bubble).

  • LOAD — Summation of all loads within the specified area.

  • LOSS — Summation of all losses within the specified area.

  • GEN — Summation of all generation within the specified area.

  • SI (Scheduled Interchange) — Export of power from the specified area.

The interchange symbol and data consists of the following:

  • Interchange symbol — Line with arrows and values for Scheduled Interchange, Actual Interchange, and Circulating Flow.

    The values are shown above the arrows.

    The example above shows that 3280 MW was scheduled from NORTHWEST to PG AND E. The actual interchange was 2735 MW. The circulating flow, defined as actual interchange minus scheduled interchange, is 545 MW from PG AND E to NORTHWEST.

Primary Diagram Components: Difference Diagram

The format of difference diagrams is very similar to the format of the standard diagram. The standard diagram uses only one case, an active case. The difference diagram uses two cases, an active case and an alternate case.

Displayed values are calculated as active case values minus alternate case values. Arrows indicate the direction of power flow in the active case.

If there are a different number of circuits in the active and reference cases, the number of circuits is in each case shown below the circuit.

Example

_images/Example_Circuit_Difference_Count.png

This example shows the active case has 3 circuits and the alternate case has 2 circuits in parallel.

_images/Bus_Branch_Diagram_with_Inset.png

Bus Branch Diagram with Inset

_images/Area_Interchange_Diagram.png

Area Interchange Diagram

Calculating Line Impedance

The line impedance subroutine was been extracted from BPA’s Electromagnetic Transients Program (EMTP) and modified for computing a balanced pi-equivalent line section. You can find a clone of BPA’s EMTP The line impedance calculation feature is invoked from the branch data dialog. See the screenshot, diagram, and table below. It calculates the pi-equivalent quantities from the conductor type, conductor bundling, and tower geometry. The following applies to all calculations:

  • There is continuous transposition of phases.

  • Resistivity is calculated at 25 degrees Celsius.

  • Earth resistivity is constant at 100 ohm-meters.

The Line Impedance dialog box consists of three panels for data.

  • Conductor Values. This is the scrollable list of conductor data, which is usually imported from a line constants data file.

  • Edit Conductor. This is the only means to edit data.

  • Calculate Impedance. This output panel displays the pi-equivalent data.

_images/Line_Impedance_Calculation_Dialog_Box.png

Line Impedance Calculation Dialog Box

Description of Conductor Data Fields

Each physical conductor is characterized by a number of items that you need to specify. The following list describes these items:

UNITS Allows you to specify either metric or English units.

BASEKV The base value for the voltage in kV.

BASE MVA The base value for the power in MVA. (Default is 100.0.)

NAME Common conductor bird names are hard-coded. In Edit mode, selecting a name from the button menu automatically transfers O.D.``(outside diameter), ``SKIN, and RESIS data to the pertinent field. If any of these fields are modified, the conductor name becomes “other.”

IPHASE The phase number (an integer) to which this conductor belongs. Specify as zero for a ground wire (ground is phase number zero by definition). If more than one conductor is specified with the same phase number, this means that those conductors are to be bundled (electrically connected in parallel). Use numbers 1, 2, etc., without any missing (unused) entries, when you number the phases. In general, 1, 2, 3 pertain to circuit1, phases a, b, c, respectively; 4, 5, 6 pertain to circuit2, phases A, B, C, respectively.

SKIN A field that is specified with the ratio T/D, where: T is the thickness of the tubular conductor. D is the outside diameter of the tubular conductor. For a solid conductor, use 0.5.

RESIS The dc resistance of the conductor in ohms/kilometer if metric or ohms/mile if English.

DIAM Outside diameter of the a tubular conductor in centimeters if metric or inches if English.

HORIZ Horizontal separation of the center of the conductor from some reference line in meters if metric or feet if English. The location of the horizontal reference line is arbitrary. Distances to the right of the center line are positive, while those to the left are negative.

VTOWER Vertical height of the conductor above the ground at the tower in meters if metric or feet if English.

VMID Vertical height of the conductor above the ground at mid-span (midway between two towers) in meters if metric or feet if English.

Note

The average height of the line is calculated by the following equation if both the VTOWER and VMID fields are specified non-zero.

\[VMID + [(VTOWER - VMID)/3] = 2/3 x VMID + 1/3 x VTOWER\]

If either data field is left blank, the blank field defaults to the other field. In effect, the user specifies the average height.

SEPAR ALPHA Leave this blank unless the automatic bundling option is desired.

FREQ The frequency, \(f\), of the line impedance calculation in units of Hertz.

DIST The length of the transmission line under consideration in kilometers if metric or miles if English.

NBUND Leave this blank unless the following automatic bundling option is desired.

AUTOMATIC BUNDLING OPTION

Rather than specifying each conductor of a bundle individually, there is an automatic bundling option that allows a single conductor data to suffice for specifying the entire bundle. This can be used for a “regular” bundle, where by definition all component conductors are identical, and such conductors are also assumed to be uniformly spaced around the circumference of a circle.

Automatic bundling uses the data fields SEPAR, ALPHA, and NBUND, which are otherwise left blank. The “conductor” data then becomes “bundle” data according to the following specifications:

SEPAR The separation between adjacent conductors in the bundle in centimeters if metric or inches if English.

ALPHA The angular position of the first conductor (or any conductor) of the bundle in units of degrees. Positive angles are measured counter-clockwise as shown in Figure C-1.

NBUND The number of conductors that make up the bundle. Or, if you specify by name, separ, and alpha, nbund will be supplied by the program. (For names, see table above under Bundle at the 500 kV lines.)

_images/A_Six_Bundle_Conductor.png

A Six Bundle Conductor

_images/BPA_Conductor_Bundles.png

BPA Conductor Bundles

Output Values

Considerable data is required to compute the pi-equivalent for a single segment. The line impedance dialog is most effective when importing files containing line impedance data.

A typical file contains ASCII data in free-field format. The file types are .lcd for “line conductor data.” The following is an example.

