Voltage Limits and Starting Voltages

The following table allows you to find global and starting voltages for a bus given the base kV and zone. These values are hard-coded in the program and cannot be altered by the user.

Table 80 Global Voltage Limits and Starting Voltages

Base kV Range

Zone

Restrictions

Global V Limits

Starting V

From

To

V_min (p.u.)

V_max (p.u.)

Gen Buses (40%)

Load Buses (20%)

0.1

6.5

0.950

1.052

1.011

1.032

6.6

6.6

M1

0.950

1.065

1.019

1.042

6.6

49.9

0.950

1.052

1.011

1.032

50.0

50.0

16

1.100

1.200

1.160

1.180

50.0

59.9

0.950

1.052

1.011

1.032

60.0

60.0

17

0.950

1.100

1.040

1.070

60.0

62.9

0.950

1.052

1.011

1.032

63.0

63.0

20

0.930

1.080

1.020

1.050

63.0

99.9

0.950

1.052

1.011

1.032

100.0

100.0

16 M5

1.100

1.200

1.160

1.180

100.0

100.0

M4

0.950

1.070

1.022

1.046

100.0

114.9

0.950

1.052

1.011

1.032

115.0

115.0

M4

0.950

1.070

1.022

1.046

115.0

131.9

0.950

1.052

1.011

1.032

132.0

161.0

17 20

0.950

1.090

1.034

1.062

132.0

199.9

0.950

1.052

1.011

1.032

200.0

200.0

16

1.100

1.200

1.160

1.180

200.0

229.9

0.950

1.052

1.011

1.032

230.0

230.0

17 20

0.950

1.070

1.022

1.046

230.0

499.9

0.950

1.052

1.011

1.032

500.0

500.0

1.000

1.100

1.060

1.080

500.1

1099.9

1

0.950

1.052

1.011

1.032

1100.0

1100.0

1

1.000

1.100

1.060

1.080

1100.1

9999.9

1

0.950

1.052

1.011

1.032

Notes

  1. Twenty percent (20%) and forty percent (40%) starting voltages are the percentages from \(V_{max}\) to \(V_{min}\):

\[V_{start} = V_{max} * (1 - \%pct) + V_{min} * \%pct\]

“0%” starts at \(V_{max}\); “100%” starts at \(V_{min}\).

Ideal starting percentages would be a value which lies closest to the final voltages. For peak load cases, a generator percentage of 30% is better; for light loads, 50% is better. The current 40% is a trade-off.

  1. Zone restrictions mean that base kV’s are also subject to zones. If the zone restriction list has nonblank entities, only base kV’s within the range and zone list zones apply. Conversely, if the zone restriction list is blank, then there are no zone restrictions: all base kV’s within the range apply.

  2. To find global and starting voltages for a bus with Base XXX and Zone ZZ, proceed as follows:

  1. Find the encompassing base kV:

    From_base <= XXX <= To_base

    There will be one or more such ranges. Zone restrictions may qualify the base range.

  1. If zone restrictions apply, check whether zone ZZ qualifies. If true, then the pertinent entity has been located.

If false, proceed to the next encompassing base kV and repeat step b. All encompassing base ranges terminate with an inclusive blank zone list, which ultimately defaults to “no restrictions”.