/GET_DATA, TYPE = LINE_IMPEDANCE_CALCULATION
 UNITS = < ENGLISH | METRIC >, DISTANCE = < miles | km >
 BASEKV = <basekv>, BASEMVA = <basemva>, FREQUENCY = <freq>
 CONDUCTOR = 1 .3636 .05215 1.602 -20.75 50. 50. 0.0 0.0 0
 CONDUCTOR = 1 .3636 .05215 1.602 -19.25 50. 50. 0.0 0.0 0
 CONDUCTOR = 2 .3636 .05215 1.602 -0.75 77.5 77.5 0.0 0.0 0
 CONDUCTOR = 2 .3636 .05215 1.602 0.75 77.5 77.5 0.0 0.0 0
 CONDUCTOR = 3 .3636 .05215 1.602 19.25 50. 50. 0.0 0.0 0
 CONDUCTOR = 3 .3636 .05215 1.602 20.75 50. 50. 0.0 0.0 0
 CONDUCTOR = 0 .5 2.61 0.386 -12.9 98.5 98.5 0.0 0.0 0
 CONDUCTOR = 0 .5 2.61 0.386 12.9 98.5 98.5 0.0 0.0 0

The usual scenario involves the following steps.

  1. Import a relevant .lcd file using the Use Saved button.

  2. Edit the file to reflect the geometric and physical attributes of the line under consideration.

  3. Calculate the pi-equivalent data. Steps 2 and 3 may be iterated as long as necessary to eliminate errors.

  4. Export the modified .lcd file using the Save Values button.

  5. If the results are acceptable, automatically transfer the positive sequence values back to the line dialog by pressing the OK button. (The zero sequence values are for inspection only.)

  6. If the results are not acceptable, press the Close button. No values are transmitted back to the line dialog by a Close action.

Calculating the Impedance

After you have supplied all the necessary values for the line impedance calculations, you can click on the Calculate Impedance button in the Line Impedance Calculation dialog box. The program fills in six numbers in per unit values having the following meanings:

R/Z1 transfer Real part of the positive sequence transfer impedance per unit.

X/Z1 transfer Imaginary part of the positive sequence transfer impedance per unit.

R/Z1 shunt Half value of the real part of the positive sequence shunt admittance per unit.

X/Z1 shunt Half value of the imaginary part of the positive sequence shunt admittance per unit.

R/Z0 transfer Real part of the zero sequence transfer impedance per unit.

X/Z0 transfer Imaginary part of the zero sequence transfer impedance per unit.

DC Line Modeling

The following describes the data representation of a DC line as used in IPF. A typical configuration of the network is shown.

_images/Two_Pole_Two_Terminal_DC_Line_Configuration.png

Two Pole, Two Terminal DC Line Configuration

Each DC line requires two DC buses, a single DC line and two commutating buses, each of which is connected to the DC bus with a commutating transformer.

Representation of the commutating transformer conforms to the ac network; one transformer is required for each bridge. They are parallel connected in the ac network, necessitating either separate transformer data records or an equivalent transformer which has the correct parallel impedance and MVA rating. As shown in the diagram, the commutating transformers must be LTC, specifically type R, subtype blank, controlling the DC bus, and oriented such that the tap range encompasses the commutating bus base kV. The magnitude of the DC bus voltage to be controlled is automatically determined from the DC line parameters.

Assuming nominal taps, the DC no-load voltage Vdo available from each converter bridge is approximated by the formula.

\[V_{do} = 1.35 * E_v * cos(\alpha)\]

where \(\alpha\) is the firing angle at the rectifier and the extinction angle at the inverter. \(V_{do}\) is the no-load direct voltage and \(E_v\) is the effective voltage at the DC bus. The actual voltage is a chopped sinusoid.

The full load direct voltage will be less. Normal representation of the DC line usually models the positive and negative poles as separate but parallel DC lines. This scheme permits asymmetrical operation of the DC line. For example, one bridge may temporarily be out of operation. In this case, one pole may have three bridges while the other has only two.

With this scheme, the model may be as shown as follows.

_images/Single_Pole_Two_Terminal_DC_Line.png

Single Pole, Two Terminal DC Line

In the former scheme the dc line quantities are pole-to-pole. In the latter scheme, the quantities are pole-to-neutral. However, the direct voltage must always be positive on the line data record.

When using the pole-to-neutral scheme, the direct voltage of each pole must correspond to the number of bridges in operation. It is recommended that the allocation of the total dc power to each pole should result in no net neutral current, that is, the current in each pole must be equal but opposite.

An example will clarify this. Assume that the normal direct voltages is 800 kV pole-to-pole with six bridges in operation, or 133 kV/bridge. It is desired to find the voltage and power in each pole required to transport 600 MW with one negative bridge out of operation. This situation is shown as follows

_images/One_Negative_Bridge_Out_of_Operation.png

One Negative Bridge Out of Operation

For zero neutral current, \(I^+_d = I^-_d\) (with positive values assigned in the direction shown)

\[\begin{split}I_d = \frac{p_{dc}}{V_{dcpole-to-pole}} &= \frac{600 MW * 1000 kV/MW}{667 kV} = 900 amps \\ P^+_{dc} = V^+_{dv} * I^+_{dc} &= 400 kV * 900 amps \\ &= 360,000 kW = 360 MW \\ P^-_{dc} = V^-_{dv} * I^-_{dc} &= 267 kV * 900 amps \\ &= 240,000 kW = 240 MW\end{split}\]

Assuming the DC line was modeled for six-bridge operation, the only changes required to take a bridge out of service would be modification of the following quantities:

  • Positive and negative pole DC line power on the LD record.

  • Negative pole DC line voltage on the LD record.

  • Delete one of the parallel commutating transformers at each end of the negative pole DC line.

  • Change the number of bridges for both converter buses.

Network Reduction

This section gives a detailed description of the network reduction method and solution options.

Method of Reduction

This program reduces a large sparse network into a smaller equivalent network by Gaussian decomposition. The original network is linearized about the operating point and is expressed by the current equation:

()\[\begin{split}\begin{bmatrix} I_1 \\ I_2 \end{bmatrix} = \begin{bmatrix} Y_{11} & Y_{12} \\ Y_{21} & Y_{22} \end{bmatrix} \begin{bmatrix} V_1 \\ V_2 \end{bmatrix}\end{split}\]

where: \(I_1\) is the complex current net injection matrix, \(Y\) the complex nodal admittance matrix, and \(V\) the complex nodal voltage matrix. The subscripts 1 and 2 pertain to the eliminated and retained portions of the network, respectively. For simplicity, the matrix is reordered as shown. We may separate the partitioned matrix equations in Eq.1.

()\[\begin{split}\begin{bmatrix} I_1 \end{bmatrix} = \begin{bmatrix} Y_{11} \end{bmatrix} \begin{bmatrix} V_1 \end{bmatrix} + \begin{bmatrix} Y_{12} \end{bmatrix} \begin{bmatrix} V_2 \end{bmatrix} \\\end{split}\]
()\[\begin{bmatrix} I_2 \end{bmatrix} = \begin{bmatrix} Y_{21} \end{bmatrix} \begin{bmatrix} V_1 \end{bmatrix} + \begin{bmatrix} Y_{22} \end{bmatrix} \begin{bmatrix} V_2 \end{bmatrix}\]

We may solve for \(\begin{bmatrix} V_1 \end{bmatrix}\) from Eq.2.

\[\begin{bmatrix} V_1 \end{bmatrix} = \begin{bmatrix} Y_{11} \end{bmatrix}^{-1} \begin{bmatrix} V_1 \end{bmatrix} + \begin{bmatrix} Y_{22} \end{bmatrix} \begin{bmatrix} V_2 \end{bmatrix}\]

and then substitute the expression into Eq.3.

\[\begin{bmatrix} I_2 \end{bmatrix} = \begin{bmatrix} V_{21} \end{bmatrix} \begin{bmatrix} \begin{bmatrix} \begin{bmatrix} Y_{11} \end{bmatrix}^{-1} \begin{bmatrix} I_1 \end{bmatrix} - \begin{bmatrix} Y_{11} \end{bmatrix}^{-1} \begin{bmatrix} Y_{12} \end{bmatrix} \begin{bmatrix} V_2 \end{bmatrix} \end{bmatrix} \end{bmatrix} + \begin{bmatrix} Y_{22} \end{bmatrix} \begin{bmatrix} V_2 \end{bmatrix}\]

Rearranging terms, we have

\[\begin{bmatrix} I_2 \end{bmatrix} - \begin{bmatrix} Y_{21} \end{bmatrix}^{-1} \begin{bmatrix} I_{1} \end{bmatrix} = \begin{bmatrix} \begin{bmatrix} Y_{22} \end{bmatrix} - \begin{bmatrix} Y_{21} \end{bmatrix} \begin{bmatrix} Y_{11} \end{bmatrix}^{-1} \begin{bmatrix} Y_{12} \end{bmatrix} \end{bmatrix} \begin{bmatrix} V_2 \end{bmatrix}\]

or

()\[\begin{bmatrix} I_2 \end{bmatrix}eq = \begin{bmatrix} Y_{22} \end{bmatrix}eq \begin{bmatrix} V_2 \end{bmatrix}\]

where:

()\[\begin{bmatrix} I_2 \end{bmatrix}eq = \begin{bmatrix} I_2 \end{bmatrix} - \begin{bmatrix} Y_{21} \end{bmatrix} \begin{bmatrix} Y_{11} \end{bmatrix}^{-1} \begin{bmatrix} I_1 \end{bmatrix}\]
()\[\begin{bmatrix} Y_{22} \end{bmatrix}eq = \begin{bmatrix} Y_{22} \end{bmatrix} - \begin{bmatrix} Y_{21} \end{bmatrix} \begin{bmatrix} Y_{11} \end{bmatrix}^{-1} \begin{bmatrix} Y_{12} \end{bmatrix}\]

The matrix operations in Eq.5 and Eq.6 have the following interpretation:

Equivalent injection = original injection + distributed injection

Equivalent admittance = Original admittance + distributed admittance + equivalent branches

Equations Eq.5 and Eq.6 have interesting topological interpretations. Some notation is necessary so the following definitions apply:

Envelope node

A retained node with at least one adjacent node in the eliminated system.

Internal node

A retained node with all adjacent nodes in the retained network.

Equivalent branch

A fictitious branch between two envelope nodes which effectively represents the reduced network as seen from those nodes.

Inherent in the reduction is the connectedness of the network and the preserved identity of the current equations. An eliminated node is connected (not necessarily directly) to several envelope nodes. Any injected current on that node becomes branch current in the eliminated system. After deducting losses, it finally reaches the envelope nodes and is reconverted into an equivalent injection. The distribution of eliminated injections is determined by the admittance of the eliminated system. By superposition, the injections from all eliminated nodes are distributed to the envelope nodes. This reflects the second term on the right side of equation Eq.5. This does not imply, however, that the equivalent injections are identical to the branch currents and could also be obtained by arbitrary cutting of the network. The reasons will be explained in examples to follow.

The equivalent branches introduced between the envelope nodes after reduction reflect the admittance seen from the envelope nodes and into the eliminated network and finally to other envelope nodes. It is similar to the delta branches introduced in a wye-delta conversion. The value of the equivalent branches is found in the second term in the right side of equation Eq.6.

The branch data is originally submitted in the form of equivalent pi’s which are used to construct the nodal admittance matrix Y. In general, the reverse process is not unique. The figure below illustrates the form of the equivalent pi-branches obtained.

_images/Equivalent_Pi-Branches.png

Equivalent Pi-Branches

In the figure below, a nine-node network is reduced. The distributed injections and equivalent branches introduced are emphasized.

_images/Network_Reduction.png

Network Reduction

Three options are available for disposal of the generation and load of eliminated nodes:

  1. Generation and load assumed constant current.

  2. Generation assumed constant current, load assumed constant admittance.

  3. Generation and load assumed constant admittance

These options are illustrated by the examples in the figure below. For simplicity, losses are ignored and a DC model is used.

_images/Eliminated_Node_Generation_and_Load_Disposal.png

Eliminated Node Generation and Load Disposal

In all examples, the equivalent branch flow represents the sum of three components:

  1. The power looping into the eliminated system and back out to the retained system.

  2. The flow of generation within the retained system through an envelope node to the distributed loads of the equivalent system.

  3. The flow of distributed generation on the envelope nodes to loads within the retained system.

The difference between network reduction and network cutting is seen in component 1 above. This component is found by assuming all generations and loads within the eliminated system are identically zero. Thus, in equation Eq.5, \(I_1 = 0\) and

()\[\begin{bmatrix} I_2 \end{bmatrix}eq = \begin{bmatrix} I_2 \end{bmatrix}\]

The branch flow in this case is strictly due to the differences of voltages between envelope nodes, i. e., looping. This is the important distinction between reduction and cutting.

Description of Reduction

The nodal admittance matrix is retrieved from the base file and selective elimination is performed first upon all eliminated nodes and then partially upon the retained nodes.

A complete pass merges the data from the reduced current matrix and the reduced admittance matrix with the system data from the base file. Eliminated data is purged and equivalent branches and distributed injections are added to the data. Concurrent with this pass, a simple injection check is performed on the envelope nodes. The net injection of the nodes is compared with the original values. Any mismatches are errors and will be flagged.

Special consideration is given to the distributed shunt admittances. The envelope nodes which receive these admittances may be subtype Q. In such a case, this portion of the shunt admittance is not adjustable for voltage control. To accomplish this, a special continuation bus subtype, +A, was created, to which all distributed injections and shunt admittances are added. In the power flow output listings, this portion of the admittance is flagged “EQUIVALENT” to confer distinction over other adjustable susceptances.

Upon completion of the reduction, all equivalent branches and injections are added to the system data and all data in the eliminated system is permanently deleted. A new base case is created, updated, and must be solved. Thus, a /SOLUTION and /NEW_BASE command must follow any network reduction. If desired, subsequent changes could be applied.

An example setup for doing a network reduction with bpf is shown in Reduction Case Example.

The program is written such that the method of determining the base case is irrelevant to the options that may be performed. Once a base case is defined and solved, any of the options for a base case may be exercised. Thus, further network reduction could be performed upon the already reduced system. Proper position of the appropriate control cards give the user complete flexibility.

Program Control Options

There are seven options that the user may exercise; they are all specified by qualifiers within the /REDUCTION command set.

  1. Admittance cutoff (MIN_EQUIV_Y).

  2. Disposition of injections (elimination mode: ELIM_MODE, final mode: ULT_MODE).

  3. Retain generators by “REI” scheme (REI_CLUSTERS, ELIM_MODE).

  4. Retain area interchange nodes (KEEP_AI_SYSTEM).

  5. Retain all generators (RETAIN_GEN).

  6. Optimal network determination (OPTIMAL_REDU)

  7. Minimum generator cutoff for “REI” equivalent (ELIM_MODE).

These options are discussed in the following paragraphs.

Admittance Cutoff

Assume that the retained network has n nodes in which m (m < n) nodes define the envelope. Assume furthermore that there is a path from any envelope node into the eliminated network and back to any other envelope node. Then, inherent in the reduction, there will result an equivalent branch between any pair of envelope nodes. The total equivalent branches added will be

\[\frac{m(m-1)}{2}\]

This total can become large. Many equivalent branches added between the most relatively remote pair of envelope nodes will have a branch impedance excessively large and presumed negligible. The admittance cutoff is a parameter that the user may choose in eliminating these branches from the generated reduced system data. It is defined as

Admittance Cuttoff = \(\abs{\frac{1}{R + jX equivalent}}\)

For example, the value 0.001 will exclude all equivalent branches with an equivalent impedance of 1000 p.u. ohms or more.

Disposition of Injections

The disposition of injections of eliminated nodes has, in all, 12 different combinations of options. Each combination is unique with its inherent advantages and disadvantages.

The injections are divided into three parts: (1) generation, (2) load, and (3) shunt admittance. Each of these injections has two modes of disposition during reduction and three additional modes ultimately. The transition of a single injection is shown in below.

_images/Injection_Disposition_of_Eliminated_Notes.png

Injection Disposition of Eliminated Nodes

Reduction Mode

The two possible modes of disposition during reduction are constant current and constant admittance. A summary of each option with its inherent characteristics follows:

Generation:

  • Constant current has improved convergence characteristics; retains identity as generation.

  • Constant admittance appears as fictitious negative impedance; has major effect on passive equivalent network.

Load:

  • Constant current retains identity of load

  • Constant admittance has slightly better convergence characteristics; has major effect on passive equivalent network.

Shunt admittance:

  • Constant current avoids negative impedances in the equivalent network.

  • Constant admittance preserves the identity of the passive network.

Ultimate Mode

After equation Eq.6 has been solved for \(I_2 eq\) and \(Y_{22} eq\), the question arises: How should the separate components of \(I_2 eq\) be disposed to their ultimate state?

From Figure 5-4 we have three options to dispose \(I\); namely \(P\), \(I\), or \(Y\). A summary of each is described below.

Generation and load:

  • Constant power is typical and preserves the identity of generation or load.

  • Constant current is preferred and has superior convergence characteristics.

  • Constant admittance is the least preferred and has poor accuracy.

Shunt admittance:

  • Constant power is atypical and is available for compatibility only.

  • Constant current is the same as constant power.

  • Constant admittance is preferred and is most realistic to a passive network.

Summary

The recommended disposition is therefore summarized in the table below.

Disposition of Components

Quantity

Reduction Mode

Ultimate Mode

Generation

I

I

Load

I

I

Shunt Admittance

Y

Y

REI Equivalent

One disadvantage inherent in reduction involves the properties of eliminated generators. The power injections are converted into current injections using the steady-state solution voltages. Every eliminated generator therefore becomes identical to a bus with fixed real and reactive injection, but without fixed voltages typical of BQ nodes with reactive inequality constraints. Consequently, the eliminated system loses its voltage regulation capacity. System changes near the border nodes of reduced equivalent systems often converge to voltage profiles quite different from the full system. The obvious remedy is to reinstate these generators or, alternately, to preserve their regulating characteristics.

The normal option of retaining generators has been unsatisfactory. A network having 1600 nodes that is reduced to a system of 600 nodes may also include about 200 retained generators and an extremely disproportionate number of equivalent branches. The reduced equivalent system is typically about 75 percent of the size of the full network and nearly defeats any merits gained in reduction.

The “REI” equivalent is an innovative alternate to preserving eliminated generators directly. The initials mean Radial Equivalent Independent. It is a simple scheme in which several eliminated generators are connected to a common ground node having zero voltage but isolated from the ground of the rest of the system. This ground node is then tied directly to an equivalent generator. The branch admittance from the ground node to all the generators and to the equivalent node are determined such that no real or reactive power is gained or lost. A simple resistive network as shown in the fibure below demonstrates the procedure.

_images/Example_of_Network_and_Its_REI_Equivalent.png

Example of Network and Its REI Equivalent

The example above has moved the current injections at nodes 2 and 3 in (a) back to an equivalent node 5, which has 3A injection. The current flowing from 4 to 2 is 2A; from 4 to 3 is 1A. The power loss in the branches is

\[ \begin{align}\begin{aligned}P = I_{42}^2 R_{42} + I_{43}^2 R_{43} + I_{54}^2 R_{54}\\= 2^2(-1.75) + 1^2(-1.833) + 3^2(0.981) = 0 watts\end{aligned}\end{align} \]

This zero power loss is deliberate. It is termed the zero power balance. Introduction of the REI system has not changed the total system losses.

Although this example demonstrates the procedure involved, it does not illustrate the merits in preserving sparsity. Only in large networks does this become apparent. Consider the network in the figure below.

_images/Direct_and_Indirect_Generator_Preservation_in_Eliminated_Network.png

Direct and Indirect Generator Preservation in Eliminated Network

The letter “b” in the figure above is the number of border nodes in the network. The letter “g” is the number of generators in the eliminated network. If they are saved directly and the rest of the network is eliminated, the number of equivalent branches is at worst.

\[N_{br} = \frac{g(g - 1)}{2} + gb + \frac{b(b - 1)}{2}\]

However, if an REI equivalent is obtained instead, \(g = 1\) and

\[N'_{br} = b + \frac{b(b - 1)}{2}\]

Typical numerical values are \(g = 10\), “math:b = 15. Then \(N_{br} = 225\) and \(N'_{br} = 120\). This is nearly a 50 percent reduction in the number of equivalent branches.

REI Clusters

In the figure of the previous example, all of the border nodes will be normally fully interconnected. The total number of branches is easily computed by b(b-1)/2 where b is the number of border nodes. If b is large, say 50, then 50*49/2 = 1225 equivalent branches will result during this elimination. (The same number would occur without the REI equivalents.) However, if the area interchange system is retained, the eliminated system becomes clustered with a dramatic reduction in the number of equivalent branches.

_images/Small_System_Network_Areas_and_Tie_Lines_Shown.png

Small System Network (Areas and Tie Lines Shown)

A typical equivalent of the figure above might normally retain area A in full detail, and would include all the tie line nodes and area slack buses of the remaining system. The rest of the system is replaced with an equivalent. This area interchange system permits the eliminated system to be assigned clusters (a minimum of one cluster per area). Each cluster is assigned an “REI” equivalent generator to replace all the eliminated generators.

Defining clusters does not decrease the number of eliminated generators nor decrease the number of border nodes. However, it isolates the interconnections from one REI equivalent to another. For example, suppose that the previous example was split into two clusters defined with the following bus counts:

\[ \begin{align}\begin{aligned}= 5 g_2 = 5 g_1 + g_2 = 1\\= 7 b_2 = 8 b_1 + b_2 = 1\\N_{br}' = (b_1 + \frac{b_1(b_1 - 1)}{2}) + b_2 + (\frac{b_2(b_2 - 1)}{2}) = 64\end{aligned}\end{align} \]

Comparing this with the previous example of 10 generators and 15 border nodes, this is nearly a 50 percent reduction in the number of equivalent branches from the REI equivalent without clusters.

Coherency Clusters

In some applications, the generators equivalenced by the area interchange clustering may not be the desired grouping. Specifically, if the reduced network is to be used with a transient stability program, the coherent groups may be determined by other factors such as size or voltage level. In this application, the coherent groups can be specified individually by additional data as shown in the figure below. The data may either supplement or complement the normal REI clustering.

_images/General_Data_Used_to_Define_or_Modify_REI_Clusters.png

The set of data cards illustrated in the figure above follow immediately the control card SAVE_BUSES or after the last bus following the control cards INCLUDE_BUSES or EXCLUDE_BUSES. The name of the equivalent generator (coherent equivalent) must be unique; i. e., it cannot be any bus already in the system. The names of the coalesced generators may be any bus already defined in the network. It may be eliminated or retained (in which case elimination will become mandatory).

It may also be already assigned to another REI equivalent cluster. Any errors encountered will

be described with diagnostics and the program will exit.

Using REI Equivalents

The ELIM_MODE command requests REI equivalencing of eliminated generators. An additional parameter specifies the minimum PGEN for a bus to be normally coalesced. Larger values of PGEN will exclude the smaller generators from being coalesced. Care should be exercised when requesting coalesced generators, since table overflow will occur if more than 99 generators are coalesced into a single equivalent.

The equivalent generators are made type BQ with a scheduled voltage computed for zero power balance. Names such as “EQUIV 1” are program generated and pertain to the clusters in which they reside. However, if “COH” data is submitted, the generator names are as specified in the data. The zone of an equivalent generator is randomly selected to be any zone of one of the coalesced generator.

Optimal Network Determination

When not using the REI equivalent, the number of equivalent branches may become excessively large and compromise any advantages obtained by network reduction, unless the retained network is judiciously chosen. If the optimal feature is selected using the OPTIMAL_REDU command, the retained network specified by the input data will be interpreted as the “minimum” retained system. Nodes selected for actual elimination will contribute to a definite reduction in system size. Thus, the optimal feature will expand the retained system if necessary to minimize the network size.

REDUCTION Command

This control card requests a network reduction to be performed on the base case or change case that has been defined. It generates an unsolved, reduced equivalent base case. Other commands must eventually follow to obtain the new solution and any desired outputs. However, system data could follow the /REDUCTION to update the reduced case.

The reduced system is composed of internal and enveloping retained nodes. The internal nodes undergo no change during the reduction. The enveloping nodes are those which have branches into the reduced system. However, these branches are replaced with equivalent branches connected to other enveloping nodes which simulate the reduced system. In addition, any nodal injection is distributed to the enveloping nodes in the form of continuation bus data.

All distributed injections and equivalent branches are flagged with the ownership code ***. This emphasizes their fictitious nature; however, they are valid system data and should be treated as such.

Retained Network Definition

The network to be reduced is obtained from a solved base case. The retained system is defined by the user in the INPUT file. Five options are available to the user as shown in the figure below.

_images/Retained_Network_Input_Options.png

Retained Network Input Options

Each of the options 1 through 5 are affected by the unique control cards described in upper case characters in the blocks in the figure above. Their formats are described in the following paragraphs.

Reduction Cards

The reduction cards specify the retained systems. There are several options available. 1. Zone Selection. The zones which normally define geographical areas may be used to define the retained system. All buses within these zones are then retained. The format is essentially “free-field”. Commas separate the different zones and a period terminates the list. Any blanks are ignored unless immediately preceded by a comma or a period. The command >SAVE_ZONES must begin in column 1. If the zone list is too long to be contained on a single card, continuation cards must be used, in which a blank appears in column 1 and the zone list continued. 2. Base kV Selection. The retained system may be selected as the set of all buses with base kV’s matching the specified set. As with the previous card, the format is essentially free-field. However, decimal points may be part of the base kV, necessitating a double period to terminate the list. The command >SAVE_BASES must begin in column 1. Continuation cards are permitted. If they are used, a blank must appear in column 1 as the base kV list continues. 3. Zone Selection Subjected to Base kV’s. This is a combination of steps 1 and 2 described previously. Each of the zones selected is further stipulated to certain base kV’s. Recognition is acknowledged that different zone/base kV combinations may be desirable, and several zone-base KV cards are permitted. The format is similar to steps 1 and 2 above. The difference is that the last zone (there may be only one) is followed by a comma and the words >SAVE_BASES. Continuation cards are permitted. 4. Inclusion and Exclusion of Buses to Retained System. The general criteria of saved zones, saved bases, or both is recognized as too general to adequately define all retained systems. Provisions permit the system thus defined to be enlarged or contracted by specifying individual buses which are to be included into or excluded from the retained system. The retained system is expanded with the control card. >INCLUDE_BUSES beginning in column 1 and followed with separate bus cards. The bus card need only contain the B in column 1, and the bus name and base kV in columns 7-18. All other fields are ignored. The list of included buses is terminated when a card without a B in column1 is encountered. The retained system is contracted with the control card >EXCLUDE_BUSES beginning in column 1 and followed with separate bus cards as described previously. 5. Individual Bus Selection. In lieu of options 1. through 4.described previously, the retained system could be identified by individually specified bus cards. This request is initiated with the control card >SAVE_BUSES beginning in column 1. Each retained bus is then individually specified with a bus card. Only the bus identification fields need be specified, that is, the B in column 1 and the bus name and base kV in columns 7-18. All other fields will be ignored. The list continues until a card without a B in column1 is encountered.

Input listings

Following the program control card and subsequent reduction cards, the retained system is defined and two listings are produced. The first listing defines the retained network. Each bus name will be preceded with one or two of the following characters: Blank Retained bus is internal and unchanged. E Retained bus is an envelope node and will receive distributed injections and equivalent branches. X Retained bus is also an envelope node. However, everyone of the adjacent nodes is eliminated. This is acceptable but may not be intentional and is intended as an informative diagnostic. * Retained bus is selected by the optimal feature. P Retained bus is a generator. The second listing defines all eliminated nodes.

Voltage Limits and Starting Voltages

The following table allows you to find global and starting voltages for a bus given the base kV and zone. These values are hard-coded in the program and cannot be altered by the user.

Global Voltage Limits and Starting Voltages

Base kV Range

Zone

Restrictions

Global V Limits

Starting V

From

To

V_min (p.u.)

V_max (p.u.)

Gen Buses (40%)

Load Buses (20%)

0.1

6.5

0.950

1.052

1.011

1.032

6.6

6.6

M1

0.950

1.065

1.019

1.042

6.6

49.9

0.950

1.052

1.011

1.032

50.0

50.0

16

1.100

1.200

1.160

1.180

50.0

59.9

0.950

1.052

1.011

1.032

60.0

60.0

17

0.950

1.100

1.040

1.070

60.0

62.9

0.950

1.052

1.011

1.032

63.0

63.0

20

0.930

1.080

1.020

1.050

63.0

99.9

0.950

1.052

1.011

1.032

100.0

100.0

16 M5

1.100

1.200

1.160

1.180

100.0

100.0

M4

0.950

1.070

1.022

1.046

100.0

114.9

0.950

1.052

1.011

1.032

115.0

115.0

M4

0.950

1.070

1.022

1.046

115.0

131.9

0.950

1.052

1.011

1.032

132.0

161.0

17 20

0.950

1.090

1.034

1.062

132.0

199.9

0.950

1.052

1.011

1.032

200.0

200.0

16

1.100

1.200

1.160

1.180

200.0

229.9

0.950

1.052

1.011

1.032

230.0

230.0

17 20

0.950

1.070

1.022

1.046

230.0

499.9

0.950

1.052

1.011

1.032

500.0

500.0

1.000

1.100

1.060

1.080

500.1

1099.9

1

0.950

1.052

1.011

1.032

1100.0

1100.0

1

1.000

1.100

1.060

1.080

1100.1

9999.9

1

0.950

1.052

1.011

1.032

Notes

  1. Twenty percent (20%) and forty percent (40%) starting voltages are the percentages from \(V_{max}\) to \(V_{min}\):

\[V_{start} = V_{max} * (1 - \%pct) + V_{min} * \%pct\]

“0%” starts at \(V_{max}\); “100%” starts at \(V_{min}\).

Ideal starting percentages would be a value which lies closest to the final voltages. For peak load cases, a generator percentage of 30% is better; for light loads, 50% is better. The current 40% is a trade-off.

  1. Zone restrictions mean that base kV’s are also subject to zones. If the zone restriction list has nonblank entities, only base kV’s within the range and zone list zones apply. Conversely, if the zone restriction list is blank, then there are no zone restrictions: all base kV’s within the range apply.

  2. To find global and starting voltages for a bus with Base XXX and Zone ZZ, proceed as follows:

  1. Find the encompassing base kV:

    From_base <= XXX <= To_base

    There will be one or more such ranges. Zone restrictions may qualify the base range.

  1. If zone restrictions apply, check whether zone ZZ qualifies. If true, then the pertinent entity has been located.

If false, proceed to the next encompassing base kV and repeat step b. All encompassing base ranges terminate with an inclusive blank zone list, which ultimately defaults to “no restrictions”.

Developer Notes

This section contains notes for developers working with, enhancing, or debugging the IPF codebase.

Debugging

You can list names of functions or subroutines to debug in a DBGIN file in .fil passed to tsp. Debug output is printed to file defined by DBGOUT. For example, the following routines can be listed: CNTRL, CNTRLA, FFREAD, INITL1, INITL4, INPUT1, INT3FA, LSREAD, MATMOD, NAMBAS, NOUT1, NOUT2, RVREAD, SOLN, SWINGM, TAPEWK, WRTHIS. These Fortran subroutines will have their debug enabled.

bpf Flowchart

Below is a high level flowchart of the batch power flow process.

_images/IPF-bpf-flowchart.png

IPF bpf Flowchart

tsp Flowchart

Below is a high level flowchart of the transient stability program.

_images/IPF-tsp-flowchart.png

IPF bpf Flowchart

Variables

Reading IPF code can be challenging. Fortran 77 was the programming language of the 70s and 80s. Today there are small percentage of developers that know Fortran and even fewer that have experience writing significant amounts of it. Though it is important to note that the language is still used in several well known projects such as the Linear Algebra PACKage (LAPACK) .

Fortran developers must use very concise variable and function/subroutine names to make sure lines fit in the 80 character limit and original limitations on 8 character file names. Additionally, IPF code base makes heavy use of common blocks to pass data between functions (these are basically like blocks of data since Fortran has no concept of an object or even a struct as in C) as well as goto statements. This can make any given piece of code overwhelming to a newcomer. For example, you might encounter something like this and feel completely lost:

kbrknt = mptr / 2
next1 = mptr + 1
next2 = mptr + 1
last1 = nsize
last2 = nsize
do k = next1, last1
   kolum1(k) = 0
   kordr1(k) = k+1
enddo
kordr1(last1) = 0
do k = 1, ntot
   jorder(k) = kownt(2,k)
   loc2(k) = loc1(k)
enddo
do k = 1, nsize
   kordr2(k) = kordr1(k)
   kolum2(k) = kolum1(k)
enddo

The table below contains a list of more descriptive names for variables. This can be used as a reference when getting started.

Variable

Description

datot

Delta area real power total. Total area real power mismatch for power flow

dptot

Delta real power total. Total real power mismatch for power flow iteration

dqtot

Delta reactive power total. Total reactive power mismatch for power flow iteration

dttot

Delta transformer MVAR. Total transformer apparent power mismatch for power flow iteration

icount

Count of solution truncation adjustments

ikecl

Jacobian matrix storage size

ittot

Power flow iteration counter

kownt

Unsolved buses count

kowntb

Unsolved auto transformers

kowntc

Unsolved areas

lppwr

Iteration for solving machine equations

eyr

Bus per unit voltage real component. “A” in “A + jB”

eyi

Bus per unit voltage imaginary component. “B” in “A + jB”

isg

Number of synchronous generators

idsw

Discontinuity state

Command Subroutines

This section has a information about which Fortran subroutines to take a look at if you’re trying to debug a certain PFC or PCL command.

/INITIALIZE

     processed by  p_pfinit_

/NETWORK_DATA, FILE = <filename>

     processed by p_gtnetdat_

/OLD_BASE, FILE = <* | filename> [, CASE = <casename>]
                               [, REBUILD = < on | off> ]
     processed by cmd_parse.c
                  p_gtbase.f
                  ctlpow.f

/CHANGES, FILE = <* | filename>

     processed by cmd_parse.c
                  p_change.f
                  ctlpow.f

/SOLUTION
> BASE_SOLUTION
> DEBUG, BUS = ON,(page 3-51 to 3-56)

     processed by cmd_parse.c
                  p_solton.f
                  ctlpow.f

/GET_DATA, TYPE = INPUT
A     <areaname>  to be added 22 July by wlp
I     <area1 area2> to be added 22 July by wlp
B     <busname, etc> returns all data associatated with bus
+     <busname, etc> returns all data if id fields have wild cards
                   (type - column 2, owner, columns 3-5, and code-year
                    columns 20-21)
X     <busname, etc>
L     <bus1 bus2, etc> returns all paralles if id is wild card (*)
                     returns all sections if section is 0
T     <bus1 bus2, etc>
R     <bus1 bus2, etc>
E     <bus1 bus2, etc>

     processed by cmd_parse.c
                  p_gtdata.f
                  gtinput.f

/GET_DATA, TYPE = BUS_VOLTAGES

     processed by cmd_parse.c
                  p_gtdata.f
                  bus_voltages.f

/GET_DATA, TYPE = BUS_LIST [ FROM BUS_DATA ]
                WHERE AREAS = <area1>, <area2>, etc AND
                       ZONES = <zone1>, <zone2>, etc AND
                       OWNERS = <own1>, <own2>, etc AND
                       BASEKV = base1
                                < base  ( example < 115.0 means all base
                                          kv's less than or equal to 115.0)
                                > base  ( example > 115.0 means all base
                                          kv's greater than or equal to 115.0)
                                base1 < base2  (all bases between base1 and
                                                base 2)
                                base2 > base1  (same as above)
                       TYPE = B , BE, BS, BC, BD ,BV ,BQ ,BG ,BO ,BT ,BX ,
                              BM ,L  ,LD ,LM , ,E  ,T  ,TP ,R
                       BUS = "<busname>" (quotes are necesary)
                       AFTER_BUS = "<busname>" ( to do 22 July by wlp)
                       ALL
                       LOADING = (<min> <max>)

     processed by cmd_parse.c
                  p_gtdata.f
                  bus_list.f
                  gtfltr.f

/GET_DATA, TYPE = A_DATA

     processed by cmd_parse.c
                  p_gtdata.f
                  a_data.f

/GET_DATA, TYPE = I_DATA

     processed by cmd_parse.c
                  p_gtdata.f
                  i_data.f

/GET_DATA, TYPE = BSEKV_LIST

     processed by cmd_parse.c
                  p_gtdata.f
                  bsekvlst.f

/GET_DATA, TYPE = AREA_LIST

     processed by cmd_parse.c
                  p_gtdata.f
                  area_list.f

/GET_DATA, TYPE = OWNER_LIST

     processed by cmd_parse.c
                  p_gtdata.f
                  owner_list.f

/GET_DATA, TYPE = BUS_EXISTS, BUS = "bus_name"

     processed by cmd_parse.c
                  p_gtdata.f
                  ex_bus.f
     return status: status = 0 : bus does not exist
                             1 : bus exists

/GET_DATA, TYPE = FILE_EXISTS, FILE = <file_name>

     processed by cmd_parse.c
                  p_gtdata.f
                  ex_file.f
     return status: status = 0 : file does not exist
                             1 : file exists
/GET_DATA, TYPE = CONNECTION
B     <busname, etc> returns all connection data associatated with bus

     processed by cmd_parse.c
                  p_gtdata.f
                  ex_file.f
     return status: status = 0 : file does not exist
                             1 : file exists

/GET_DATA, TYPE = ZONE_LIST

     processed by cmd_parse.c
                  p_gtdata.f
                  zone_list.f

/GET_DATA, TYPE = OUTAGES

     processed by cmd_parse.c
                  p_gtdata.f
                  gtoutage.f

/GET_DATA, TYPE = LINE_IMPEDANCE_CALCULATION
         UNITS = < ENGLISH | METRIC >,
         DISTANCE = < miles | km >
         BASEKV = <basekv>,
         BASEMVA = <basemva>,
         FREQUENCY = <freq>

     processed by cmd_parse.c
                  p_gtdata.f
                  p_lic.f
                  linimp.f

/GET_DATA, TYPE = output

     processed by cmd_parse.c
                  p_gtdata.f
                  gtoutput.f

/GET_DATA, TYPE = INITIALIZE_DEF

     processed by cmd_parse.c
                 p_gtdata.f
                 p_initdef.f

/GET_DATA, TYPE = LOAD_DEFINE
> DEFINE ...

     processed by cmd_parse.c
                 p_gtdata.f
                 p_loaddef.f

/GET_DATA, TYPE = SUB_DEFINE, SOURCE = BASE
                                     ALTERNATE_BASE

     processed by cmd_parse.c
                 p_gtdata.f
                 p_subdef.f

/GET_DATA, TYPE = LOAD_AREA

     processed by cmd_parse.c
                  p_gtdata.f
                  p_ldardata.f
     return status: status = 0 : success
                             1 : errors

/GET_DATA, TYPE = AREA_DATA
A  <areaname>

     processed by cmd_parse.c
                  p_gtdata.f
                  gtardata
     return status: status = 0 : success
                             1 : errors

/REPORTS, SELECT BUS_BR_INPUT [ FROM BUS_DATA ]
               [ OUTPUT = <filename> ]
               WHERE (repeat filter from BUS_LIST)

     processed by cmd_parse.c
                 p_report.f
                 busbrinrpt.f
                 gtfltr.f

/REPORTS, SELECT BUS_BR_OUTPUT [ FROM BUS_DATA ]
               [ OUTPUT = <filename> ]
               WHERE (repeat filter from BUS_LIST)

     processed by cmd_parse.c
                 p_report.f
                 busbrotrpt.f
                 gtfltr.f

/REPORTS, SELECT OVERLOADED_LINES [ FROM BUS_DATA ]
               [ OUTPUT = <filename> ]
               WHERE (repeat filter from BUS_LIST)

     processed by cmd_parse.c
                 p_report.f
                 ovldlnsrpt.f
                 gtfltr.f

/REPORTS, SELECT OVERLOADED_TXS [ FROM BUS_DATA ]
               [ OUTPUT = <filename> ]
               WHERE (repeat filter from BUS_LIST)

     processed by cmd_parse.c
                 p_report.f
                 ovldtxsrpt.f
                 gtfltr.f

/REPORTS, SELECT BUS_UVOV [ FROM BUS_DATA ]
               [ OUTPUT = <filename> ]
               WHERE (repeat filter from BUS_LIST)

     processed by cmd_parse.c
                 p_report.f
                 busuvovrpt.f
                 gtfltr.f

/REPORTS, SELECT
        (GUI-customized reports, but not completed!)
     processed by cmd_parse.c
                 p_report.f
                 outputrpt.f
                 gtfltr.f

/NEW_BASE, FILE = <filename>, CASE = <casename>
     processed by cmd_parse.c
                  p_newbse.f
                  ctlpow.f

/QUIT

      processed by p_pfexit_

/EXIT

      processed by p_pfexit_

/CFLOW_GUI

      processed by p_cflow_gui

/INITDEF

      processed by p_initdef_

/LOADDEF

      processed by p_loaddef_

/SUBDEF

     processed by p_subdef_

WSCC Specifications

These functional specifications are here for more historical reasons than present day usefulness but they are from Wester Systems Coordinating Council Load Flow and Stability Computer Programs department. They were used during intial development of IPS.

General, Load Flow, & Stability

  1. WSCC will consider any deviations and alternates of these specifications, provided the details of such deviations and alternates are explained by the supplier.

  2. Load Flow and Stability programs shall be compatible. Load flow shall accept card input or tape input from previous cases. Stability program shall accept load flow output and system data directly from load flow history tape of any case. Load flow and stability shall also run “back-to-back” if desired, that is, stability program run as a continuation of load flow without operator intervention to intiate stability run.

  3. Program shall be written ina standard Fortran language for ease of modification except for relocatable Fortran subroutines.

  4. Programs shall be completely documented including full explanation of theory and equations upon which calculations are based as well as the Fortran listings. Complete users manual and program documentation shall be supplied with delivery of programs. A glossary of terms shall be included in the documentation.

  5. Programs shall be written for computer acceptable to the Coucil.

  6. Reduced computer storage capacity shall result in reduced prgoram limits rather than elimination of program features.

  7. Program features shall not be at the expense of excessive input manipulation or machine time.

  8. Diagnostics shall be provided in program operation to reveal cause of program stoppage or failure to converge. Included in diagnostic shall be maximum real and quadrature components of power and voltage change and names of buses on which they occur. Bus mismatch shall be available as diagnostic at user’s option. Diagnostics shall be available at each iteration at user’s option.

Load Flow Program

  1. System Limits

  1. 2000 buses

  2. 3000 branches, 1000 of which may be transformers with fixed or LTC taps.

  3. 50 phase shifters

  4. 60 interchange control areas.

  5. Voltage at 400 buses controlled remotely by generation or transformer LTC.

  6. 90 loss accumulation areas other than interchange areas.

  7. 10 two-terminal and 5 three-terminal DC lines.

  1. Buses

  1. Machines, loads, shunt capacitors, and shunt reactors shall all be representable separately at each bus.

  2. Loads shall be representable as scheduled mw and mvar.

  3. Shunt admittances shall be representable in per-unit as follows:

  1. Fixed admittance

  2. Switched capacitor in steps with on and off voltages

  3. Switched reactor in steps with on and off voltages

  1. Machines shall be represetable as follows:

  1. Scheduled voltage magnitude and angle (swing).

  2. Scheduled mw and voltage magnitude, with or without mvar limits. In event mvar limit is reached, voltage schedule is no longer held.

  3. Scheduled mw and mvar, with or without voltage limits. In event voltage limit is reached, mvar schedule is no longer held.

  4. Scheduled mw and variable mvar to hold voltage on remote bus. Provision shall be made at 50 voltage controlled buses for the controlling action to be shared in scheduled proportion among the reactive outputs of up to 5 remote machines.

  1. Buses shall be identified by name rather than number. Bus name shall include bus voltage base.

Additional Resources